Skip to content

Class: SynchronousMachineTimeConstantReactance

Synchronous machine detailed modelling types are defined by the combination of the attributes SynchronousMachineTimeConstantReactance.modelType and SynchronousMachineTimeConstantReactance.rotorType.

_Parameter details: _

_

    _

_

  • The “p” in the time-related attribute names is a substitution for a “prime” in the usual parameter notation, e.g. tpdo refers to T'do.
  • _

    _

  • The parameters used for models expressed in time constant reactance form include:
  • _

    _ _

    _- RotatingMachine.ratedS (MVAbase); _

    _- RotatingMachineDynamics.damping (D); _

    _- RotatingMachineDynamics.inertia (H); _

    _- RotatingMachineDynamics.saturationFactor (S1); _

    _- RotatingMachineDynamics.saturationFactor120 (S12); _

    _- RotatingMachineDynamics.statorLeakageReactance (Xl); _

    _- RotatingMachineDynamics.statorResistance (Rs); _

    _- SynchronousMachineTimeConstantReactance.ks (Ks); _

    _- SynchronousMachineDetailed.saturationFactorQAxis (S1q); _

    _- SynchronousMachineDetailed.saturationFactor120QAxis (S12q); _

    _- SynchronousMachineDetailed.efdBaseRatio; _

    _- SynchronousMachineDetailed.ifdBaseType; _

    _- .xDirectSync (Xd); _

    _- .xDirectTrans (X'd); _

    _- .xDirectSubtrans (X''d); _

    _- .xQuadSync (Xq); _

    _- .xQuadTrans (X'q); _

    _- .xQuadSubtrans (X''q); _

    _- .tpdo (T'do); _

    _- .tppdo (T''do); _

    _- .tpqo (T'qo); _

    _- .tppqo (T''qo); _

    - .tc.

    URI: cim:SynchronousMachineTimeConstantReactance

     classDiagram
        class SynchronousMachineTimeConstantReactance
          SynchronousMachineDetailed <|-- SynchronousMachineTimeConstantReactance
    
          SynchronousMachineTimeConstantReactance : alias_name
    
          SynchronousMachineTimeConstantReactance : cross_compound_turbine_governor_dyanmics
    
              SynchronousMachineTimeConstantReactance --> CrossCompoundTurbineGovernorDynamics : cross_compound_turbine_governor_dyanmics
    
          SynchronousMachineTimeConstantReactance : cross_compound_turbine_governor_dynamics
    
              SynchronousMachineTimeConstantReactance --> CrossCompoundTurbineGovernorDynamics : cross_compound_turbine_governor_dynamics
    
          SynchronousMachineTimeConstantReactance : damping
    
          SynchronousMachineTimeConstantReactance : description
    
          SynchronousMachineTimeConstantReactance : diagram_objects
    
              SynchronousMachineTimeConstantReactance --> DiagramObject : diagram_objects
    
          SynchronousMachineTimeConstantReactance : efd_base_ratio
    
          SynchronousMachineTimeConstantReactance : enabled
    
          SynchronousMachineTimeConstantReactance : excitation_system_dynamics
    
              SynchronousMachineTimeConstantReactance --> ExcitationSystemDynamics : excitation_system_dynamics
    
          SynchronousMachineTimeConstantReactance : gen_icompensation_for_gen_j
    
              SynchronousMachineTimeConstantReactance --> GenICompensationForGenJ : gen_icompensation_for_gen_j
    
          SynchronousMachineTimeConstantReactance : ifd_base_type
    
              SynchronousMachineTimeConstantReactance --> IfdBaseKind : ifd_base_type
    
          SynchronousMachineTimeConstantReactance : inertia
    
              SynchronousMachineTimeConstantReactance --> Seconds : inertia
    
          SynchronousMachineTimeConstantReactance : instance_set
    
              SynchronousMachineTimeConstantReactance --> InstanceSet : instance_set
    
          SynchronousMachineTimeConstantReactance : ks
    
          SynchronousMachineTimeConstantReactance : m_rid
    
          SynchronousMachineTimeConstantReactance : mechanical_load_dynamics
    
              SynchronousMachineTimeConstantReactance --> MechanicalLoadDynamics : mechanical_load_dynamics
    
          SynchronousMachineTimeConstantReactance : model_type
    
              SynchronousMachineTimeConstantReactance --> SynchronousMachineModelKind : model_type
    
          SynchronousMachineTimeConstantReactance : names
    
              SynchronousMachineTimeConstantReactance --> Name : names
    
          SynchronousMachineTimeConstantReactance : properties_cimdata_object
    
              SynchronousMachineTimeConstantReactance --> ChangeSetMember : properties_cimdata_object
    
          SynchronousMachineTimeConstantReactance : rotor_type
    
              SynchronousMachineTimeConstantReactance --> RotorKind : rotor_type
    
          SynchronousMachineTimeConstantReactance : saturation_factor
    
          SynchronousMachineTimeConstantReactance : saturation_factor___qaxis
    
          SynchronousMachineTimeConstantReactance : saturation_factor_qaxis
    
          SynchronousMachineTimeConstantReactance : stator_leakage_reactance
    
              SynchronousMachineTimeConstantReactance --> PU : stator_leakage_reactance
    
          SynchronousMachineTimeConstantReactance : stator_resistance
    
              SynchronousMachineTimeConstantReactance --> PU : stator_resistance
    
          SynchronousMachineTimeConstantReactance : synchronous_machine
    
              SynchronousMachineTimeConstantReactance --> SynchronousMachine : synchronous_machine
    
