Class: ShuntCompensator
A shunt capacitor or reactor or switchable bank of shunt capacitors or reactors. A section of a shunt compensator is an individual capacitor or reactor. A negative value for bPerSection indicates that the compensator is a reactor. ShuntCompensator is a single terminal device. Ground is implied.
URI: cim:ShuntCompensator
classDiagram
class ShuntCompensator
RegulatingCondEq <|-- ShuntCompensator
ShuntCompensator <|-- LinearShuntCompensator
ShuntCompensator <|-- NonlinearShuntCompensator
ShuntCompensator <|-- SVC
ShuntCompensator <|-- MktShuntCompensator
ShuntCompensator : a_vrdelay
ShuntCompensator --> Seconds : a_vrdelay
ShuntCompensator : additional_equipment_container
ShuntCompensator --> EquipmentContainer : additional_equipment_container
ShuntCompensator : aggregate
ShuntCompensator : alias_name
ShuntCompensator : asset_datasheet
ShuntCompensator --> AssetInfo : asset_datasheet
ShuntCompensator : assets
ShuntCompensator --> Asset : assets
ShuntCompensator : base_voltage
ShuntCompensator --> BaseVoltage : base_voltage
ShuntCompensator : clearances
ShuntCompensator --> ClearanceDocument : clearances
ShuntCompensator : configuration_event
ShuntCompensator --> ConfigurationEvent : configuration_event
ShuntCompensator : contingency_equipment
ShuntCompensator --> ContingencyEquipment : contingency_equipment
ShuntCompensator : control_enabled
ShuntCompensator : controls
ShuntCompensator --> Control : controls
ShuntCompensator : description
ShuntCompensator : diagram_objects
ShuntCompensator --> DiagramObject : diagram_objects
ShuntCompensator : energy_component
ShuntCompensator --> EnergyComponent : energy_component
ShuntCompensator : eqiupment_limit_series_component
ShuntCompensator --> EquipmentLimitSeriesComponent : eqiupment_limit_series_component
ShuntCompensator : equipment_container
ShuntCompensator --> EquipmentContainer : equipment_container
ShuntCompensator : equipment_unavailability_schedule
ShuntCompensator --> EquipmentUnavailabilitySchedule : equipment_unavailability_schedule
ShuntCompensator : faults
ShuntCompensator --> Fault : faults
ShuntCompensator : generic_action
ShuntCompensator --> GenericAction : generic_action
ShuntCompensator : grounded
ShuntCompensator : grounding_action
ShuntCompensator --> GroundAction : grounding_action
ShuntCompensator : in_service
ShuntCompensator : instance_set
ShuntCompensator --> InstanceSet : instance_set
ShuntCompensator : jumping_action
ShuntCompensator --> JumperAction : jumping_action
ShuntCompensator : limit_dependency_model
ShuntCompensator --> LimitDependency : limit_dependency_model
ShuntCompensator : location
ShuntCompensator --> Location : location
ShuntCompensator : m_rid
ShuntCompensator : maximum_sections
ShuntCompensator : measurements
ShuntCompensator --> Measurement : measurements
ShuntCompensator : names
ShuntCompensator --> Name : names
ShuntCompensator : network_analysis_enabled
ShuntCompensator : nom_u
ShuntCompensator --> Voltage : nom_u
ShuntCompensator : normal_sections
ShuntCompensator : normally_in_service
ShuntCompensator : operating_share
ShuntCompensator --> OperatingShare : operating_share
ShuntCompensator : operational_limit_set
ShuntCompensator --> OperationalLimitSet : operational_limit_set
ShuntCompensator : operational_restrictions
ShuntCompensator --> OperationalRestriction : operational_restrictions
ShuntCompensator : operational_tags
ShuntCompensator --> OperationalTag : operational_tags
ShuntCompensator : outage
ShuntCompensator --> Outage : outage
ShuntCompensator : outages
ShuntCompensator --> Outage : outages
ShuntCompensator : phase_connection
ShuntCompensator --> PhaseShuntConnectionKind : phase_connection
ShuntCompensator : pin_equipment
ShuntCompensator --> PinEquipment : pin_equipment
ShuntCompensator : properties_cimdata_object
ShuntCompensator --> ChangeSetMember : properties_cimdata_object
ShuntCompensator : protection_equipments
ShuntCompensator --> ProtectionEquipment : protection_equipments
ShuntCompensator : protective_action_adjustment
ShuntCompensator --> ProtectiveActionAdjustment : protective_action_adjustment
ShuntCompensator : protective_action_equipment
ShuntCompensator --> ProtectiveActionEquipment : protective_action_equipment
ShuntCompensator : psrevents
ShuntCompensator --> PSREvent : psrevents
ShuntCompensator : psrtype
ShuntCompensator --> PSRType : psrtype
ShuntCompensator : regulating_control
ShuntCompensator --> RegulatingControl : regulating_control
ShuntCompensator : reporting_group
ShuntCompensator --> ReportingGroup : reporting_group
ShuntCompensator : sections
ShuntCompensator : shunt_compensator_action
