Class: SynchronousMachineDetailed
All synchronous machine detailed types use a subset of the same data parameters and input/output variables.
_The several variations differ in the following ways: _
_- the number of equivalent windings that are included; _
_- the way in which saturation is incorporated into the model; _
_- whether or not “subtransient saliency” (X''q not = X''d) is represented. _
_It is not necessary for each simulation tool to have separate models for each of the model types. The same model can often be used for several types by alternative logic within the model. Also, differences in saturation representation might not result in significant model performance differences so model substitutions are often acceptable. _
URI: cim:SynchronousMachineDetailed
classDiagram
class SynchronousMachineDetailed
SynchronousMachineDynamics <|-- SynchronousMachineDetailed
SynchronousMachineDetailed <|-- SynchronousMachineTimeConstantReactance
SynchronousMachineDetailed <|-- SynchronousMachineEquivalentCircuit
SynchronousMachineDetailed : alias_name
SynchronousMachineDetailed : cross_compound_turbine_governor_dyanmics
SynchronousMachineDetailed --> CrossCompoundTurbineGovernorDynamics : cross_compound_turbine_governor_dyanmics
SynchronousMachineDetailed : cross_compound_turbine_governor_dynamics
SynchronousMachineDetailed --> CrossCompoundTurbineGovernorDynamics : cross_compound_turbine_governor_dynamics
SynchronousMachineDetailed : damping
SynchronousMachineDetailed : description
SynchronousMachineDetailed : diagram_objects
SynchronousMachineDetailed --> DiagramObject : diagram_objects
SynchronousMachineDetailed : efd_base_ratio
SynchronousMachineDetailed : enabled
SynchronousMachineDetailed : excitation_system_dynamics
SynchronousMachineDetailed --> ExcitationSystemDynamics : excitation_system_dynamics
SynchronousMachineDetailed : gen_icompensation_for_gen_j
SynchronousMachineDetailed --> GenICompensationForGenJ : gen_icompensation_for_gen_j
SynchronousMachineDetailed : ifd_base_type
SynchronousMachineDetailed --> IfdBaseKind : ifd_base_type
SynchronousMachineDetailed : inertia
SynchronousMachineDetailed --> Seconds : inertia
SynchronousMachineDetailed : instance_set
SynchronousMachineDetailed --> InstanceSet : instance_set
SynchronousMachineDetailed : m_rid
SynchronousMachineDetailed : mechanical_load_dynamics
SynchronousMachineDetailed --> MechanicalLoadDynamics : mechanical_load_dynamics
SynchronousMachineDetailed : names
SynchronousMachineDetailed --> Name : names
SynchronousMachineDetailed : properties_cimdata_object
SynchronousMachineDetailed --> ChangeSetMember : properties_cimdata_object
SynchronousMachineDetailed : saturation_factor
SynchronousMachineDetailed : saturation_factor___qaxis
SynchronousMachineDetailed : saturation_factor_qaxis
SynchronousMachineDetailed : stator_leakage_reactance
SynchronousMachineDetailed --> PU : stator_leakage_reactance
SynchronousMachineDetailed : stator_resistance
SynchronousMachineDetailed --> PU : stator_resistance
SynchronousMachineDetailed : synchronous_machine
SynchronousMachineDetailed --> SynchronousMachine : synchronous_machine
SynchronousMachineDetailed : targeting_cimdata_object
SynchronousMachineDetailed --> ChangeSetMember : targeting_cimdata_object
SynchronousMachineDetailed : turbine_governor_dynamics
SynchronousMachineDetailed --> TurbineGovernorDynamics : turbine_governor_dynamics
Inheritance
Slots
| Name | Cardinality and Range | Description | Inheritance |
|---|---|---|---|
| efd_base_ratio | 0..1 Float |
Ratio (exciter voltage/generator voltage) of Efd bases of exciter and ... | direct |
| ifd_base_type | 0..1 IfdBaseKind |
Excitation base system mode | direct |
| saturation_factor___qaxis | 0..1 Float |
Quadrature-axis saturation factor at 120% of rated terminal voltage (S12q<... | direct |
| saturation_factor_qaxis | 0..1 Float |
Quadrature-axis saturation factor at rated terminal voltage (S1q) (>... | direct |
| synchronous_machine | 1..1 SynchronousMachine |
Synchronous machine to which synchronous machine dynamics model applies | SynchronousMachineDynamics |
| turbine_governor_dynamics | 0..* TurbineGovernorDynamics |
Turbine-governor model associated with this synchronous machine model | SynchronousMachineDynamics |