          SynchronousMachineTimeConstantReactance : targeting_cimdata_object
    
              SynchronousMachineTimeConstantReactance --> ChangeSetMember : targeting_cimdata_object
    
          SynchronousMachineTimeConstantReactance : tc
    
              SynchronousMachineTimeConstantReactance --> Seconds : tc
    
          SynchronousMachineTimeConstantReactance : tpdo
    
              SynchronousMachineTimeConstantReactance --> Seconds : tpdo
    
          SynchronousMachineTimeConstantReactance : tppdo
    
              SynchronousMachineTimeConstantReactance --> Seconds : tppdo
    
          SynchronousMachineTimeConstantReactance : tppqo
    
              SynchronousMachineTimeConstantReactance --> Seconds : tppqo
    
          SynchronousMachineTimeConstantReactance : tpqo
    
              SynchronousMachineTimeConstantReactance --> Seconds : tpqo
    
          SynchronousMachineTimeConstantReactance : turbine_governor_dynamics
    
              SynchronousMachineTimeConstantReactance --> TurbineGovernorDynamics : turbine_governor_dynamics
    
          SynchronousMachineTimeConstantReactance : x_direct_subtrans
    
              SynchronousMachineTimeConstantReactance --> PU : x_direct_subtrans
    
          SynchronousMachineTimeConstantReactance : x_direct_sync
    
              SynchronousMachineTimeConstantReactance --> PU : x_direct_sync
    
          SynchronousMachineTimeConstantReactance : x_direct_trans
    
              SynchronousMachineTimeConstantReactance --> PU : x_direct_trans
    
          SynchronousMachineTimeConstantReactance : x_quad_subtrans
    
              SynchronousMachineTimeConstantReactance --> PU : x_quad_subtrans
    
          SynchronousMachineTimeConstantReactance : x_quad_sync
    
              SynchronousMachineTimeConstantReactance --> PU : x_quad_sync
    
          SynchronousMachineTimeConstantReactance : x_quad_trans
    
              SynchronousMachineTimeConstantReactance --> PU : x_quad_trans
    
    

    Inheritance

    Slots

    Name Cardinality and Range Description Inheritance
    ks 0..1
    Float
    Saturation loading correction factor (Ks) (>= 0) direct
    model_type 0..1
    SynchronousMachineModelKind
    Type of synchronous machine model used in dynamic simulation applications direct
    rotor_type 0..1
    RotorKind
    Type of rotor on physical machine direct
    tc 0..1
    Seconds
    Damping time constant for “Canay” reactance (>= 0) direct
    tpdo 0..1
    Seconds
    Direct-axis transient rotor time constant (T'do) (> SynchronousMach... direct
    tppdo 0..1
    Seconds
    Direct-axis subtransient rotor time constant (T''do) (> 0) direct
    tppqo 0..1
    Seconds
    Quadrature-axis subtransient rotor time constant (T''qo) (> 0) direct
    tpqo 0..1
    Seconds
    Quadrature-axis transient rotor time constant (T'qo) (> Synchronous... direct
    x_direct_subtrans 0..1
    PU
    Direct-axis subtransient reactance (unsaturated) (X''d) (> Rotating... direct
    x_direct_sync 0..1
    PU
    Direct-axis synchronous reactance (Xd) (>= SynchronousMachineTimeCo... direct
    x_direct_trans 0..1
    PU
    Direct-axis transient reactance (unsaturated) (X'd) (>= Synchronous... direct
    x_quad_subtrans 0..1
    PU
    Quadrature-axis subtransient reactance (X''q) (> RotatingMachineDyn... direct
    x_quad_sync 0..1
    PU
    Quadrature-axis synchronous reactance (Xq) (>= SynchronousMachineTi... direct
    x_quad_trans 0..1
    PU
    Quadrature-axis transient reactance (X'q) (>= SynchronousMachineTim... direct
    efd_base_ratio 0..1
    Float
    Ratio (exciter voltage/generator voltage) of Efd bases of exciter and ... SynchronousMachineDetailed
    ifd_base_type 0..1
    IfdBaseKind
    Excitation base system mode SynchronousMachineDetailed
    saturation_factor___qaxis 0..1
    Float
    Quadrature-axis saturation factor at 120% of rated terminal voltage (S12q<... SynchronousMachineDetailed
    saturation_factor_qaxis 0..1
    Float
    Quadrature-axis saturation factor at rated terminal voltage (S1q) (&gt... SynchronousMachineDetailed
    synchronous_machine 1..1
    SynchronousMachine
    Synchronous machine to which synchronous machine dynamics model applies SynchronousMachineDynamics
    turbine_governor_dynamics 0..*
    TurbineGovernorDynamics
    Turbine-governor model associated with this synchronous machine model SynchronousMachineDynamics
    gen_icompensation_for_gen_j 0..*
    GenICompensationForGenJ
    Compensation of voltage compensator's generator for current flow out of this ... SynchronousMachineDynamics
    excitation_system_dynamics 0..1
    ExcitationSystemDynamics
    Excitation system model associated with this synchronous machine model SynchronousMachineDynamics
    cross_compound_turbine_governor_dynamics 0..1
    CrossCompoundTurbineGovernorDynamics
    The cross-compound turbine governor with which this low-pressure synchronous ... SynchronousMachineDynamics
    cross_compound_turbine_governor_dyanmics 0..1
    CrossCompoundTurbineGovernorDynamics
    The cross-compound turbine governor with which this high-pressure synchronous... SynchronousMachineDynamics
    mechanical_load_dynamics 0..1
    MechanicalLoadDynamics
    Mechanical load model associated with this synchronous machine model SynchronousMachineDynamics
    damping 0..1
    Float
    Damping torque coefficient (D) (>= 0) RotatingMachineDynamics
    inertia 0..1
    Seconds
    Inertia constant of generator or motor and mechanical load (H) (> 0... RotatingMachineDynamics
    saturation_factor 0..1
    Float
    Saturation factor at 120% of rated terminal voltage (S12) (>= Rotat... RotatingMachineDynamics
    stator_leakage_reactance 0..1
    PU
    Stator leakage reactance (Xl) (>= 0) RotatingMachineDynamics
    stator_resistance 0..1
    PU
    Stator (armature) resistance (Rs) (>= 0) RotatingMachineDynamics
    enabled 0..1
    Boolean
    Function block used indicator DynamicsFunctionBlock
    alias_name 0..1
    String
    The aliasName is free text human readable name of the object alternative to I... IdentifiedObject
    description 0..1
    String
    The description is a free human readable text describing or naming the object IdentifiedObject
    m_rid 0..1
    String
    Master resource identifier issued by a model authority IdentifiedObject
    diagram_objects 0..*
    DiagramObject
    The diagram objects that are associated with the domain object IdentifiedObject
    instance_set 1..1
    InstanceSet
    Dataset containing the data objects IdentifiedObject
    names 0..*
    Name
    All names of this identified object IdentifiedObject
    properties_cimdata_object 0..1
    ChangeSetMember
    The single CIM data object in the appropriate dataset context IdentifiedObject
    targeting_cimdata_object 0..*
    ChangeSetMember
    Data objects registered IdentifiedObject

