Class: Equipment
The parts of a power system that are physical devices, electronic or mechanical.
URI: cim:Equipment
classDiagram
class Equipment
PowerSystemResource <|-- Equipment
Equipment <|-- ConductingEquipment
Equipment : Equipment.aggregate
Equipment : IdentifiedObject.description
Equipment : IdentifiedObject.energyIdentCodeEic
Equipment : Equipment.EquipmentContainer
Equipment --> EquipmentContainer : Equipment.EquipmentContainer
Equipment : IdentifiedObject.mRID
Equipment : IdentifiedObject.Names
Equipment --> Name : IdentifiedObject.Names
Equipment : Equipment.normallyInService
Equipment : IdentifiedObject.shortName
Inheritance
Slots
Name | Cardinality and Range | Description | Inheritance |
---|---|---|---|
aggregate | 0..1 Boolean |
The aggregate flag provides an alternative way of representing an aggregated ... | direct |
normally_in_service | 0..1 Boolean |
Specifies the availability of the equipment under normal operating conditions | direct |
equipment_container | 0..1 EquipmentContainer |
Container of this equipment | direct |
description | 0..1 String |
The description is a free human readable text describing or naming the object | IdentifiedObject |
energy_ident_code_eic | 0..1 String |
The attribute is used for an exchange of the EIC code (Energy identification ... | IdentifiedObject |
m_rid | 1..1 String |
Master resource identifier issued by a model authority | IdentifiedObject |
short_name | 0..1 String |
The attribute is used for an exchange of a human readable short name with len... | IdentifiedObject |
names | 0..* Name |
All names of this identified object | IdentifiedObject |
Usages
used by | used in | type | used |
---|---|---|---|
VoltageLevel | equipments | range | Equipment |
Bay | equipments | range | Equipment |
Substation | equipments | range | Equipment |
EquipmentContainer | equipments | range | Equipment |
Line | equipments | range | Equipment |
Identifier and Mapping Information
Schema Source
- from schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile
Mappings
Mapping Type | Mapped Value |
---|---|
self | cim:Equipment |
native | this:Equipment |
LinkML Source
Direct
name: Equipment
description: The parts of a power system that are physical devices, electronic or
mechanical.
from_schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile
rank: 1000
is_a: PowerSystemResource
attributes:
aggregate:
name: aggregate
description: "The aggregate flag provides an alternative way of representing an\
\ aggregated (equivalent) element. It is applicable in cases when the dedicated\
\ classes for equivalent equipment do not have all of the attributes necessary\
\ to represent the required level of detail. In case the flag is set to “true”\
\ the single instance of equipment represents multiple pieces of equipment that\
\ have been modelled together as an aggregate equivalent obtained by a network\
\ reduction procedure. Examples would be power transformers or synchronous machines\
\ operating in parallel modelled as a single aggregate power transformer or\
\ aggregate synchronous machine. \nThe attribute is not used for EquivalentBranch,\
\ EquivalentShunt and EquivalentInjection."
from_schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile
rank: 1000
slot_uri: cim:Equipment.aggregate
multivalued: false
domain_of:
- Equipment
range: boolean
required: false
normally_in_service:
name: normally_in_service
description: Specifies the availability of the equipment under normal operating
conditions. True means the equipment is available for topology processing, which
determines if the equipment is energized or not. False means that the equipment
is treated by network applications as if it is not in the model.
from_schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile
rank: 1000
slot_uri: cim:Equipment.normallyInService
multivalued: false
domain_of:
- Equipment
range: boolean
required: false
equipment_container:
name: equipment_container
description: Container of this equipment.
from_schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile
rank: 1000
slot_uri: cim:Equipment.EquipmentContainer
multivalued: false
domain_of:
- Equipment
range: EquipmentContainer
required: false
class_uri: cim:Equipment
Induced
name: Equipment
description: The parts of a power system that are physical devices, electronic or
mechanical.
from_schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile
rank: 1000
is_a: PowerSystemResource
attributes:
aggregate:
name: aggregate
description: "The aggregate flag provides an alternative way of representing an\
\ aggregated (equivalent) element. It is applicable in cases when the dedicated\
\ classes for equivalent equipment do not have all of the attributes necessary\
\ to represent the required level of detail. In case the flag is set to “true”\
\ the single instance of equipment represents multiple pieces of equipment that\
\ have been modelled together as an aggregate equivalent obtained by a network\
\ reduction procedure. Examples would be power transformers or synchronous machines\
\ operating in parallel modelled as a single aggregate power transformer or\
\ aggregate synchronous machine. \nThe attribute is not used for EquivalentBranch,\
\ EquivalentShunt and EquivalentInjection."
from_schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile
rank: 1000
slot_uri: cim:Equipment.aggregate
multivalued: false
alias: aggregate
owner: Equipment
domain_of:
- Equipment
range: boolean
required: false
normally_in_service:
name: normally_in_service
description: Specifies the availability of the equipment under normal operating
conditions. True means the equipment is available for topology processing, which
determines if the equipment is energized or not. False means that the equipment
is treated by network applications as if it is not in the model.
from_schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile
rank: 1000
slot_uri: cim:Equipment.normallyInService
multivalued: false
alias: normally_in_service
owner: Equipment
domain_of:
- Equipment
range: boolean
required: false
equipment_container:
name: equipment_container
description: Container of this equipment.
from_schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile
rank: 1000
slot_uri: cim:Equipment.EquipmentContainer
multivalued: false
alias: equipment_container
owner: Equipment
domain_of:
- Equipment
range: EquipmentContainer
required: false
description:
name: description
description: The description is a free human readable text describing or naming
the object. It may be non unique and may not correlate to a naming hierarchy.
from_schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile
rank: 1000
slot_uri: cim:IdentifiedObject.description
multivalued: false
alias: description
owner: Equipment
domain_of:
- IdentifiedObject
- NameType
- NameTypeAuthority
range: string
required: false
energy_ident_code_eic:
name: energy_ident_code_eic
description: The attribute is used for an exchange of the EIC code (Energy identification
Code). The length of the string is 16 characters as defined by the EIC code.
For details on EIC scheme please refer to ENTSO-E web site.
from_schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile
rank: 1000
slot_uri: eu:IdentifiedObject.energyIdentCodeEic
multivalued: false
alias: energy_ident_code_eic
owner: Equipment
domain_of:
- IdentifiedObject
range: string
required: false
m_rid:
name: m_rid
description: 'Master resource identifier issued by a model authority. The mRID
is unique within an exchange context. Global uniqueness is easily achieved by
using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly
recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is
mapped to rdf:ID or rdf:about attributes that identify CIM object elements.'
from_schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile
rank: 1000
slot_uri: cim:IdentifiedObject.mRID
multivalued: false
alias: m_rid
owner: Equipment
domain_of:
- IdentifiedObject
range: string
required: true
short_name:
name: short_name
description: The attribute is used for an exchange of a human readable short name
with length of the string 12 characters maximum.
from_schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile
rank: 1000
slot_uri: eu:IdentifiedObject.shortName
multivalued: false
alias: short_name
owner: Equipment
domain_of:
- IdentifiedObject
range: string
required: false
names:
name: names
description: All names of this identified object.
from_schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile
rank: 1000
slot_uri: cim:IdentifiedObject.Names
multivalued: true
alias: names
owner: Equipment
domain_of:
- IdentifiedObject
- NameType
range: Name
required: false
class_uri: cim:Equipment