Class: GovHydroPelton
_Detailed hydro unit - Pelton model. This model can be used to represent the dynamic related to water tunnel and surge chamber. _
The DetailedHydroModelHydraulicSystem diagram, located under the GovHydroFrancis class, provides a schematic of the hydraulic system of detailed hydro unit models, such as Francis and Pelton.
URI: cim:GovHydroPelton
classDiagram
class GovHydroPelton
TurbineGovernorDynamics <|-- GovHydroPelton
GovHydroPelton : alias_name
GovHydroPelton : asynchronous_machine_dynamics
GovHydroPelton --> AsynchronousMachineDynamics : asynchronous_machine_dynamics
GovHydroPelton : av
GovHydroPelton --> Area : av
GovHydroPelton : bp
GovHydroPelton --> PU : bp
GovHydroPelton : db
GovHydroPelton --> Frequency : db
GovHydroPelton : description
GovHydroPelton : diagram_objects
GovHydroPelton --> DiagramObject : diagram_objects
GovHydroPelton : enabled
GovHydroPelton : h
GovHydroPelton --> Length : h
GovHydroPelton : hn
GovHydroPelton --> Length : hn
GovHydroPelton : instance_set
GovHydroPelton --> InstanceSet : instance_set
GovHydroPelton : kc
GovHydroPelton --> PU : kc
GovHydroPelton : kg
GovHydroPelton --> PU : kg
GovHydroPelton : m_rid
GovHydroPelton : names
GovHydroPelton --> Name : names
GovHydroPelton : properties_cimdata_object
GovHydroPelton --> ChangeSetMember : properties_cimdata_object
GovHydroPelton : qc
GovHydroPelton --> PU : qc
GovHydroPelton : qn
GovHydroPelton --> VolumeFlowRate : qn
GovHydroPelton : simplified_pelton
GovHydroPelton : static_compensating
GovHydroPelton : synchronous_machine_dynamics
GovHydroPelton --> SynchronousMachineDynamics : synchronous_machine_dynamics
GovHydroPelton : ta
GovHydroPelton --> Seconds : ta
GovHydroPelton : targeting_cimdata_object
GovHydroPelton --> ChangeSetMember : targeting_cimdata_object
GovHydroPelton : ts
GovHydroPelton --> Seconds : ts
GovHydroPelton : turbine_load_controller_dynamics
GovHydroPelton --> TurbineLoadControllerDynamics : turbine_load_controller_dynamics
GovHydroPelton : tv
GovHydroPelton --> Seconds : tv
GovHydroPelton : twnc
GovHydroPelton --> Seconds : twnc
GovHydroPelton : twng
GovHydroPelton --> Seconds : twng
GovHydroPelton : tx
GovHydroPelton --> Seconds : tx
GovHydroPelton : va
GovHydroPelton : valvmax
GovHydroPelton --> PU : valvmax
GovHydroPelton : valvmin
GovHydroPelton --> PU : valvmin
GovHydroPelton : vav
GovHydroPelton --> PU : vav
GovHydroPelton : vc
GovHydroPelton : vcv
GovHydroPelton --> PU : vcv
GovHydroPelton : water_tunnel_surge_chamber_simulation
GovHydroPelton : zsfc
GovHydroPelton --> Length : zsfc
Inheritance
- IdentifiedObject
- DynamicsFunctionBlock
- TurbineGovernorDynamics
- GovHydroPelton
- TurbineGovernorDynamics
- DynamicsFunctionBlock
Slots
| Name | Cardinality and Range | Description | Inheritance |
|---|---|---|---|
| av | 0..1 Area |
Area of the compensation tank (AV1) | direct |
| bp | 0..1 PU |
Droop (bp) | direct |
| db | 0..1 Frequency |
Intentional dead-band width of valve opening error (DB2) | direct |
| h | 0..1 Length |
Head of surge tank water level with respect to the level of penstock (H</i... | direct |
| hn | 0..1 Length |
Rated hydraulic head (Hn) | direct |
| kc | 0..1 PU |
Penstock loss coefficient (due to friction) (Kc) | direct |
| kg | 0..1 PU |
Water tunnel and surge chamber loss coefficient (due to friction) (Kg) | direct |
| qc | 0..1 PU |
No-load turbine flow at nominal head (Qc0) | direct |
| qn | 0..1 VolumeFlowRate |
Rated flow (Qn) | direct |
| simplified_pelton | 0..1 Boolean |
Simplified Pelton model simulation (Sflag) | direct |
| static_compensating | 0..1 Boolean |
Static compensating characteristic (Cflag) | direct |
| ta | 0..1 Seconds |
Derivative gain (accelerometer time constant) (Ta) (>= 0) | direct |
| ts | 0..1 Seconds |
Gate servo time constant (Ts) (>= 0) | direct |
