Slot: line_discharge_class
Determines the arrester energy discharge capability. Choices are limited to 0 (none) through 5 (highest) by IEC 60099. Classes 1..3 require a 10-kA nominal discharge current. Classes 4..5 require a 20-kA nominal discharge current. Lower nominal discharge currents must use class 0.
URI: cim:SurgeArresterInfo.lineDischargeClass
Applicable Classes
| Name | Description | Modifies Slot |
|---|---|---|
| SurgeArresterInfo | Properties of surge arrester | no |
Properties
- Range: Integer
Identifier and Mapping Information
Schema Source
- from schema: https://cim.ucaiug.io/ns#TC57CIM
LinkML Source
name: line_discharge_class
description: Determines the arrester energy discharge capability. Choices are limited
to 0 (none) through 5 (highest) by IEC 60099. Classes 1..3 require a 10-kA nominal
discharge current. Classes 4..5 require a 20-kA nominal discharge current. Lower
nominal discharge currents must use class 0.