    Identifier and Mapping Information

    Schema Source

    • from schema: https://cim.ucaiug.io/ns#TC57CIM

    Mappings

    Mapping Type Mapped Value
    self cim:SynchronousMachineTimeConstantReactance
    native cim:SynchronousMachineTimeConstantReactance

    LinkML Source

    Direct

    name: SynchronousMachineTimeConstantReactance
    description: "Synchronous machine detailed modelling types are defined by the combination\
      \ of the attributes SynchronousMachineTimeConstantReactance.modelType and SynchronousMachineTimeConstantReactance.rotorType.\
      \  \r\nParameter details:\r\n<ol>\r\n\t<li>The “p” in the time-related attribute\
      \ names is a substitution for a “prime” in the usual parameter notation, e.g. tpdo\
      \ refers to <i>T'do</i>.</li>\r\n\t<li>The parameters used for models expressed\
      \ in time constant reactance form include:</li>\r\n</ol>\r\n- RotatingMachine.ratedS\
      \ (<i>MVAbase</i>);\r\n- RotatingMachineDynamics.damping (<i>D</i>);\r\n- RotatingMachineDynamics.inertia\
      \ (<i>H</i>);\r\n- RotatingMachineDynamics.saturationFactor (<i>S1</i>);\r\n- RotatingMachineDynamics.saturationFactor120\
      \ (<i>S12</i>);\r\n- RotatingMachineDynamics.statorLeakageReactance (<i>Xl</i>);\r\
      \n- RotatingMachineDynamics.statorResistance (<i>Rs</i>);\r\n- SynchronousMachineTimeConstantReactance.ks\
      \ (<i>Ks</i>);\r\n- SynchronousMachineDetailed.saturationFactorQAxis (<i>S1q</i>);\r\
      \n- SynchronousMachineDetailed.saturationFactor120QAxis (<i>S12q</i>);\r\n- SynchronousMachineDetailed.efdBaseRatio;\r\
      \n- SynchronousMachineDetailed.ifdBaseType;\r\n- .xDirectSync (<i>Xd</i>);\r\n-\
      \ .xDirectTrans (<i>X'd</i>);\r\n- .xDirectSubtrans (<i>X''d</i>);\r\n- .xQuadSync\
      \ (<i>Xq</i>);\r\n- .xQuadTrans (<i>X'q</i>);\r\n- .xQuadSubtrans (<i>X''q</i>);\r\
      \n- .tpdo (<i>T'do</i>);\r\n- .tppdo (<i>T''do</i>);\r\n- .tpqo (<i>T'qo</i>);\r\
      \n- .tppqo (<i>T''qo</i>);\r\n- .tc."
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    is_a: SynchronousMachineDetailed
    attributes:
      ks:
        name: ks
        description: Saturation loading correction factor (<i>Ks</i>) (&gt;= 0).  Used
          only by type J model.  Typical value = 0.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.ks
        multivalued: false
        domain_of:
        - SynchronousMachineTimeConstantReactance
        - GovSteamBB
        - ExcAC1A
        - ExcAC2A
        - ExcAC3A
        - ExcAC5A
        - ExcAC6A
        - ExcAC8B
        - ExcDC1A
        - ExcDC2A
        - ExcDC3A
        - ExcELIN1
        - ExcREXS
        - ExcST3A
        - PssIEEE1A
        - PssIEEE2B
        - PssIEEE3B
        - Pss1
        - Pss1A
        - Pss2B
        - PssELIN2
        range: float
        required: false
      model_type:
        name: model_type
        description: Type of synchronous machine model used in dynamic simulation applications.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.modelType
        multivalued: false
        domain_of:
        - SynchronousMachineTimeConstantReactance
        range: SynchronousMachineModelKind
        required: false
      rotor_type:
        name: rotor_type
        description: Type of rotor on physical machine.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.rotorType
        multivalued: false
        domain_of:
        - SynchronousMachineTimeConstantReactance
        range: RotorKind
        required: false
      tc:
        name: tc
        description: Damping time constant for “Canay” reactance (&gt;= 0).  Typical value
          = 0.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.tc
        multivalued: false
        domain_of:
        - SynchronousMachineTimeConstantReactance
        - GovCT1
        - GovCT2
        - GovGAST2
        - GovGAST3
        - GovGAST4
        - GovGASTWD
        - GovSteamFV2
        - GovSteamFV3
        - GovSteamFV4
        - ExcIEEEAC1A
        - ExcIEEEAC2A
        - ExcIEEEAC3A
        - ExcIEEEAC4A
        - ExcIEEEAC6A
        - ExcIEEEDC1A
        - ExcIEEEDC2A
        - ExcIEEEST1A
        - ExcIEEEST3A
        - ExcIEEEST5B
        - ExcIEEEST7B
        - ExcAC1A
        - ExcAC2A
        - ExcAC3A
        - ExcAC4A
        - ExcAC5A
        - ExcAC6A
        - ExcCZ
        - ExcDC1A
        - ExcDC2A
        - ExcREXS
        - ExcRQB
        - ExcSEXS
        - ExcSK
        - ExcST1A
        - ExcST2A
        - ExcST3A
        - ExcST7B
        - PssSB4
        range: Seconds
        required: false
      tpdo:
        name: tpdo
        description: Direct-axis transient rotor time constant (<i>T'do</i>) (&gt; SynchronousMachineTimeConstantReactance.tppdo).  Typical