| tv | 0..1 Seconds |
Servomotor integrator time constant (Tv) (>= 0) | direct |
| twnc | 0..1 Seconds |
Water inertia time constant (Twnc) (>= 0) | direct |
| twng | 0..1 Seconds |
Water tunnel and surge chamber inertia time constant (Twng) (>= 0) | direct |
| tx | 0..1 Seconds |
Electronic integrator time constant (Tx) (>= 0) | direct |
| va | 0..1 Float |
Maximum gate opening velocity (Va) | direct |
| valvmax | 0..1 PU |
Maximum gate opening (ValvMax) (> GovHydroPelton | direct |
| valvmin | 0..1 PU |
Minimum gate opening (ValvMin) (< GovHydroPelton | direct |
| vav | 0..1 PU |
Maximum servomotor valve opening velocity (Vav) | direct |
| vc | 0..1 Float |
Maximum gate closing velocity (Vc) | direct |
| vcv | 0..1 PU |
Maximum servomotor valve closing velocity (Vcv) | direct |
| water_tunnel_surge_chamber_simulation | 0..1 Boolean |
Water tunnel and surge chamber simulation (Tflag) | direct |
| zsfc | 0..1 Length |
Head of upper water level with respect to the level of penstock (Zsfc) | direct |
| asynchronous_machine_dynamics | 0..1 AsynchronousMachineDynamics |
Asynchronous machine model with which this turbine-governor model is associat... | TurbineGovernorDynamics |
| turbine_load_controller_dynamics | 0..1 TurbineLoadControllerDynamics |
Turbine load controller providing input to this turbine-governor | TurbineGovernorDynamics |
| synchronous_machine_dynamics | 0..1 SynchronousMachineDynamics |
Synchronous machine model with which this turbine-governor model is associate... | TurbineGovernorDynamics |
| enabled | 0..1 Boolean |
Function block used indicator | DynamicsFunctionBlock |
| alias_name | 0..1 String |
The aliasName is free text human readable name of the object alternative to I... | IdentifiedObject |
| description | 0..1 String |
The description is a free human readable text describing or naming the object | IdentifiedObject |
| m_rid | 0..1 String |
Master resource identifier issued by a model authority | IdentifiedObject |
| diagram_objects | 0..* DiagramObject |
The diagram objects that are associated with the domain object | IdentifiedObject |
| instance_set | 1..1 InstanceSet |
Dataset containing the data objects | IdentifiedObject |
| names | 0..* Name |
All names of this identified object | IdentifiedObject |
| properties_cimdata_object | 0..1 ChangeSetMember |
The single CIM data object in the appropriate dataset context | IdentifiedObject |
| targeting_cimdata_object | 0..* ChangeSetMember |
Data objects registered | IdentifiedObject |
Identifier and Mapping Information
Schema Source
- from schema: https://cim.ucaiug.io/ns#TC57CIM
Mappings
| Mapping Type | Mapped Value |
|---|---|
| self | cim:GovHydroPelton |
| native | cim:GovHydroPelton |
LinkML Source
Direct
name: GovHydroPelton
description: "Detailed hydro unit - Pelton model. This model can be used to represent\
\ the dynamic related to water tunnel and surge chamber.\r\nThe DetailedHydroModelHydraulicSystem\
\ diagram, located under the GovHydroFrancis class, provides a schematic of the\
\ hydraulic system of detailed hydro unit models, such as Francis and Pelton."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
is_a: TurbineGovernorDynamics
attributes:
av:
name: av
description: Area of the compensation tank (<i>A</i><i><sub>V1</sub></i>). Unit
= m<sup>2</sup>. Typical value = 700.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.av1
multivalued: false
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: Area
required: false
bp:
name: bp
description: Droop (<i>bp</i>). Typical value = 0,05.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.bp
multivalued: false
domain_of:
- GovGAST3
- GovGAST4
- GovHydroFrancis
- GovHydroPelton
range: PU
required: false
db:
name: db
description: Intentional dead-band width of valve opening error (<i>DB2</i>).