| gen_icompensation_for_gen_j | 0..* GenICompensationForGenJ |
Compensation of voltage compensator's generator for current flow out of this ... | SynchronousMachineDynamics |
| excitation_system_dynamics | 0..1 ExcitationSystemDynamics |
Excitation system model associated with this synchronous machine model | SynchronousMachineDynamics |
| cross_compound_turbine_governor_dynamics | 0..1 CrossCompoundTurbineGovernorDynamics |
The cross-compound turbine governor with which this low-pressure synchronous ... | SynchronousMachineDynamics |
| cross_compound_turbine_governor_dyanmics | 0..1 CrossCompoundTurbineGovernorDynamics |
The cross-compound turbine governor with which this high-pressure synchronous... | SynchronousMachineDynamics |
| mechanical_load_dynamics | 0..1 MechanicalLoadDynamics |
Mechanical load model associated with this synchronous machine model | SynchronousMachineDynamics |
| damping | 0..1 Float |
Damping torque coefficient (D) (>= 0) | RotatingMachineDynamics |
| inertia | 0..1 Seconds |
Inertia constant of generator or motor and mechanical load (H) (> 0... | RotatingMachineDynamics |
| saturation_factor | 0..1 Float |
Saturation factor at 120% of rated terminal voltage (S12) (>= Rotat... | RotatingMachineDynamics |
| stator_leakage_reactance | 0..1 PU |
Stator leakage reactance (Xl) (>= 0) | RotatingMachineDynamics |
| stator_resistance | 0..1 PU |
Stator (armature) resistance (Rs) (>= 0) | RotatingMachineDynamics |
| enabled | 0..1 Boolean |
Function block used indicator | DynamicsFunctionBlock |
| alias_name | 0..1 String |
The aliasName is free text human readable name of the object alternative to I... | IdentifiedObject |
| description | 0..1 String |
The description is a free human readable text describing or naming the object | IdentifiedObject |
| m_rid | 0..1 String |
Master resource identifier issued by a model authority | IdentifiedObject |
| diagram_objects | 0..* DiagramObject |
The diagram objects that are associated with the domain object | IdentifiedObject |
| instance_set | 1..1 InstanceSet |
Dataset containing the data objects | IdentifiedObject |
| names | 0..* Name |
All names of this identified object | IdentifiedObject |
| properties_cimdata_object | 0..1 ChangeSetMember |
The single CIM data object in the appropriate dataset context | IdentifiedObject |
| targeting_cimdata_object | 0..* ChangeSetMember |
Data objects registered | IdentifiedObject |
Identifier and Mapping Information
Schema Source
- from schema: https://cim.ucaiug.io/ns#TC57CIM
Mappings
| Mapping Type | Mapped Value |
|---|---|
| self | cim:SynchronousMachineDetailed |
| native | cim:SynchronousMachineDetailed |
LinkML Source
Direct
name: SynchronousMachineDetailed
description: "All synchronous machine detailed types use a subset of the same data\
\ parameters and input/output variables. \r\nThe several variations differ in the\
\ following ways:\r\n- the number of equivalent windings that are included;\r\n\
- the way in which saturation is incorporated into the model;\r\n- whether or not\
\ “subtransient saliency” (<i>X''q</i> not = <i>X''d</i>) is represented.\r\nIt\
\ is not necessary for each simulation tool to have separate models for each of\
\ the model types. The same model can often be used for several types by alternative\
\ logic within the model. Also, differences in saturation representation might\
\ not result in significant model performance differences so model substitutions\
\ are often acceptable. "
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
is_a: SynchronousMachineDynamics
attributes:
efd_base_ratio:
name: efd_base_ratio
description: Ratio (exciter voltage/generator voltage) of <i>Efd</i> bases of
exciter and generator models (> 0). Typical value = 1.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:SynchronousMachineDetailed.efdBaseRatio
multivalued: false
domain_of:
- SynchronousMachineDetailed
range: float
required: false
ifd_base_type:
name: ifd_base_type
description: 'Excitation base system mode. It should be equal to the value of
<i>WLMDV</i> given by the user. <i>WLMDV</i> is the PU ratio between the field
voltage and the excitation current: <i>Efd</i> = <i>WLMDV</i> x <i>Ifd</i>.