          value = 5.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.tpdo
        multivalued: false
        domain_of:
        - SynchronousMachineTimeConstantReactance
        range: Seconds
        required: false
      tppdo:
        name: tppdo
        description: Direct-axis subtransient rotor time constant (<i>T''do</i>) (&gt;
          0).  Typical value = 0,03.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.tppdo
        multivalued: false
        domain_of:
        - SynchronousMachineTimeConstantReactance
        range: Seconds
        required: false
      tppqo:
        name: tppqo
        description: Quadrature-axis subtransient rotor time constant (<i>T''qo</i>) (&gt;
          0). Typical value = 0,03.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.tppqo
        multivalued: false
        domain_of:
        - SynchronousMachineTimeConstantReactance
        range: Seconds
        required: false
      tpqo:
        name: tpqo
        description: Quadrature-axis transient rotor time constant (<i>T'qo</i>) (&gt;
          SynchronousMachineTimeConstantReactance.tppqo). Typical value = 0,5.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.tpqo
        multivalued: false
        domain_of:
        - SynchronousMachineTimeConstantReactance
        range: Seconds
        required: false
      x_direct_subtrans:
        name: x_direct_subtrans
        description: Direct-axis subtransient reactance (unsaturated) (<i>X''d</i>) (&gt;
          RotatingMachineDynamics.statorLeakageReactance).  Typical value = 0,2.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.xDirectSubtrans
        multivalued: false
        domain_of:
        - SynchronousMachineTimeConstantReactance
        - GeneratorTypeAsset
        range: PU
        required: false
      x_direct_sync:
        name: x_direct_sync
        description: Direct-axis synchronous reactance (<i>Xd</i>) (&gt;= SynchronousMachineTimeConstantReactance.xDirectTrans).
          The quotient of a sustained value of that AC component of armature voltage that
          is produced by the total direct-axis flux due to direct-axis armature current
          and the value of the AC component of this current, the machine running at rated
          speed.  Typical value = 1,8.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.xDirectSync
        multivalued: false
        domain_of:
        - SynchronousMachineTimeConstantReactance
        - GeneratorTypeAsset
        range: PU
        required: false
      x_direct_trans:
        name: x_direct_trans
        description: Direct-axis transient reactance (unsaturated) (<i>X'd</i>) (&gt;=
          SynchronousMachineTimeConstantReactance.xDirectSubtrans).  Typical value = 0,5.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.xDirectTrans
        multivalued: false
        domain_of:
        - SynchronousMachineTimeConstantReactance
        - GeneratorTypeAsset
        range: PU
        required: false
      x_quad_subtrans:
        name: x_quad_subtrans
        description: Quadrature-axis subtransient reactance (<i>X''q</i>) (&gt; RotatingMachineDynamics.statorLeakageReactance).  Typical
          value = 0,2.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.xQuadSubtrans
        multivalued: false
        domain_of:
        - SynchronousMachineTimeConstantReactance
        - GeneratorTypeAsset
        range: PU
        required: false
      x_quad_sync:
        name: x_quad_sync
        description: "Quadrature-axis synchronous reactance (<i>Xq</i>) (&gt;= SynchronousMachineTimeConstantReactance.xQuadTrans).\r\
          \nThe ratio of the component of reactive armature voltage, due to the quadrature-axis\
          \ component of armature current, to this component of current, under steady\
          \ state conditions and at rated frequency.  Typical value = 1,6."
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.xQuadSync
        multivalued: false
        domain_of:
        - SynchronousMachineTimeConstantReactance
        - GeneratorTypeAsset
        range: PU
        required: false
      x_quad_trans:
        name: x_quad_trans
        description: Quadrature-axis transient reactance (<i>X'q</i>) (&gt;= SynchronousMachineTimeConstantReactance.xQuadSubtrans).  Typical
          value = 0,3.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.xQuadTrans
        multivalued: false
        domain_of:
        - SynchronousMachineTimeConstantReactance
        - GeneratorTypeAsset
        range: PU
        required: false
    class_uri: cim:SynchronousMachineTimeConstantReactance
    