Unit = Hz. Typical value = 0,01.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.db2
multivalued: false
domain_of:
- GovCT1
- GovCT2
- GovGAST1
- GovHydro2
- GovHydro3
- GovHydro4
- GovHydroDD
- GovHydroFrancis
- GovHydroPelton
- GovHydroPID
- GovHydroR
- GovHydroWEH
- GovSteam1
- GovSteamEU
- TurbLCFB1
range: Frequency
required: false
h:
name: h
description: Head of surge tank water level with respect to the level of penstock
(<i>H</i><i><sub>2</sub></i>). Unit = km. Typical value = 0,040.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.h2
multivalued: false
domain_of:
- GovHydro3
- GovHydroFrancis
- GovHydroPelton
- GovHydroR
- LoadComposite
- LoadMotor
range: Length
required: false
hn:
name: hn
description: Rated hydraulic head (<i>H</i><i><sub>n</sub></i>). Unit = km. Typical
value = 0,250.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.hn
multivalued: false
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: Length
required: false
kc:
name: kc
description: Penstock loss coefficient (due to friction) (<i>Kc</i>). Typical
value = 0,025.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.kc
multivalued: false
domain_of:
- GovHydroFrancis
- GovHydroPelton
- ExcIEEEAC1A
- ExcIEEEAC2A
- ExcIEEEAC3A
- ExcIEEEAC4A
- ExcIEEEAC6A
- ExcIEEEAC7B
- ExcIEEEAC8B
- ExcIEEEST1A
- ExcIEEEST2A
- ExcIEEEST3A
- ExcIEEEST4B
- ExcIEEEST5B
- ExcAC1A
- ExcAC2A
- ExcAC3A
- ExcAC4A
- ExcAC6A
- ExcAC8B
- ExcOEX3T
- ExcPIC
- ExcREXS
- ExcSEXS
- ExcSK
- ExcST1A
- ExcST2A
- ExcST3A
- ExcST4B
range: PU
required: false
kg:
name: kg
description: Water tunnel and surge chamber loss coefficient (due to friction)
(<i>Kg</i>). Typical value = 0,025.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.kg
multivalued: false
domain_of:
- GovHydro3
- GovHydroDD
- GovHydroFrancis
- GovHydroPelton
- GovHydroPID
- GovHydroR
- GovSteamBB
- ExcIEEEST3A
- ExcIEEEST4B
- ExcIEEEST6B
- ExcST3A
- ExcST4B
- ExcST6B
range: PU
required: false
qc:
name: qc
description: No-load turbine flow at nominal head (<i>Qc0</i>). Typical value
= 0,05.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.qc0
multivalued: false
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: PU
required: false
qn:
name: qn
description: Rated flow (<i>Q</i><i><sub>n</sub></i>). Unit = m<sup>3</sup>/s.