Typical value = ifag.'
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:SynchronousMachineDetailed.ifdBaseType
multivalued: false
domain_of:
- SynchronousMachineDetailed
range: IfdBaseKind
required: false
saturation_factor___qaxis:
name: saturation_factor___qaxis
description: Quadrature-axis saturation factor at 120% of rated terminal voltage
(<i>S12q</i>) (>= SynchonousMachineDetailed.saturationFactorQAxis). Typical
value = 0,12.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:SynchronousMachineDetailed.saturationFactor120QAxis
multivalued: false
domain_of:
- SynchronousMachineDetailed
range: float
required: false
saturation_factor_qaxis:
name: saturation_factor_qaxis
description: Quadrature-axis saturation factor at rated terminal voltage (<i>S1q</i>)
(>= 0). Typical value = 0,02.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:SynchronousMachineDetailed.saturationFactorQAxis
multivalued: false
domain_of:
- SynchronousMachineDetailed
range: float
required: false
class_uri: cim:SynchronousMachineDetailed
Induced
name: SynchronousMachineDetailed
description: "All synchronous machine detailed types use a subset of the same data\
\ parameters and input/output variables. \r\nThe several variations differ in the\
\ following ways:\r\n- the number of equivalent windings that are included;\r\n\
- the way in which saturation is incorporated into the model;\r\n- whether or not\
\ “subtransient saliency” (<i>X''q</i> not = <i>X''d</i>) is represented.\r\nIt\
\ is not necessary for each simulation tool to have separate models for each of\
\ the model types. The same model can often be used for several types by alternative\
\ logic within the model. Also, differences in saturation representation might\
\ not result in significant model performance differences so model substitutions\
\ are often acceptable. "
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
is_a: SynchronousMachineDynamics
attributes:
efd_base_ratio:
name: efd_base_ratio
description: Ratio (exciter voltage/generator voltage) of <i>Efd</i> bases of
exciter and generator models (> 0). Typical value = 1.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:SynchronousMachineDetailed.efdBaseRatio
multivalued: false
alias: efd_base_ratio
owner: SynchronousMachineDetailed
domain_of:
- SynchronousMachineDetailed
range: float
required: false
ifd_base_type:
name: ifd_base_type
description: 'Excitation base system mode. It should be equal to the value of
<i>WLMDV</i> given by the user. <i>WLMDV</i> is the PU ratio between the field
voltage and the excitation current: <i>Efd</i> = <i>WLMDV</i> x <i>Ifd</i>.
Typical value = ifag.'
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:SynchronousMachineDetailed.ifdBaseType
multivalued: false
alias: ifd_base_type
owner: SynchronousMachineDetailed
domain_of:
- SynchronousMachineDetailed
range: IfdBaseKind
required: false
saturation_factor___qaxis:
name: saturation_factor___qaxis
description: Quadrature-axis saturation factor at 120% of rated terminal voltage
(<i>S12q</i>) (>= SynchonousMachineDetailed.saturationFactorQAxis). Typical
value = 0,12.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:SynchronousMachineDetailed.saturationFactor120QAxis
multivalued: false
alias: saturation_factor___qaxis
owner: SynchronousMachineDetailed
domain_of:
- SynchronousMachineDetailed
range: float
required: false
saturation_factor_qaxis:
name: saturation_factor_qaxis
description: Quadrature-axis saturation factor at rated terminal voltage (<i>S1q</i>)
(>= 0). Typical value = 0,02.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:SynchronousMachineDetailed.saturationFactorQAxis
multivalued: false
alias: saturation_factor_qaxis
owner: SynchronousMachineDetailed
domain_of:
- SynchronousMachineDetailed
range: float
required: false
synchronous_machine:
name: synchronous_machine
description: Synchronous machine to which synchronous machine dynamics model applies.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:SynchronousMachineDynamics.SynchronousMachine
multivalued: false
alias: synchronous_machine
owner: SynchronousMachineDetailed
domain_of:
- SynchronousMachineDynamics
range: SynchronousMachine
required: true
turbine_governor_dynamics:
name: turbine_governor_dynamics
description: Turbine-governor model associated with this synchronous machine model.
