To prevent some overload of the communication it is sensible to detect and suppress oscillating (fast changing) binary inputs. If a signal changes in a defined time twice in the same direction (from 0 to 1 or from 1 to 0) then oscillation is detected and the detail quality identifier "oscillatory" is set. If it is detected a configured numbers of transient changes could be passed by. In this time the validity status "questionable" is set. If after this defined numbers of changes the signal is still in the oscillating state the value shall be set either to the opposite state of the previous stable value or to a defined default value. In this case the validity status "questionable" is reset and "invalid" is set as long as the signal is oscillating. If it is configured such that no transient changes should be passed by then the validity status "invalid" is set immediately in addition to the detail quality identifier "oscillatory" (used for status information only).

URI: cim:Quality61850.oscillatory

Applicable Classes

Name Description Modifies Slot
DiscreteMeasurementValueQuality Measurement quality flags for Discrete Values no
AnalogMeasurementValueQuality Measurement quality flags for Analog Values no
MeasurementValueQuality Measurement quality flags no
Quality61850 Quality flags in this class are as defined in IEC 61850, except for estimator... no

Properties

Identifier and Mapping Information

Schema Source

  • from schema: https://cim.ucaiug.io/ns#TC57CIM

LinkML Source

name: oscillatory
description: To prevent some overload of the communication it is sensible to detect
  and suppress oscillating (fast changing) binary inputs. If a signal changes in a
  defined time twice in the same direction (from 0 to 1 or from 1 to 0) then oscillation
  is detected and the detail quality identifier "oscillatory" is set. If it is detected
  a configured numbers of transient changes could be passed by. In this time the validity
  status "questionable" is set. If after this defined numbers of changes the signal
  is still in the oscillating state the value shall be set either to the opposite
  state of the previous stable value or to a defined default value. In this case the
  validity status "questionable" is reset and "invalid" is set as long as the signal
  is oscillating. If it is configured such that no transient changes should be passed
  by then the validity status "invalid" is set immediately in addition to the detail
  quality identifier "oscillatory" (used for status information only).
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Quality61850.oscillatory
multivalued: false
alias: oscillatory
owner: Quality61850
domain_of:
- Quality61850
range: boolean
required: false