Typical value = 250.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.qn
multivalued: false
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: VolumeFlowRate
required: false
simplified_pelton:
name: simplified_pelton
description: "Simplified Pelton model simulation (<i>Sflag</i>).\r\ntrue = enable\
\ of simplified Pelton model simulation\r\nfalse = enable of complete Pelton\
\ model simulation (non-linear gain).\r\nTypical value = true."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:GovHydroPelton.simplifiedPelton
multivalued: false
domain_of:
- GovHydroPelton
range: boolean
required: false
static_compensating:
name: static_compensating
description: "Static compensating characteristic (<i>Cflag</i>). It should be\
\ true if simplifiedPelton = false.\r\ntrue = enable of static compensating\
\ characteristic \r\nfalse = inhibit of static compensating characteristic.\r\
\nTypical value = false."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:GovHydroPelton.staticCompensating
multivalued: false
domain_of:
- GovHydroPelton
range: boolean
required: false
ta:
name: ta
description: Derivative gain (accelerometer time constant) (<i>Ta</i>) (>=
0). Typical value = 3.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.ta
multivalued: false
domain_of:
- GovCT1
- GovCT2
- GovGAST4
- GovHydroFrancis
- GovHydroPelton
- GovHydroPID2
- GovHydroWPID
- GovSteamFV2
- GovSteamFV3
- GovSteamFV4
- ExcIEEEAC1A
- ExcIEEEAC2A
- ExcIEEEAC3A
- ExcIEEEAC4A
- ExcIEEEAC5A
- ExcIEEEAC6A
- ExcIEEEAC8B
- ExcIEEEDC1A
- ExcIEEEDC2A
- ExcIEEEDC4B
- ExcIEEEST1A
- ExcIEEEST2A
- ExcIEEEST3A
- ExcIEEEST4B
- ExcAC1A
- ExcAC2A
- ExcAC3A
- ExcAC4A
- ExcAC5A
- ExcAC6A
- ExcAC8B
- ExcAVR1
- ExcAVR2
- ExcAVR5
- ExcCZ
- ExcDC1A
- ExcDC2A
- ExcDC3A1
- ExcNI
- ExcPIC
- ExcREXS
- ExcST1A
- ExcST2A
- ExcST4B
- Pss2B
- PssSB4
range: Seconds
required: false
ts:
name: ts
description: Gate servo time constant (<i>Ts</i>) (>= 0). Typical value =
0,15.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.ts
multivalued: false
domain_of:
- GovHydroFrancis
- GovHydroPelton
- ExcELIN1
- ExcST6B
- ExcST7B
- PssELIN2
range: Seconds
required: false
tv:
name: tv
description: Servomotor integrator time constant (<i>Tv</i>) (>= 0). Typical
value = 0,3.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:GovHydroPelton.tv
multivalued: false
domain_of:
- GovHydroPelton
- GovSteamFV4
- LoadMotor
range: Seconds
required: false
twnc:
name: twnc
description: Water inertia time constant (<i>Twnc</i>) (>= 0). Typical value
= 1.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.twnc
multivalued: false
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: Seconds
required: false
twng:
name: twng
description: Water tunnel and surge chamber inertia time constant (<i>Twng</i>)
(>= 0). Typical value = 3.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.twng
multivalued: false
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: Seconds
required: false
tx:
name: tx
description: Electronic integrator time constant (<i>Tx</i>) (>= 0). Typical
value = 0,5.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.tx
multivalued: false
domain_of:
- GovHydroFrancis
- GovHydroPelton
- PssSB4
range: Seconds
required: false
va:
name: va
description: Maximum gate opening velocity (<i>Va</i>). Unit = PU / s. Typical
value = 0,06.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.va
multivalued: false
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: float
required: false
valvmax:
name: valvmax
description: Maximum gate opening (<i>ValvMax</i>) (> GovHydroPelton.valvmin). Typical
value = 1,1.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.valvmax
multivalued: false
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: PU
required: false
valvmin:
name: valvmin
description: Minimum gate opening (<i>ValvMin</i>) (< GovHydroPelton.valvmax). Typical
value = 0.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.valvmin
multivalued: false
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: PU
required: false
vav:
name: vav
description: Maximum servomotor valve opening velocity (<i>Vav</i>). Typical
value = 0,1.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:GovHydroPelton.vav
multivalued: false
domain_of:
- GovHydroPelton
range: PU
required: false
vc:
name: vc
description: Maximum gate closing velocity (<i>Vc</i>). Unit = PU / s. Typical
value = -0,06.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.vc
multivalued: false
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: float
required: false
vcv:
name: vcv
description: Maximum servomotor valve closing velocity (<i>Vcv</i>). Typical