Multiplicity of greater than one is intended to support hydro units that have
multiple turbines on one generator.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:SynchronousMachineDynamics.TurbineGovernorDynamics
multivalued: true
alias: turbine_governor_dynamics
owner: SynchronousMachineDetailed
domain_of:
- SynchronousMachineDynamics
- AsynchronousMachineDynamics
- TurbineLoadControllerDynamics
range: TurbineGovernorDynamics
required: false
gen_icompensation_for_gen_j:
name: gen_icompensation_for_gen_j
description: Compensation of voltage compensator's generator for current flow
out of this generator.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:SynchronousMachineDynamics.GenICompensationForGenJ
multivalued: true
alias: gen_icompensation_for_gen_j
owner: SynchronousMachineDetailed
domain_of:
- SynchronousMachineDynamics
- VCompIEEEType2
range: GenICompensationForGenJ
required: false
excitation_system_dynamics:
name: excitation_system_dynamics
description: Excitation system model associated with this synchronous machine
model.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:SynchronousMachineDynamics.ExcitationSystemDynamics
multivalued: false
alias: excitation_system_dynamics
owner: SynchronousMachineDetailed
domain_of:
- SynchronousMachineDynamics
- VoltageCompensatorDynamics
- PowerSystemStabilizerDynamics
- UnderexcitationLimiterDynamics
- DiscontinuousExcitationControlDynamics
- PFVArControllerType1Dynamics
- OverexcitationLimiterDynamics
- PFVArControllerType2Dynamics
range: ExcitationSystemDynamics
required: false
cross_compound_turbine_governor_dynamics:
name: cross_compound_turbine_governor_dynamics
description: The cross-compound turbine governor with which this low-pressure
synchronous machine is associated.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:SynchronousMachineDynamics.CrossCompoundTurbineGovernorDynamics
multivalued: false
alias: cross_compound_turbine_governor_dynamics
owner: SynchronousMachineDetailed
domain_of:
- SynchronousMachineDynamics
range: CrossCompoundTurbineGovernorDynamics
required: false
cross_compound_turbine_governor_dyanmics:
name: cross_compound_turbine_governor_dyanmics
description: The cross-compound turbine governor with which this high-pressure
synchronous machine is associated.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:SynchronousMachineDynamics.CrossCompoundTurbineGovernorDyanmics
multivalued: false
alias: cross_compound_turbine_governor_dyanmics
owner: SynchronousMachineDetailed
domain_of:
- SynchronousMachineDynamics
range: CrossCompoundTurbineGovernorDynamics
required: false
mechanical_load_dynamics:
name: mechanical_load_dynamics
description: Mechanical load model associated with this synchronous machine model.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:SynchronousMachineDynamics.MechanicalLoadDynamics
multivalued: false
alias: mechanical_load_dynamics
owner: SynchronousMachineDetailed
domain_of:
- SynchronousMachineDynamics
- AsynchronousMachineDynamics
range: MechanicalLoadDynamics
required: false
damping:
name: damping
description: Damping torque coefficient (<i>D</i>) (>= 0). A proportionality
constant that, when multiplied by the angular velocity of the rotor poles with
respect to the magnetic field (frequency), results in the damping torque. This
value is often zero when the sources of damping torques (generator damper windings,
load damping effects, etc.) are modelled in detail. Typical value = 0.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:RotatingMachineDynamics.damping
multivalued: false
alias: damping
owner: SynchronousMachineDetailed
domain_of:
- RotatingMachineDynamics
range: float
required: false
inertia:
name: inertia
description: Inertia constant of generator or motor and mechanical load (<i>H</i>)
(> 0). This is the specification for the stored energy in the rotating mass
when operating at rated speed. For a generator, this includes the generator
plus all other elements (turbine, exciter) on the same shaft and has units of
MW x s. For a motor, it includes the motor plus its mechanical load. Conventional
units are PU on the generator MVA base, usually expressed as MW x s / MVA or
just s. This value is used in the accelerating power reference frame for operator
training simulator solutions. Typical value = 3.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:RotatingMachineDynamics.inertia
multivalued: false
alias: inertia
owner: SynchronousMachineDetailed
domain_of:
- RotatingMachineDynamics
range: Seconds
required: false
saturation_factor:
name: saturation_factor
description: Saturation factor at 120% of rated terminal voltage (<i>S12</i>)
(>= RotatingMachineDynamics.saturationFactor). Not used by the simplified
model, defined by <i>S</i>(<i>E2</i>) in the SynchronousMachineSaturationParameters