ShuntCompensator --> ShuntCompensatorAction : shunt_compensator_action
ShuntCompensator : shunt_compensator_phase
ShuntCompensator --> ShuntCompensatorPhase : shunt_compensator_phase
ShuntCompensator : sv_shunt_compensator_sections
ShuntCompensator --> SvShuntCompensatorSections : sv_shunt_compensator_sections
ShuntCompensator : sv_status
ShuntCompensator --> SvStatus : sv_status
ShuntCompensator : switch_on_count
ShuntCompensator : switch_on_date
ShuntCompensator : targeting_cimdata_object
ShuntCompensator --> ChangeSetMember : targeting_cimdata_object
ShuntCompensator : terminals
ShuntCompensator --> Terminal : terminals
ShuntCompensator : usage_points
ShuntCompensator --> UsagePoint : usage_points
ShuntCompensator : verification_action
ShuntCompensator --> VerificationAction : verification_action
ShuntCompensator : voltage_sensitivity
ShuntCompensator --> VoltagePerReactivePower : voltage_sensitivity
ShuntCompensator : weather_station
ShuntCompensator --> WeatherStation : weather_station
Inheritance
Slots
| Name | Cardinality and Range | Description | Inheritance |
|---|---|---|---|
| a_vrdelay | 0..1 Seconds |
An automatic voltage regulation delay (AVRDelay) which is the time delay from... | direct |
| grounded | 0..1 Boolean |
Used for Yn and Zn connections | direct |
| maximum_sections | 0..1 Integer |
The maximum number of sections that may be switched in | direct |
| nom_u | 0..1 Voltage |
The voltage at which the nominal reactive power may be calculated | direct |
| normal_sections | 0..1 Integer |
The normal number of sections switched in | direct |
| phase_connection | 0..1 PhaseShuntConnectionKind |
The type of phase connection, such as wye or delta | direct |
| sections | 0..1 Float |
Shunt compensator sections in use | direct |
| switch_on_count | 0..1 Integer |
The switch on count since the capacitor count was last reset or initialized | direct |
| switch_on_date | 0..1 date |
The date and time when the capacitor bank was last switched on | direct |
| voltage_sensitivity | 0..1 VoltagePerReactivePower |
Voltage sensitivity required for the device to regulate the bus voltage, in v... | direct |
| shunt_compensator_phase | 0..* ShuntCompensatorPhase |
The individual phases models for the shunt compensator | direct |
| shunt_compensator_action | 0..1 ShuntCompensatorAction |
The shunt compensator action that is performed on the shunt compensator | direct |
| sv_shunt_compensator_sections | 0..* SvShuntCompensatorSections |
The state for the number of shunt compensator sections in service | direct |
| control_enabled | 0..1 Boolean |
Specifies the regulation status of the equipment | RegulatingCondEq |
| regulating_control | 0..1 RegulatingControl |
The regulating control scheme in which this equipment participates | RegulatingCondEq |
| energy_component | 0..* EnergyComponent |
EnergyConnection | |
| protective_action_adjustment | 0..* ProtectiveActionAdjustment |
The operating condition to the Conducting Equipment is changed when protectiv... | ConductingEquipment |
| sv_status | 0..* SvStatus |
The status state variable associated with this conducting equipment | ConductingEquipment |
| protection_equipments | 0..* ProtectionEquipment |
Protection equipment used to protect specific conducting equipment | ConductingEquipment |
| base_voltage | 0..1 BaseVoltage |
Base voltage of this conducting equipment | ConductingEquipment |
| terminals | 0..* Terminal |
Conducting equipment have terminals that may be connected to other conducting... | ConductingEquipment |
| jumping_action | 0..1 JumperAction |
Jumper action involving jumping operation on this conducting equipment | ConductingEquipment |
| grounding_action | 0..1 GroundAction |
Action involving grounding operation on this conducting equipment | ConductingEquipment |
| outage | 0..1 Outage |
The outage that is isolated by the outage isolation equipment | ConductingEquipment |
| aggregate | 0..1 Boolean |
The aggregate flag provides an alternative way of representing an aggregated ... | Equipment |
| in_service | 0..1 Boolean |
Specifies the availability of the equipment | Equipment |
| network_analysis_enabled | 0..1 Boolean |
The equipment is enabled to participate in network analysis | Equipment |
| normally_in_service | 0..1 Boolean |
Specifies the availability of the equipment under normal operating conditions | Equipment |
| weather_station | 0..* WeatherStation |
Equipment | |
| operational_limit_set | 0..* OperationalLimitSet |
The operational limit sets associated with this equipment | Equipment |
| contingency_equipment | 0..* ContingencyEquipment |
The contingency equipments in which this equipment participates | Equipment |