    Induced

    name: SynchronousMachineTimeConstantReactance
    description: "Synchronous machine detailed modelling types are defined by the combination\
      \ of the attributes SynchronousMachineTimeConstantReactance.modelType and SynchronousMachineTimeConstantReactance.rotorType.\
      \  \r\nParameter details:\r\n<ol>\r\n\t<li>The “p” in the time-related attribute\
      \ names is a substitution for a “prime” in the usual parameter notation, e.g. tpdo\
      \ refers to <i>T'do</i>.</li>\r\n\t<li>The parameters used for models expressed\
      \ in time constant reactance form include:</li>\r\n</ol>\r\n- RotatingMachine.ratedS\
      \ (<i>MVAbase</i>);\r\n- RotatingMachineDynamics.damping (<i>D</i>);\r\n- RotatingMachineDynamics.inertia\
      \ (<i>H</i>);\r\n- RotatingMachineDynamics.saturationFactor (<i>S1</i>);\r\n- RotatingMachineDynamics.saturationFactor120\
      \ (<i>S12</i>);\r\n- RotatingMachineDynamics.statorLeakageReactance (<i>Xl</i>);\r\
      \n- RotatingMachineDynamics.statorResistance (<i>Rs</i>);\r\n- SynchronousMachineTimeConstantReactance.ks\
      \ (<i>Ks</i>);\r\n- SynchronousMachineDetailed.saturationFactorQAxis (<i>S1q</i>);\r\
      \n- SynchronousMachineDetailed.saturationFactor120QAxis (<i>S12q</i>);\r\n- SynchronousMachineDetailed.efdBaseRatio;\r\
      \n- SynchronousMachineDetailed.ifdBaseType;\r\n- .xDirectSync (<i>Xd</i>);\r\n-\
      \ .xDirectTrans (<i>X'd</i>);\r\n- .xDirectSubtrans (<i>X''d</i>);\r\n- .xQuadSync\
      \ (<i>Xq</i>);\r\n- .xQuadTrans (<i>X'q</i>);\r\n- .xQuadSubtrans (<i>X''q</i>);\r\
      \n- .tpdo (<i>T'do</i>);\r\n- .tppdo (<i>T''do</i>);\r\n- .tpqo (<i>T'qo</i>);\r\
      \n- .tppqo (<i>T''qo</i>);\r\n- .tc."
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    is_a: SynchronousMachineDetailed
    attributes:
      ks:
        name: ks
        description: Saturation loading correction factor (<i>Ks</i>) (&gt;= 0).  Used
          only by type J model.  Typical value = 0.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.ks
        multivalued: false
        alias: ks
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineTimeConstantReactance
        - GovSteamBB
        - ExcAC1A
        - ExcAC2A
        - ExcAC3A
        - ExcAC5A
        - ExcAC6A
        - ExcAC8B
        - ExcDC1A
        - ExcDC2A
        - ExcDC3A
        - ExcELIN1
        - ExcREXS
        - ExcST3A
        - PssIEEE1A
        - PssIEEE2B
        - PssIEEE3B
        - Pss1
        - Pss1A
        - Pss2B
        - PssELIN2
        range: float
        required: false
      model_type:
        name: model_type
        description: Type of synchronous machine model used in dynamic simulation applications.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.modelType
        multivalued: false
        alias: model_type
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineTimeConstantReactance
        range: SynchronousMachineModelKind
        required: false
      rotor_type:
        name: rotor_type
        description: Type of rotor on physical machine.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.rotorType
        multivalued: false
        alias: rotor_type
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineTimeConstantReactance
        range: RotorKind
        required: false
      tc:
        name: tc
        description: Damping time constant for “Canay” reactance (&gt;= 0).  Typical value
          = 0.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.tc
        multivalued: false
        alias: tc
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineTimeConstantReactance
        - GovCT1
        - GovCT2
        - GovGAST2
        - GovGAST3
        - GovGAST4
        - GovGASTWD
        - GovSteamFV2
        - GovSteamFV3
        - GovSteamFV4
        - ExcIEEEAC1A
        - ExcIEEEAC2A
        - ExcIEEEAC3A
        - ExcIEEEAC4A
        - ExcIEEEAC6A
        - ExcIEEEDC1A
        - ExcIEEEDC2A
        - ExcIEEEST1A
        - ExcIEEEST3A
        - ExcIEEEST5B
        - ExcIEEEST7B
        - ExcAC1A
        - ExcAC2A
        - ExcAC3A
        - ExcAC4A
        - ExcAC5A
        - ExcAC6A
        - ExcCZ
        - ExcDC1A
        - ExcDC2A
        - ExcREXS
        - ExcRQB
        - ExcSEXS
        - ExcSK
        - ExcST1A
        - ExcST2A
        - ExcST3A
        - ExcST7B
        - PssSB4
        range: Seconds
        required: false
      tpdo:
        name: tpdo
        description: Direct-axis transient rotor time constant (<i>T'do</i>) (&gt; SynchronousMachineTimeConstantReactance.tppdo).  Typical
          value = 5.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.tpdo
        multivalued: false
        alias: tpdo
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineTimeConstantReactance
        range: Seconds
        required: false
      tppdo:
        name: tppdo
        description: Direct-axis subtransient rotor time constant (<i>T''do</i>) (&gt;
          0).  Typical value = 0,03.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.tppdo
        multivalued: false
        alias: tppdo
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineTimeConstantReactance
        range: Seconds
        required: false
      tppqo:
        name: tppqo
        description: Quadrature-axis subtransient rotor time constant (<i>T''qo</i>) (&gt;
          0). Typical value = 0,03.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.tppqo
        multivalued: false
        alias: tppqo
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineTimeConstantReactance
        range: Seconds
        required: false
      tpqo:
        name: tpqo
        description: Quadrature-axis transient rotor time constant (<i>T'qo</i>) (&gt;
          SynchronousMachineTimeConstantReactance.tppqo). Typical value = 0,5.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.tpqo
        multivalued: false