value = -0,1.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:GovHydroPelton.vcv
multivalued: false
domain_of:
- GovHydroPelton
range: PU
required: false
water_tunnel_surge_chamber_simulation:
name: water_tunnel_surge_chamber_simulation
description: "Water tunnel and surge chamber simulation (<i>Tflag</i>).\r\ntrue\
\ = enable of water tunnel and surge chamber simulation\r\nfalse = inhibit of\
\ water tunnel and surge chamber simulation.\r\nTypical value = false."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.waterTunnelSurgeChamberSimulation
multivalued: false
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: boolean
required: false
zsfc:
name: zsfc
description: Head of upper water level with respect to the level of penstock (<i>Zsfc</i>). Unit
= km. Typical value = 0,025.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.zsfc
multivalued: false
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: Length
required: false
class_uri: cim:GovHydroPelton
Induced
name: GovHydroPelton
description: "Detailed hydro unit - Pelton model. This model can be used to represent\
\ the dynamic related to water tunnel and surge chamber.\r\nThe DetailedHydroModelHydraulicSystem\
\ diagram, located under the GovHydroFrancis class, provides a schematic of the\
\ hydraulic system of detailed hydro unit models, such as Francis and Pelton."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
is_a: TurbineGovernorDynamics
attributes:
av:
name: av
description: Area of the compensation tank (<i>A</i><i><sub>V1</sub></i>). Unit
= m<sup>2</sup>. Typical value = 700.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.av1
multivalued: false
alias: av
owner: GovHydroPelton
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: Area
required: false
bp:
name: bp
description: Droop (<i>bp</i>). Typical value = 0,05.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.bp
multivalued: false
alias: bp
owner: GovHydroPelton
domain_of:
- GovGAST3
- GovGAST4
- GovHydroFrancis
- GovHydroPelton
range: PU
required: false
db:
name: db
description: Intentional dead-band width of valve opening error (<i>DB2</i>).
Unit = Hz. Typical value = 0,01.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.db2
multivalued: false
alias: db
owner: GovHydroPelton
domain_of:
- GovCT1
- GovCT2
- GovGAST1
- GovHydro2
- GovHydro3
- GovHydro4
- GovHydroDD
- GovHydroFrancis
- GovHydroPelton
- GovHydroPID
- GovHydroR
- GovHydroWEH
- GovSteam1
- GovSteamEU
- TurbLCFB1
range: Frequency
required: false
h:
name: h
description: Head of surge tank water level with respect to the level of penstock
(<i>H</i><i><sub>2</sub></i>). Unit = km. Typical value = 0,040.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.h2
multivalued: false
alias: h
owner: GovHydroPelton
domain_of:
- GovHydro3
- GovHydroFrancis
- GovHydroPelton
- GovHydroR
- LoadComposite
- LoadMotor
range: Length
required: false
hn:
name: hn
description: Rated hydraulic head (<i>H</i><i><sub>n</sub></i>). Unit = km. Typical
value = 0,250.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.hn
multivalued: false
alias: hn
owner: GovHydroPelton
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: Length
required: false
kc:
name: kc
description: Penstock loss coefficient (due to friction) (<i>Kc</i>). Typical
value = 0,025.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.kc
multivalued: false
alias: kc
owner: GovHydroPelton
domain_of:
- GovHydroFrancis
- GovHydroPelton
- ExcIEEEAC1A
- ExcIEEEAC2A
- ExcIEEEAC3A
- ExcIEEEAC4A
- ExcIEEEAC6A
- ExcIEEEAC7B
- ExcIEEEAC8B
- ExcIEEEST1A
- ExcIEEEST2A
- ExcIEEEST3A
- ExcIEEEST4B
- ExcIEEEST5B
- ExcAC1A
- ExcAC2A
- ExcAC3A
- ExcAC4A
- ExcAC6A
- ExcAC8B
- ExcOEX3T
- ExcPIC
- ExcREXS
- ExcSEXS
- ExcSK
- ExcST1A
- ExcST2A
- ExcST3A
- ExcST4B
range: PU
required: false
kg:
name: kg
description: Water tunnel and surge chamber loss coefficient (due to friction)
(<i>Kg</i>). Typical value = 0,025.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.kg
multivalued: false
alias: kg
owner: GovHydroPelton
domain_of:
- GovHydro3
- GovHydroDD
- GovHydroFrancis
- GovHydroPelton
- GovHydroPID
- GovHydroR
- GovSteamBB
- ExcIEEEST3A
- ExcIEEEST4B
- ExcIEEEST6B
- ExcST3A
- ExcST4B
- ExcST6B
range: PU
required: false
qc:
name: qc
description: No-load turbine flow at nominal head (<i>Qc0</i>). Typical value
= 0,05.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.qc0
multivalued: false
alias: qc
owner: GovHydroPelton
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: PU
required: false
qn:
name: qn
description: Rated flow (<i>Q</i><i><sub>n</sub></i>). Unit = m<sup>3</sup>/s.