| equipment_container | 0..1 EquipmentContainer |
Container of this equipment | Equipment |
| faults | 0..* Fault |
All faults on this equipment | Equipment |
| limit_dependency_model | 0..* LimitDependency |
Limit dependencymodels organized under this equipment as a means for organizi... | Equipment |
| eqiupment_limit_series_component | 0..* EquipmentLimitSeriesComponent |
Equipment limit series calculation component to which this equipment contribu... | Equipment |
| protective_action_equipment | 0..* ProtectiveActionEquipment |
Protective action is controlling equipment | Equipment |
| pin_equipment | 0..* PinEquipment |
Equipment | |
| equipment_unavailability_schedule | 0..* EquipmentUnavailabilitySchedule |
Equipment | |
| additional_equipment_container | 0..* EquipmentContainer |
Additional equipment container beyond the primary equipment container | Equipment |
| usage_points | 0..* UsagePoint |
All usage points connected to the electrical grid through this equipment | Equipment |
| outages | 0..* Outage |
All outages in which this equipment is involved | Equipment |
| operational_restrictions | 0..* OperationalRestriction |
All operational restrictions for this equipment | Equipment |
| controls | 0..* Control |
The controller outputs used to actually govern a regulating device, e | PowerSystemResource |
| measurements | 0..* Measurement |
The measurements associated with this power system resource | PowerSystemResource |
| psrtype | 0..1 PSRType |
Custom classification for this power system resource | PowerSystemResource |
| configuration_event | 0..* ConfigurationEvent |
All configuration events created for this Power System resource | PowerSystemResource |
| reporting_group | 0..* ReportingGroup |
Reporting groups to which this power system resource belongs | PowerSystemResource |
| operating_share | 0..* OperatingShare |
The operating shares of this power system resource | PowerSystemResource |
| asset_datasheet | 0..1 AssetInfo |
Datasheet information for this power system resource | PowerSystemResource |
| verification_action | 0..* VerificationAction |
The verification action that is performed on the power system resource | PowerSystemResource |
| clearances | 0..* ClearanceDocument |
All clearances applicable to this power system resource | PowerSystemResource |
| generic_action | 0..* GenericAction |
The generic action that is performed on the power system resource | PowerSystemResource |
| psrevents | 0..* PSREvent |
All events associated with this power system resource | PowerSystemResource |
| assets | 0..* Asset |
All assets represented by this power system resource | PowerSystemResource |
| location | 0..1 Location |
Location of this power system resource | PowerSystemResource |
| operational_tags | 0..* OperationalTag |
All operational tags placed on this power system resource | PowerSystemResource |
| alias_name | 0..1 String |
The aliasName is free text human readable name of the object alternative to I... | IdentifiedObject |
| description | 0..1 String |
The description is a free human readable text describing or naming the object | IdentifiedObject |
| m_rid | 0..1 String |
Master resource identifier issued by a model authority | IdentifiedObject |
| diagram_objects | 0..* DiagramObject |
The diagram objects that are associated with the domain object | IdentifiedObject |
| instance_set | 1..1 InstanceSet |
Dataset containing the data objects | IdentifiedObject |
| names | 0..* Name |
All names of this identified object | IdentifiedObject |
| properties_cimdata_object | 0..1 ChangeSetMember |
The single CIM data object in the appropriate dataset context | IdentifiedObject |
| targeting_cimdata_object | 0..* ChangeSetMember |
Data objects registered | IdentifiedObject |
Usages
Identifier and Mapping Information
Schema Source
- from schema: https://cim.ucaiug.io/ns#TC57CIM
Mappings
| Mapping Type | Mapped Value |
|---|---|
| self | cim:ShuntCompensator |
| native | cim:ShuntCompensator |
LinkML Source
Direct
name: ShuntCompensator
description: A shunt capacitor or reactor or switchable bank of shunt capacitors or
reactors. A section of a shunt compensator is an individual capacitor or reactor.
A negative value for bPerSection indicates that the compensator is a reactor. ShuntCompensator
is a single terminal device. Ground is implied.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
is_a: RegulatingCondEq
attributes:
a_vrdelay:
name: a_vrdelay
description: An automatic voltage regulation delay (AVRDelay) which is the time
delay from a change in voltage to when the capacitor is allowed to change state.