        alias: tpqo
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineTimeConstantReactance
        range: Seconds
        required: false
      x_direct_subtrans:
        name: x_direct_subtrans
        description: Direct-axis subtransient reactance (unsaturated) (<i>X''d</i>) (&gt;
          RotatingMachineDynamics.statorLeakageReactance).  Typical value = 0,2.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.xDirectSubtrans
        multivalued: false
        alias: x_direct_subtrans
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineTimeConstantReactance
        - GeneratorTypeAsset
        range: PU
        required: false
      x_direct_sync:
        name: x_direct_sync
        description: Direct-axis synchronous reactance (<i>Xd</i>) (&gt;= SynchronousMachineTimeConstantReactance.xDirectTrans).
          The quotient of a sustained value of that AC component of armature voltage that
          is produced by the total direct-axis flux due to direct-axis armature current
          and the value of the AC component of this current, the machine running at rated
          speed.  Typical value = 1,8.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.xDirectSync
        multivalued: false
        alias: x_direct_sync
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineTimeConstantReactance
        - GeneratorTypeAsset
        range: PU
        required: false
      x_direct_trans:
        name: x_direct_trans
        description: Direct-axis transient reactance (unsaturated) (<i>X'd</i>) (&gt;=
          SynchronousMachineTimeConstantReactance.xDirectSubtrans).  Typical value = 0,5.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.xDirectTrans
        multivalued: false
        alias: x_direct_trans
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineTimeConstantReactance
        - GeneratorTypeAsset
        range: PU
        required: false
      x_quad_subtrans:
        name: x_quad_subtrans
        description: Quadrature-axis subtransient reactance (<i>X''q</i>) (&gt; RotatingMachineDynamics.statorLeakageReactance).  Typical
          value = 0,2.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.xQuadSubtrans
        multivalued: false
        alias: x_quad_subtrans
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineTimeConstantReactance
        - GeneratorTypeAsset
        range: PU
        required: false
      x_quad_sync:
        name: x_quad_sync
        description: "Quadrature-axis synchronous reactance (<i>Xq</i>) (&gt;= SynchronousMachineTimeConstantReactance.xQuadTrans).\r\
          \nThe ratio of the component of reactive armature voltage, due to the quadrature-axis\
          \ component of armature current, to this component of current, under steady\
          \ state conditions and at rated frequency.  Typical value = 1,6."
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.xQuadSync
        multivalued: false
        alias: x_quad_sync
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineTimeConstantReactance
        - GeneratorTypeAsset
        range: PU
        required: false
      x_quad_trans:
        name: x_quad_trans
        description: Quadrature-axis transient reactance (<i>X'q</i>) (&gt;= SynchronousMachineTimeConstantReactance.xQuadSubtrans).  Typical
          value = 0,3.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineTimeConstantReactance.xQuadTrans
        multivalued: false
        alias: x_quad_trans
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineTimeConstantReactance
        - GeneratorTypeAsset
        range: PU
        required: false
      efd_base_ratio:
        name: efd_base_ratio
        description: Ratio (exciter voltage/generator voltage) of <i>Efd</i> bases of
          exciter and generator models (&gt; 0). Typical value = 1.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineDetailed.efdBaseRatio
        multivalued: false
        alias: efd_base_ratio
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineDetailed
        range: float
        required: false
      ifd_base_type:
        name: ifd_base_type
        description: 'Excitation base system mode. It should be equal to the value of
          <i>WLMDV</i> given by the user. <i>WLMDV</i> is the PU ratio between the field
          voltage and the excitation current: <i>Efd</i> = <i>WLMDV</i> x <i>Ifd</i>.
          Typical value = ifag.'
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineDetailed.ifdBaseType
        multivalued: false
        alias: ifd_base_type
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineDetailed
        range: IfdBaseKind
        required: false
      saturation_factor___qaxis:
        name: saturation_factor___qaxis
        description: Quadrature-axis saturation factor at 120% of rated terminal voltage
          (<i>S12q</i>) (&gt;= SynchonousMachineDetailed.saturationFactorQAxis).  Typical
          value = 0,12.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineDetailed.saturationFactor120QAxis
        multivalued: false
        alias: saturation_factor___qaxis
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineDetailed
        range: float
        required: false
      saturation_factor_qaxis:
        name: saturation_factor_qaxis
        description: Quadrature-axis saturation factor at rated terminal voltage (<i>S1q</i>)
          (&gt;= 0). Typical value = 0,02.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineDetailed.saturationFactorQAxis
        multivalued: false
        alias: saturation_factor_qaxis
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineDetailed
        range: float
        required: false
      synchronous_machine:
        name: synchronous_machine
        description: Synchronous machine to which synchronous machine dynamics model applies.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineDynamics.SynchronousMachine
