Skip to content

Slot: winding_connection_angle

The phase angle between the in-phase winding and the out-of -phase winding used for creating phase shift. The out-of-phase winding produces what is known as the difference voltage. Setting this angle to 90 degrees is not the same as a symmetrical transformer. The attribute can only be multiples of 30 degrees. The allowed range is -150 degrees to 150 degrees excluding 0.

URI: cim:PhaseTapChangerAsymmetrical.windingConnectionAngle

Applicable Classes

Name Description Modifies Slot
PhaseTapChangerAsymmetrical Describes the tap model for an asymmetrical phase shifting transformer in whi... no

Properties

Identifier and Mapping Information

Schema Source

  • from schema: https://cim.ucaiug.io/ns#TC57CIM

LinkML Source

name: winding_connection_angle
description: The phase angle between the in-phase winding and the out-of -phase winding
  used for creating phase shift. The out-of-phase winding produces what is known as
  the difference voltage.  Setting this angle to 90 degrees is not the same as a symmetrical
  transformer. The attribute can only be multiples of 30 degrees.  The allowed range
  is -150 degrees to 150 degrees excluding 0.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PhaseTapChangerAsymmetrical.windingConnectionAngle
multivalued: false
alias: winding_connection_angle
owner: PhaseTapChangerAsymmetrical
domain_of:
- PhaseTapChangerAsymmetrical
range: AngleDegrees
required: false