Slot: target_deadband
_This is a deadband used with discrete control to avoid excessive update of controls like tap changers and shunt compensator banks while regulating. The units of those appropriate for the mode. The attribute shall be a positive value or zero. If RegulatingControl.discrete is set to "false", the RegulatingControl.targetDeadband is to be ignored. _
Note that for instance, if the targetValue is 100 kV and the targetDeadband is 2 kV the range is from 99 to 101 kV.
URI: cim:RegulatingControl.targetDeadband
Applicable Classes
| Name | Description | Modifies Slot |
|---|---|---|
| TapChangerControl | Describes behaviour specific to tap changers, e | no |
| ShuntCompensatorControl | Distribution capacitor bank control settings | no |
| RegulatingControl | Specifies a set of equipment that works together to control a power system qu... | no |
Properties
- Range: Float
Identifier and Mapping Information
Schema Source
- from schema: https://cim.ucaiug.io/ns#TC57CIM
LinkML Source
name: target_deadband
description: "This is a deadband used with discrete control to avoid excessive update\
\ of controls like tap changers and shunt compensator banks while regulating. The\
\ units of those appropriate for the mode. The attribute shall be a positive value\
\ or zero. If RegulatingControl.discrete is set to \"false\", the RegulatingControl.targetDeadband\
\ is to be ignored.\r\nNote that for instance, if the targetValue is 100 kV and\
\ the targetDeadband is 2 kV the range is from 99 to 101 kV."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:RegulatingControl.targetDeadband
multivalued: false
alias: target_deadband
owner: RegulatingControl
domain_of:
- RegulatingControl
range: float
required: false