        multivalued: false
        alias: synchronous_machine
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineDynamics
        range: SynchronousMachine
        required: true
      turbine_governor_dynamics:
        name: turbine_governor_dynamics
        description: Turbine-governor model associated with this synchronous machine model.
          Multiplicity of greater than one is intended to support hydro units that have
          multiple turbines on one generator.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineDynamics.TurbineGovernorDynamics
        multivalued: true
        alias: turbine_governor_dynamics
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineDynamics
        - AsynchronousMachineDynamics
        - TurbineLoadControllerDynamics
        range: TurbineGovernorDynamics
        required: false
      gen_icompensation_for_gen_j:
        name: gen_icompensation_for_gen_j
        description: Compensation of voltage compensator's generator for current flow
          out of this  generator.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineDynamics.GenICompensationForGenJ
        multivalued: true
        alias: gen_icompensation_for_gen_j
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineDynamics
        - VCompIEEEType2
        range: GenICompensationForGenJ
        required: false
      excitation_system_dynamics:
        name: excitation_system_dynamics
        description: Excitation system model associated with this synchronous machine
          model.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineDynamics.ExcitationSystemDynamics
        multivalued: false
        alias: excitation_system_dynamics
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineDynamics
        - VoltageCompensatorDynamics
        - PowerSystemStabilizerDynamics
        - UnderexcitationLimiterDynamics
        - DiscontinuousExcitationControlDynamics
        - PFVArControllerType1Dynamics
        - OverexcitationLimiterDynamics
        - PFVArControllerType2Dynamics
        range: ExcitationSystemDynamics
        required: false
      cross_compound_turbine_governor_dynamics:
        name: cross_compound_turbine_governor_dynamics
        description: The cross-compound turbine governor with which this low-pressure
          synchronous machine is associated.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineDynamics.CrossCompoundTurbineGovernorDynamics
        multivalued: false
        alias: cross_compound_turbine_governor_dynamics
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineDynamics
        range: CrossCompoundTurbineGovernorDynamics
        required: false
      cross_compound_turbine_governor_dyanmics:
        name: cross_compound_turbine_governor_dyanmics
        description: The cross-compound turbine governor with which this high-pressure
          synchronous machine is associated.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineDynamics.CrossCompoundTurbineGovernorDyanmics
        multivalued: false
        alias: cross_compound_turbine_governor_dyanmics
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineDynamics
        range: CrossCompoundTurbineGovernorDynamics
        required: false
      mechanical_load_dynamics:
        name: mechanical_load_dynamics
        description: Mechanical load model associated with this synchronous machine model.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:SynchronousMachineDynamics.MechanicalLoadDynamics
        multivalued: false
        alias: mechanical_load_dynamics
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - SynchronousMachineDynamics
        - AsynchronousMachineDynamics
        range: MechanicalLoadDynamics
        required: false
      damping:
        name: damping
        description: Damping torque coefficient (<i>D</i>) (&gt;= 0).  A proportionality
          constant that, when multiplied by the angular velocity of the rotor poles with
          respect to the magnetic field (frequency), results in the damping torque.  This
          value is often zero when the sources of damping torques (generator damper windings,
          load damping effects, etc.) are modelled in detail.  Typical value = 0.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:RotatingMachineDynamics.damping
        multivalued: false
        alias: damping
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - RotatingMachineDynamics
        range: float
        required: false
      inertia:
        name: inertia
        description: Inertia constant of generator or motor and mechanical load (<i>H</i>)
          (&gt; 0).  This is the specification for the stored energy in the rotating mass
          when operating at rated speed.  For a generator, this includes the generator
          plus all other elements (turbine, exciter) on the same shaft and has units of
          MW x s.  For a motor, it includes the motor plus its mechanical load. Conventional
          units are PU on the generator MVA base, usually expressed as MW x s / MVA or
          just s. This value is used in the accelerating power reference frame for operator
          training simulator solutions.  Typical value = 3.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:RotatingMachineDynamics.inertia
        multivalued: false
        alias: inertia
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - RotatingMachineDynamics
        range: Seconds
        required: false
      saturation_factor:
        name: saturation_factor
        description: Saturation factor at 120% of rated terminal voltage (<i>S12</i>)
          (&gt;= RotatingMachineDynamics.saturationFactor). Not used by the simplified
          model, defined by <i>S</i>(<i>E2</i>) in the SynchronousMachineSaturationParameters
          diagram.  Typical value = 0,12.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:RotatingMachineDynamics.saturationFactor120