This filters out temporary changes in voltage.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ShuntCompensator.aVRDelay
multivalued: false
domain_of:
- ShuntCompensator
range: Seconds
required: false
grounded:
name: grounded
description: Used for Yn and Zn connections. True if the neutral is solidly grounded.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ShuntCompensator.grounded
multivalued: false
domain_of:
- TransformerEnd
- UsagePoint
- ShuntCompensator
- EnergyConsumer
range: boolean
required: false
maximum_sections:
name: maximum_sections
description: "The maximum number of sections that may be switched in. \r\n"
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ShuntCompensator.maximumSections
multivalued: false
domain_of:
- ShuntCompensatorPhase
- ShuntCompensator
range: integer
required: false
nom_u:
name: nom_u
description: "The voltage at which the nominal reactive power may be calculated.\
\ This should normally be within 10% of the voltage at which the capacitor is\
\ connected to the network.\r\n"
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ShuntCompensator.nomU
multivalued: false
domain_of:
- ShuntCompensator
range: Voltage
required: false
normal_sections:
name: normal_sections
description: "The normal number of sections switched in. The value shall be between\
\ zero and ShuntCompensator.maximumSections.\r\n"
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ShuntCompensator.normalSections
multivalued: false
domain_of:
- ShuntCompensatorPhase
- ShuntCompensator
range: integer
required: false
phase_connection:
name: phase_connection
description: "The type of phase connection, such as wye or delta.\r\n"
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ShuntCompensator.phaseConnection
multivalued: false
domain_of:
- ShuntCompensator
- EnergyConsumer
range: PhaseShuntConnectionKind
required: false
sections:
name: sections
description: "Shunt compensator sections in use. Starting value for steady state\
\ solution. The attribute shall be a positive value or zero. Non integer values\
\ are allowed to support continuous variables. The reasons for continuous value\
\ are to support study cases where no discrete shunt compensators has yet been\
\ designed, a solutions where a narrow voltage band force the sections to oscillate\
\ or accommodate for a continuous solution as input. \r\nFor LinearShuntConpensator\
\ the value shall be between zero and ShuntCompensator.maximumSections. At value\
\ zero the shunt compensator conductance and admittance is zero. Linear interpolation\
\ of conductance and admittance between the previous and next integer section\
\ is applied in case of non-integer values.\r\nFor NonlinearShuntCompensator-s\
\ shall only be set to one of the NonlinearShuntCompenstorPoint.sectionNumber.\
\ There is no interpolation between NonlinearShuntCompenstorPoint-s."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ShuntCompensator.sections
multivalued: false
domain_of:
- ShuntCompensatorPhase
- ShuntCompensator
- SvShuntCompensatorSections
range: float
required: false
switch_on_count:
name: switch_on_count
description: The switch on count since the capacitor count was last reset or initialized.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ShuntCompensator.switchOnCount
multivalued: false
domain_of:
- Switch
- ShuntCompensator
range: integer
required: false
switch_on_date:
name: switch_on_date
description: The date and time when the capacitor bank was last switched on.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ShuntCompensator.switchOnDate
multivalued: false
domain_of:
- Switch
- ShuntCompensator
range: date
required: false
voltage_sensitivity:
name: voltage_sensitivity
description: Voltage sensitivity required for the device to regulate the bus voltage,
in voltage/reactive power.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ShuntCompensator.voltageSensitivity
multivalued: false
domain_of:
- ShuntCompensator
range: VoltagePerReactivePower
required: false
shunt_compensator_phase:
name: shunt_compensator_phase
description: The individual phases models for the shunt compensator.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ShuntCompensator.ShuntCompensatorPhase
multivalued: true
domain_of:
- ShuntCompensator
range: ShuntCompensatorPhase
required: false
shunt_compensator_action:
name: shunt_compensator_action
description: The shunt compensator action that is performed on the shunt compensator
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ShuntCompensator.ShuntCompensatorAction
multivalued: false
domain_of:
- ShuntCompensator
range: ShuntCompensatorAction
required: false
sv_shunt_compensator_sections:
name: sv_shunt_compensator_sections
description: The state for the number of shunt compensator sections in service.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ShuntCompensator.SvShuntCompensatorSections
multivalued: true
domain_of:
- ShuntCompensator
range: SvShuntCompensatorSections
required: false
class_uri: cim:ShuntCompensator
Induced
name: ShuntCompensator
description: A shunt capacitor or reactor or switchable bank of shunt capacitors or
reactors. A section of a shunt compensator is an individual capacitor or reactor.
A negative value for bPerSection indicates that the compensator is a reactor. ShuntCompensator
is a single terminal device. Ground is implied.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
is_a: RegulatingCondEq
attributes:
a_vrdelay:
name: a_vrdelay
description: An automatic voltage regulation delay (AVRDelay) which is the time
delay from a change in voltage to when the capacitor is allowed to change state.
