Slot: pole_loss_p
_The active power loss at a DC Pole _
_= idleLoss + switchingLoss|Idc| + resitiveLossIdc^2. _
_For lossless operation Pdc=Pac. _
_For rectifier operation with losses Pdc=Pac-lossP. _
_For inverter operation with losses Pdc=Pac+lossP. _
It is converter’s state variable used in power flow. The attribute shall be a positive value.
URI: cim:ACDCConverter.poleLossP
Applicable Classes
| Name | Description | Modifies Slot |
|---|---|---|
| ACDCConverter | A unit with valves for three phases, together with unit control equipment, es... | no |
| CsConverter | DC side of the current source converter (CSC) | no |
| VsConverter | DC side of the voltage source converter (VSC) | no |
Properties
- Range: ActivePower
Identifier and Mapping Information
Schema Source
- from schema: https://cim.ucaiug.io/ns#TC57CIM
LinkML Source
name: pole_loss_p
description: "The active power loss at a DC Pole \r\n= idleLoss + switchingLoss*|Idc|\
\ + resitiveLoss*Idc^2.\r\nFor lossless operation Pdc=Pac.\r\nFor rectifier operation\
\ with losses Pdc=Pac-lossP.\r\nFor inverter operation with losses Pdc=Pac+lossP.\r\
\nIt is converter’s state variable used in power flow. The attribute shall be a\
\ positive value."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ACDCConverter.poleLossP
multivalued: false
alias: pole_loss_p
owner: ACDCConverter
domain_of:
- ACDCConverter
range: ActivePower
required: false