        multivalued: false
        alias: saturation_factor
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - RotatingMachineDynamics
        range: float
        required: false
      stator_leakage_reactance:
        name: stator_leakage_reactance
        description: Stator leakage reactance (<i>Xl</i>) (&gt;= 0). Typical value = 0,15.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:RotatingMachineDynamics.statorLeakageReactance
        multivalued: false
        alias: stator_leakage_reactance
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - RotatingMachineDynamics
        range: PU
        required: false
      stator_resistance:
        name: stator_resistance
        description: Stator (armature) resistance (<i>Rs</i>) (&gt;= 0). Typical value
          = 0,005.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:RotatingMachineDynamics.statorResistance
        multivalued: false
        alias: stator_resistance
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - RotatingMachineDynamics
        range: PU
        required: false
      enabled:
        name: enabled
        description: "Function block used indicator.\r\ntrue = use of function block is\
          \ enabled\r\nfalse = use of function block is disabled."
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        slot_uri: cim:DynamicsFunctionBlock.enabled
        multivalued: false
        alias: enabled
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - ProtectiveAction
        - EndDeviceFunction
        - RegulatingControl
        - DynamicsFunctionBlock
        range: boolean
        required: false
      alias_name:
        name: alias_name
        description: "The aliasName is free text human readable name of the object alternative\
          \ to IdentifiedObject.name. It may be non unique and may not correlate to a\
          \ naming hierarchy.\r\nThe attribute aliasName is retained because of backwards\
          \ compatibility between CIM relases. It is however recommended to replace aliasName\
          \ with the Name class as aliasName is planned for retirement at a future time.\r\
          \n\r\n"
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:IdentifiedObject.aliasName
        multivalued: false
        alias: alias_name
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - IdentifiedObject
        range: string
        required: false
      description:
        name: description
        description: The description is a free human readable text describing or naming
          the object. It may be non unique and may not correlate to a naming hierarchy.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:IdentifiedObject.description
        multivalued: false
        alias: description
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - IdentifiedObject
        - NameType
        - NameTypeAuthority
        - DataSet
        - SwitchingStepGroup
        - AreaReserveSpec
        range: string
        required: false
      m_rid:
        name: m_rid
        description: "Master resource identifier issued by a model authority. The mRID\
          \ is unique within an exchange context. Global uniqueness is easily achieved\
          \ by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is\
          \ strongly recommended.\r\nFor CIMXML data files in RDF syntax conforming to\
          \ IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify\
          \ CIM object elements."
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:IdentifiedObject.mRID
        multivalued: false
        alias: m_rid
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - IdentifiedObject
        - DataSet
        range: string
        required: false
      diagram_objects:
        name: diagram_objects
        description: The diagram objects that are associated with the domain object.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:IdentifiedObject.DiagramObjects
        multivalued: true
        alias: diagram_objects
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - IdentifiedObject
        range: DiagramObject
        required: false
      instance_set:
        name: instance_set
        description: Dataset containing the data objects.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:IdentifiedObject.InstanceSet
        multivalued: false
        alias: instance_set
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - IdentifiedObject
        range: InstanceSet
        required: true
      names:
        name: names
        description: All names of this identified object.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:IdentifiedObject.Names
        multivalued: true
        alias: names
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - IdentifiedObject
        - NameType
        range: Name
        required: false
      properties_cimdata_object:
        name: properties_cimdata_object
        description: The single CIM data object in the appropriate dataset context.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:IdentifiedObject.PropertiesCIMDataObject
        multivalued: false
        alias: properties_cimdata_object
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - IdentifiedObject
        range: ChangeSetMember
        required: false
      targeting_cimdata_object:
        name: targeting_cimdata_object
        description: Data objects registered.
        from_schema: https://cim.ucaiug.io/ns#TC57CIM
        rank: 1000
        slot_uri: cim:IdentifiedObject.TargetingCIMDataObject
        multivalued: true
        alias: targeting_cimdata_object
        owner: SynchronousMachineTimeConstantReactance
        domain_of:
        - IdentifiedObject
        range: ChangeSetMember
        required: false
    class_uri: cim:SynchronousMachineTimeConstantReactance