This filters out temporary changes in voltage.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ShuntCompensator.aVRDelay
multivalued: false
alias: a_vrdelay
owner: ShuntCompensator
domain_of:
- ShuntCompensator
range: Seconds
required: false
grounded:
name: grounded
description: Used for Yn and Zn connections. True if the neutral is solidly grounded.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ShuntCompensator.grounded
multivalued: false
alias: grounded
owner: ShuntCompensator
domain_of:
- TransformerEnd
- UsagePoint
- ShuntCompensator
- EnergyConsumer
range: boolean
required: false
maximum_sections:
name: maximum_sections
description: "The maximum number of sections that may be switched in. \r\n"
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ShuntCompensator.maximumSections
multivalued: false
alias: maximum_sections
owner: ShuntCompensator
domain_of:
- ShuntCompensatorPhase
- ShuntCompensator
range: integer
required: false
nom_u:
name: nom_u
description: "The voltage at which the nominal reactive power may be calculated.\
\ This should normally be within 10% of the voltage at which the capacitor is\
\ connected to the network.\r\n"
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ShuntCompensator.nomU
multivalued: false
alias: nom_u
owner: ShuntCompensator
domain_of:
- ShuntCompensator
range: Voltage
required: false
normal_sections:
name: normal_sections
description: "The normal number of sections switched in. The value shall be between\
\ zero and ShuntCompensator.maximumSections.\r\n"
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ShuntCompensator.normalSections
multivalued: false
alias: normal_sections
owner: ShuntCompensator
domain_of:
- ShuntCompensatorPhase
- ShuntCompensator
range: integer
required: false
phase_connection:
name: phase_connection
description: "The type of phase connection, such as wye or delta.\r\n"
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ShuntCompensator.phaseConnection
multivalued: false
alias: phase_connection
owner: ShuntCompensator
domain_of:
- ShuntCompensator
- EnergyConsumer
range: PhaseShuntConnectionKind
required: false
sections:
name: sections
description: "Shunt compensator sections in use. Starting value for steady state\
\ solution. The attribute shall be a positive value or zero. Non integer values\
\ are allowed to support continuous variables. The reasons for continuous value\
\ are to support study cases where no discrete shunt compensators has yet been\
\ designed, a solutions where a narrow voltage band force the sections to oscillate\
\ or accommodate for a continuous solution as input. \r\nFor LinearShuntConpensator\
\ the value shall be between zero and ShuntCompensator.maximumSections. At value\
\ zero the shunt compensator conductance and admittance is zero. Linear interpolation\
\ of conductance and admittance between the previous and next integer section\
\ is applied in case of non-integer values.\r\nFor NonlinearShuntCompensator-s\
\ shall only be set to one of the NonlinearShuntCompenstorPoint.sectionNumber.\
\ There is no interpolation between NonlinearShuntCompenstorPoint-s."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ShuntCompensator.sections
multivalued: false
alias: sections
owner: ShuntCompensator
domain_of:
- ShuntCompensatorPhase
- ShuntCompensator
- SvShuntCompensatorSections
range: float
required: false
switch_on_count:
name: switch_on_count
description: The switch on count since the capacitor count was last reset or initialized.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ShuntCompensator.switchOnCount
multivalued: false
alias: switch_on_count
owner: ShuntCompensator
domain_of:
- Switch
- ShuntCompensator
range: integer
required: false
switch_on_date:
name: switch_on_date
description: The date and time when the capacitor bank was last switched on.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ShuntCompensator.switchOnDate
multivalued: false
alias: switch_on_date
owner: ShuntCompensator
domain_of:
- Switch
- ShuntCompensator
range: date
required: false
voltage_sensitivity:
name: voltage_sensitivity
description: Voltage sensitivity required for the device to regulate the bus voltage,
in voltage/reactive power.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ShuntCompensator.voltageSensitivity
multivalued: false
alias: voltage_sensitivity
owner: ShuntCompensator
domain_of:
- ShuntCompensator
range: VoltagePerReactivePower
required: false
shunt_compensator_phase:
name: shunt_compensator_phase
description: The individual phases models for the shunt compensator.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ShuntCompensator.ShuntCompensatorPhase
multivalued: true
alias: shunt_compensator_phase
owner: ShuntCompensator
domain_of:
- ShuntCompensator
range: ShuntCompensatorPhase
required: false
shunt_compensator_action:
name: shunt_compensator_action
description: The shunt compensator action that is performed on the shunt compensator
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ShuntCompensator.ShuntCompensatorAction
multivalued: false
alias: shunt_compensator_action
owner: ShuntCompensator
domain_of:
- ShuntCompensator
range: ShuntCompensatorAction
required: false
sv_shunt_compensator_sections:
name: sv_shunt_compensator_sections
description: The state for the number of shunt compensator sections in service.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ShuntCompensator.SvShuntCompensatorSections
multivalued: true
alias: sv_shunt_compensator_sections
owner: ShuntCompensator
domain_of:
- ShuntCompensator
range: SvShuntCompensatorSections
required: false
control_enabled:
name: control_enabled
description: Specifies the regulation status of the equipment. True is regulating,
false is not regulating.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:RegulatingCondEq.controlEnabled
multivalued: false
alias: control_enabled
owner: ShuntCompensator
domain_of:
- RegulatingCondEq
- TapChanger
range: boolean
required: false
regulating_control:
name: regulating_control
description: The regulating control scheme in which this equipment participates.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:RegulatingCondEq.RegulatingControl
multivalued: false
alias: regulating_control
owner: ShuntCompensator
domain_of:
- Terminal
- RegulatingCondEq
- RegulationSchedule
- ProtectiveActionRegulation