diagram. Typical value = 0,12.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:RotatingMachineDynamics.saturationFactor120
multivalued: false
alias: saturation_factor
owner: SynchronousMachineDetailed
domain_of:
- RotatingMachineDynamics
range: float
required: false
stator_leakage_reactance:
name: stator_leakage_reactance
description: Stator leakage reactance (<i>Xl</i>) (>= 0). Typical value = 0,15.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:RotatingMachineDynamics.statorLeakageReactance
multivalued: false
alias: stator_leakage_reactance
owner: SynchronousMachineDetailed
domain_of:
- RotatingMachineDynamics
range: PU
required: false
stator_resistance:
name: stator_resistance
description: Stator (armature) resistance (<i>Rs</i>) (>= 0). Typical value
= 0,005.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:RotatingMachineDynamics.statorResistance
multivalued: false
alias: stator_resistance
owner: SynchronousMachineDetailed
domain_of:
- RotatingMachineDynamics
range: PU
required: false
enabled:
name: enabled
description: "Function block used indicator.\r\ntrue = use of function block is\
\ enabled\r\nfalse = use of function block is disabled."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:DynamicsFunctionBlock.enabled
multivalued: false
alias: enabled
owner: SynchronousMachineDetailed
domain_of:
- ProtectiveAction
- EndDeviceFunction
- RegulatingControl
- DynamicsFunctionBlock
range: boolean
required: false
alias_name:
name: alias_name
description: "The aliasName is free text human readable name of the object alternative\
\ to IdentifiedObject.name. It may be non unique and may not correlate to a\
\ naming hierarchy.\r\nThe attribute aliasName is retained because of backwards\
\ compatibility between CIM relases. It is however recommended to replace aliasName\
\ with the Name class as aliasName is planned for retirement at a future time.\r\
\n\r\n"
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.aliasName
multivalued: false
alias: alias_name
owner: SynchronousMachineDetailed
domain_of:
- IdentifiedObject
range: string
required: false
description:
name: description
description: The description is a free human readable text describing or naming
the object. It may be non unique and may not correlate to a naming hierarchy.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.description
multivalued: false
alias: description
owner: SynchronousMachineDetailed
domain_of:
- IdentifiedObject
- NameType
- NameTypeAuthority
- DataSet
- SwitchingStepGroup
- AreaReserveSpec
range: string
required: false
m_rid:
name: m_rid
description: "Master resource identifier issued by a model authority. The mRID\
\ is unique within an exchange context. Global uniqueness is easily achieved\
\ by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is\
\ strongly recommended.\r\nFor CIMXML data files in RDF syntax conforming to\
\ IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify\
\ CIM object elements."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.mRID
multivalued: false
alias: m_rid
owner: SynchronousMachineDetailed
domain_of:
- IdentifiedObject
- DataSet
range: string
required: false
diagram_objects:
name: diagram_objects
description: The diagram objects that are associated with the domain object.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.DiagramObjects
multivalued: true
alias: diagram_objects
owner: SynchronousMachineDetailed
domain_of:
- IdentifiedObject
range: DiagramObject
required: false
instance_set:
name: instance_set
description: Dataset containing the data objects.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.InstanceSet
multivalued: false
alias: instance_set
owner: SynchronousMachineDetailed
domain_of:
- IdentifiedObject
range: InstanceSet
required: true
names:
name: names
description: All names of this identified object.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.Names
multivalued: true
alias: names
owner: SynchronousMachineDetailed
domain_of:
- IdentifiedObject
- NameType
range: Name
required: false
properties_cimdata_object:
name: properties_cimdata_object
description: The single CIM data object in the appropriate dataset context.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.PropertiesCIMDataObject
multivalued: false
alias: properties_cimdata_object
owner: SynchronousMachineDetailed
domain_of:
- IdentifiedObject
range: ChangeSetMember
required: false
targeting_cimdata_object:
name: targeting_cimdata_object
description: Data objects registered.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.TargetingCIMDataObject
multivalued: true
alias: targeting_cimdata_object
owner: SynchronousMachineDetailed
domain_of:
- IdentifiedObject
range: ChangeSetMember
required: false
class_uri: cim:SynchronousMachineDetailed