Slot: oscillatory
To prevent some overload of the communication it is sensible to detect and suppress oscillating (fast changing) binary inputs. If a signal changes in a defined time twice in the same direction (from 0 to 1 or from 1 to 0) then oscillation is detected and the detail quality identifier "oscillatory" is set. If it is detected a configured numbers of transient changes could be passed by. In this time the validity status "questionable" is set. If after this defined numbers of changes the signal is still in the oscillating state the value shall be set either to the opposite state of the previous stable value or to a defined default value. In this case the validity status "questionable" is reset and "invalid" is set as long as the signal is oscillating. If it is configured such that no transient changes should be passed by then the validity status "invalid" is set immediately in addition to the detail quality identifier "oscillatory" (used for status information only).
URI: cim:Quality61850.oscillatory
Applicable Classes
| Name | Description | Modifies Slot |
|---|---|---|
| DiscreteMeasurementValueQuality | Measurement quality flags for Discrete Values | no |
| AnalogMeasurementValueQuality | Measurement quality flags for Analog Values | no |
| MeasurementValueQuality | Measurement quality flags | no |
| Quality61850 | Quality flags in this class are as defined in IEC 61850, except for estimator... | no |
Properties
- Range: Boolean
Identifier and Mapping Information
Schema Source
- from schema: https://cim.ucaiug.io/ns#TC57CIM
LinkML Source
name: oscillatory
description: To prevent some overload of the communication it is sensible to detect
and suppress oscillating (fast changing) binary inputs. If a signal changes in a
defined time twice in the same direction (from 0 to 1 or from 1 to 0) then oscillation
is detected and the detail quality identifier "oscillatory" is set. If it is detected
a configured numbers of transient changes could be passed by. In this time the validity
status "questionable" is set. If after this defined numbers of changes the signal
is still in the oscillating state the value shall be set either to the opposite
state of the previous stable value or to a defined default value. In this case the
validity status "questionable" is reset and "invalid" is set as long as the signal
is oscillating. If it is configured such that no transient changes should be passed
by then the validity status "invalid" is set immediately in addition to the detail
quality identifier "oscillatory" (used for status information only).
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Quality61850.oscillatory
multivalued: false
alias: oscillatory
owner: Quality61850
domain_of:
- Quality61850
range: boolean
required: false