range: RegulatingControl
required: false
energy_component:
name: energy_component
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:EnergyConnection.EnergyComponent
multivalued: true
alias: energy_component
owner: ShuntCompensator
domain_of:
- EnergyGroup
- EnergyConnection
range: EnergyComponent
required: false
protective_action_adjustment:
name: protective_action_adjustment
description: 'The operating condition to the Conducting Equipment is changed when
protective action adjustment is activated. For ShuntCompensator or other conducting
equipment that operates on discrete values (integer), the values given in float
will be rounded. '
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ConductingEquipment.ProtectiveActionAdjustment
multivalued: true
alias: protective_action_adjustment
owner: ShuntCompensator
domain_of:
- Measurement
- ConductingEquipment
- DCConductingEquipment
range: ProtectiveActionAdjustment
required: false
sv_status:
name: sv_status
description: The status state variable associated with this conducting equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ConductingEquipment.SvStatus
multivalued: true
alias: sv_status
owner: ShuntCompensator
domain_of:
- ConductingEquipment
range: SvStatus
required: false
protection_equipments:
name: protection_equipments
description: 'Protection equipment used to protect specific conducting equipment. '
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ConductingEquipment.ProtectionEquipments
multivalued: true
alias: protection_equipments
owner: ShuntCompensator
domain_of:
- ConductingEquipment
range: ProtectionEquipment
required: false
base_voltage:
name: base_voltage
description: Base voltage of this conducting equipment. Use only when there is
no voltage level container used and only one base voltage applies. For example,
not used for transformers.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ConductingEquipment.BaseVoltage
multivalued: false
alias: base_voltage
owner: ShuntCompensator
domain_of:
- TopologicalNode
- TransformerEnd
- ConductingEquipment
- VoltageLevel
- AssetDeployment
range: BaseVoltage
required: false
terminals:
name: terminals
description: Conducting equipment have terminals that may be connected to other
conducting equipment terminals via connectivity nodes or topological nodes.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ConductingEquipment.Terminals
multivalued: true
alias: terminals
owner: ShuntCompensator
domain_of:
- ConnectivityNode
- ConductingEquipment
range: Terminal
required: false
jumping_action:
name: jumping_action
description: Jumper action involving jumping operation on this conducting equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ConductingEquipment.JumpingAction
multivalued: false
alias: jumping_action
owner: ShuntCompensator
domain_of:
- ConductingEquipment
range: JumperAction
required: false
grounding_action:
name: grounding_action
description: Action involving grounding operation on this conducting equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ConductingEquipment.GroundingAction
multivalued: false
alias: grounding_action
owner: ShuntCompensator
domain_of:
- ConductingEquipment
range: GroundAction
required: false
outage:
name: outage
description: The outage that is isolated by the outage isolation equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ConductingEquipment.Outage
multivalued: false
alias: outage
owner: ShuntCompensator
domain_of:
- Incident
- SwitchingPlan
- UsagePoint
- ConductingEquipment
- Crew
- EstimatedRestorationTime
- OutageArea
- Fault
range: Outage
required: false
aggregate:
name: aggregate
description: "The aggregate flag provides an alternative way of representing an\
\ aggregated (equivalent) element. It is applicable in cases when the dedicated\
\ classes for equivalent equipment do not have all of the attributes necessary\
\ to represent the required level of detail. In case the flag is set to “true”\
\ the single instance of equipment represents multiple pieces of equipment that\
\ have been modelled together as an aggregate equivalent obtained by a network\
\ reduction procedure. Examples would be power transformers or synchronous machines\
\ operating in parallel modelled as a single aggregate power transformer or\
\ aggregate synchronous machine. \r\nThe attribute is not used for EquivalentBranch,\
\ EquivalentShunt and EquivalentInjection."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.aggregate
multivalued: false
alias: aggregate
owner: ShuntCompensator
domain_of:
- Equipment
- ReadingType
range: boolean
required: false
in_service:
name: in_service
description: Specifies the availability of the equipment. True means the equipment
is available for topology processing, which determines if the equipment is energized
or not. False means that the equipment is treated by network applications as
if it is not in the model.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.inService
multivalued: false
alias: in_service
owner: ShuntCompensator
domain_of:
- Equipment
- SvStatus
- ProtectiveActionEquipment
range: boolean
required: false
network_analysis_enabled:
name: network_analysis_enabled
description: The equipment is enabled to participate in network analysis. If
unspecified, the value is assumed to be true.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.networkAnalysisEnabled
multivalued: false
alias: network_analysis_enabled
owner: ShuntCompensator
domain_of:
- Equipment
range: boolean
required: false
normally_in_service:
name: normally_in_service
description: Specifies the availability of the equipment under normal operating
conditions. True means the equipment is available for topology processing, which
determines if the equipment is energized or not. False means that the equipment
is treated by network applications as if it is not in the model.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.normallyInService
multivalued: false
alias: normally_in_service
owner: ShuntCompensator
domain_of:
- Equipment
range: boolean
required: false
weather_station:
name: weather_station
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.WeatherStation
multivalued: true
alias: weather_station
owner: ShuntCompensator
domain_of:
- Equipment
range: WeatherStation
required: false
operational_limit_set:
name: operational_limit_set
description: The operational limit sets associated with this equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:Equipment.OperationalLimitSet
multivalued: true
alias: operational_limit_set
owner: ShuntCompensator
domain_of:
- ACDCTerminal
- OperationalLimit
- Equipment
range: OperationalLimitSet
required: false
contingency_equipment:
name: contingency_equipment
description: The contingency equipments in which this equipment participates.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.ContingencyEquipment
multivalued: true
alias: contingency_equipment
owner: ShuntCompensator
domain_of:
- Equipment
range: ContingencyEquipment
required: false
equipment_container:
name: equipment_container
description: Container of this equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.EquipmentContainer
multivalued: false
alias: equipment_container
owner: ShuntCompensator
domain_of:
- Equipment
range: EquipmentContainer
required: false
faults:
name: faults
description: All faults on this equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.Faults
multivalued: true
alias: faults
owner: ShuntCompensator
domain_of:
- Equipment
- Outage
- FaultCauseType
range: Fault
required: false
limit_dependency_model:
name: limit_dependency_model
description: Limit dependencymodels organized under this equipment as a means
for organizing the model in a tree view.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:Equipment.LimitDependencyModel
multivalued: true
alias: limit_dependency_model
owner: ShuntCompensator
domain_of:
- OperationalLimit
- Equipment
range: LimitDependency
required: false
eqiupment_limit_series_component:
name: eqiupment_limit_series_component
description: Equipment limit series calculation component to which this equipment
contributes.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.EqiupmentLimitSeriesComponent
multivalued: true
alias: eqiupment_limit_series_component
owner: ShuntCompensator
domain_of:
- Equipment
range: EquipmentLimitSeriesComponent
required: false
protective_action_equipment:
name: protective_action_equipment
description: Protective action is controlling equipment. This can be direct signals
from the control center, or emulation of action done by protection equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.ProtectiveActionEquipment
multivalued: true
alias: protective_action_equipment
owner: ShuntCompensator
domain_of:
- Equipment
range: ProtectiveActionEquipment
required: false
pin_equipment:
name: pin_equipment
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.PinEquipment
multivalued: true
alias: pin_equipment
owner: ShuntCompensator
domain_of:
- Equipment
range: PinEquipment
required: false
equipment_unavailability_schedule:
name: equipment_unavailability_schedule
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.EquipmentUnavailabilitySchedule
multivalued: true
alias: equipment_unavailability_schedule
owner: ShuntCompensator
domain_of:
- Equipment
- UnavailabilitySwitchAction
- UnavailablitySchedule
range: EquipmentUnavailabilitySchedule
required: false
additional_equipment_container:
name: additional_equipment_container
description: Additional equipment container beyond the primary equipment container. The
equipment is contained in another equipment container, but also grouped with
this equipment container.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.AdditionalEquipmentContainer
multivalued: true
alias: additional_equipment_container
owner: ShuntCompensator
domain_of:
- Equipment
range: EquipmentContainer
required: false
usage_points:
name: usage_points
description: All usage points connected to the electrical grid through this equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.UsagePoints
multivalued: true
alias: usage_points
owner: ShuntCompensator
domain_of:
- Equipment
- CustomerAgreement
- ServiceCategory
- PricingStructure
- EndDeviceControl
- UsagePointGroup
- ServiceLocation
- MetrologyRequirement
- ServiceSupplier
- UsagePointLocation
range: UsagePoint
required: false
outages:
name: outages
description: All outages in which this equipment is involved.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.Outages
multivalued: true
alias: outages
owner: ShuntCompensator
domain_of:
- Equipment
range: Outage
required: false
operational_restrictions:
name: operational_restrictions
description: All operational restrictions for this equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.OperationalRestrictions
multivalued: true
alias: operational_restrictions
owner: ShuntCompensator
domain_of:
- Equipment
- ProductAssetModel
range: OperationalRestriction
required: false
controls:
name: controls
description: The controller outputs used to actually govern a regulating device,
e.g. the magnetization of a synchronous machine or capacitor bank breaker actuator.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.Controls
multivalued: true
alias: controls
owner: ShuntCompensator
domain_of:
- PowerSystemResource
- HostControlArea
range: Control
required: false
measurements:
name: measurements
description: The measurements associated with this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.Measurements
multivalued: true
alias: measurements
owner: ShuntCompensator
domain_of:
- PowerSystemResource
- ACDCTerminal
- Asset
- Location
- Procedure
- AnalogLimitSet
- AccumulatorLimitSet
range: Measurement
required: false
psrtype:
name: psrtype
description: Custom classification for this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.PSRType
multivalued: false
alias: psrtype
owner: ShuntCompensator
domain_of:
- PowerSystemResource
range: PSRType
required: false
configuration_event:
name: configuration_event
description: All configuration events created for this Power System resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.ConfigurationEvent
multivalued: true
alias: configuration_event
owner: ShuntCompensator
domain_of:
- PowerSystemResource
- FaultCauseType
range: ConfigurationEvent
required: false
reporting_group:
name: reporting_group
description: Reporting groups to which this power system resource belongs.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.ReportingGroup
multivalued: true
alias: reporting_group
owner: ShuntCompensator
domain_of:
- PowerSystemResource
- BusNameMarker
- TopologicalNode
- ReportingSuperGroup
range: ReportingGroup
required: false
operating_share:
name: operating_share
description: The operating shares of this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.OperatingShare
multivalued: true
alias: operating_share
owner: ShuntCompensator
domain_of:
- PowerSystemResource
- OperatingParticipant
range: OperatingShare
required: false
asset_datasheet:
name: asset_datasheet
description: Datasheet information for this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.AssetDatasheet
multivalued: false
alias: asset_datasheet
owner: ShuntCompensator
domain_of:
- PowerSystemResource
range: AssetInfo
required: false
verification_action:
name: verification_action
description: The verification action that is performed on the power system resource
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.VerificationAction
multivalued: true
alias: verification_action
owner: ShuntCompensator
domain_of:
- PowerSystemResource
range: VerificationAction
required: false
clearances:
name: clearances
description: All clearances applicable to this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.Clearances
multivalued: true
alias: clearances
owner: ShuntCompensator
domain_of:
- PowerSystemResource
range: ClearanceDocument
required: false
generic_action:
name: generic_action
description: The generic action that is performed on the power system resource
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.GenericAction
multivalued: true
alias: generic_action
owner: ShuntCompensator
domain_of:
- PowerSystemResource
range: GenericAction
required: false
psrevents:
name: psrevents
description: All events associated with this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.PSREvents
multivalued: true
alias: psrevents
owner: ShuntCompensator
domain_of:
- PowerSystemResource
range: PSREvent
required: false
assets:
name: assets
description: All assets represented by this power system resource. For example,
multiple conductor assets are electrically modelled as a single AC line segment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.Assets
multivalued: true
alias: assets
owner: ShuntCompensator
domain_of:
- PowerSystemResource
- AssetInfo
- Location
- WorkTask
- ErpRecDelvLineItem
- AssetContainer
- ActivityRecord
- Procedure
- ReliabilityInfo
- AssetPropertyCurve
- AssetOrganisationRole
- ScheduledEvent
range: Asset
required: false
location:
name: location
description: Location of this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.Location
multivalued: false
alias: location
owner: ShuntCompensator
domain_of:
- PowerSystemResource
- Asset
- Incident
- SwitchingOrder
- TroubleOrder
- Crew
- Fault
- PointOfSale
- TroubleTicket
- OutageOrder
- EnvironmentalMonitoringStation
- EnvironmentalLocationType
- PositionPoint
- FailureEvent
range: Location
required: false
operational_tags:
name: operational_tags
description: All operational tags placed on this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.OperationalTags
multivalued: true
alias: operational_tags
owner: ShuntCompensator
domain_of:
- PowerSystemResource
- Asset
range: OperationalTag
required: false
alias_name:
name: alias_name
description: "The aliasName is free text human readable name of the object alternative\
\ to IdentifiedObject.name. It may be non unique and may not correlate to a\
\ naming hierarchy.\r\nThe attribute aliasName is retained because of backwards\
\ compatibility between CIM relases. It is however recommended to replace aliasName\
\ with the Name class as aliasName is planned for retirement at a future time.\r\
\n\r\n"
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.aliasName
multivalued: false
alias: alias_name
owner: ShuntCompensator
domain_of:
- IdentifiedObject
range: string
required: false
description:
name: description
description: The description is a free human readable text describing or naming
the object. It may be non unique and may not correlate to a naming hierarchy.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.description
multivalued: false
alias: description
owner: ShuntCompensator
domain_of:
- IdentifiedObject
- NameType
- NameTypeAuthority
- DataSet
- SwitchingStepGroup
- AreaReserveSpec
range: string
required: false
m_rid:
name: m_rid
description: "Master resource identifier issued by a model authority. The mRID\
\ is unique within an exchange context. Global uniqueness is easily achieved\
\ by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is\
\ strongly recommended.\r\nFor CIMXML data files in RDF syntax conforming to\
\ IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify\
\ CIM object elements."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.mRID
multivalued: false
alias: m_rid
owner: ShuntCompensator
domain_of:
- IdentifiedObject
- DataSet
range: string
required: false
diagram_objects:
name: diagram_objects
description: The diagram objects that are associated with the domain object.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.DiagramObjects
multivalued: true
alias: diagram_objects
owner: ShuntCompensator
domain_of:
- IdentifiedObject
range: DiagramObject
required: false
instance_set:
name: instance_set
description: Dataset containing the data objects.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.InstanceSet
multivalued: false
alias: instance_set
owner: ShuntCompensator
domain_of:
- IdentifiedObject
range: InstanceSet
required: true
names:
name: names
description: All names of this identified object.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.Names
multivalued: true
alias: names
owner: ShuntCompensator
domain_of:
- IdentifiedObject
- NameType
range: Name
required: false
properties_cimdata_object:
name: properties_cimdata_object
description: The single CIM data object in the appropriate dataset context.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.PropertiesCIMDataObject
multivalued: false
alias: properties_cimdata_object
owner: ShuntCompensator
domain_of:
- IdentifiedObject
range: ChangeSetMember
required: false
targeting_cimdata_object:
name: targeting_cimdata_object
description: Data objects registered.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.TargetingCIMDataObject
multivalued: true
alias: targeting_cimdata_object
owner: ShuntCompensator
domain_of:
- IdentifiedObject
range: ChangeSetMember
required: false
class_uri: cim:ShuntCompensator