Typical value = 250.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.qn
multivalued: false
alias: qn
owner: GovHydroPelton
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: VolumeFlowRate
required: false
simplified_pelton:
name: simplified_pelton
description: "Simplified Pelton model simulation (<i>Sflag</i>).\r\ntrue = enable\
\ of simplified Pelton model simulation\r\nfalse = enable of complete Pelton\
\ model simulation (non-linear gain).\r\nTypical value = true."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:GovHydroPelton.simplifiedPelton
multivalued: false
alias: simplified_pelton
owner: GovHydroPelton
domain_of:
- GovHydroPelton
range: boolean
required: false
static_compensating:
name: static_compensating
description: "Static compensating characteristic (<i>Cflag</i>). It should be\
\ true if simplifiedPelton = false.\r\ntrue = enable of static compensating\
\ characteristic \r\nfalse = inhibit of static compensating characteristic.\r\
\nTypical value = false."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:GovHydroPelton.staticCompensating
multivalued: false
alias: static_compensating
owner: GovHydroPelton
domain_of:
- GovHydroPelton
range: boolean
required: false
ta:
name: ta
description: Derivative gain (accelerometer time constant) (<i>Ta</i>) (>=
0). Typical value = 3.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.ta
multivalued: false
alias: ta
owner: GovHydroPelton
domain_of:
- GovCT1
- GovCT2
- GovGAST4
- GovHydroFrancis
- GovHydroPelton
- GovHydroPID2
- GovHydroWPID
- GovSteamFV2
- GovSteamFV3
- GovSteamFV4
- ExcIEEEAC1A
- ExcIEEEAC2A
- ExcIEEEAC3A
- ExcIEEEAC4A
- ExcIEEEAC5A
- ExcIEEEAC6A
- ExcIEEEAC8B
- ExcIEEEDC1A
- ExcIEEEDC2A
- ExcIEEEDC4B
- ExcIEEEST1A
- ExcIEEEST2A
- ExcIEEEST3A
- ExcIEEEST4B
- ExcAC1A
- ExcAC2A
- ExcAC3A
- ExcAC4A
- ExcAC5A
- ExcAC6A
- ExcAC8B
- ExcAVR1
- ExcAVR2
- ExcAVR5
- ExcCZ
- ExcDC1A
- ExcDC2A
- ExcDC3A1
- ExcNI
- ExcPIC
- ExcREXS
- ExcST1A
- ExcST2A
- ExcST4B
- Pss2B
- PssSB4
range: Seconds
required: false
ts:
name: ts
description: Gate servo time constant (<i>Ts</i>) (>= 0). Typical value =
0,15.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.ts
multivalued: false
alias: ts
owner: GovHydroPelton
domain_of:
- GovHydroFrancis
- GovHydroPelton
- ExcELIN1
- ExcST6B
- ExcST7B
- PssELIN2
range: Seconds
required: false
tv:
name: tv
description: Servomotor integrator time constant (<i>Tv</i>) (>= 0). Typical
value = 0,3.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:GovHydroPelton.tv
multivalued: false
alias: tv
owner: GovHydroPelton
domain_of:
- GovHydroPelton
- GovSteamFV4
- LoadMotor
range: Seconds
required: false
twnc:
name: twnc
description: Water inertia time constant (<i>Twnc</i>) (>= 0). Typical value
= 1.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.twnc
multivalued: false
alias: twnc
owner: GovHydroPelton
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: Seconds
required: false
twng:
name: twng
description: Water tunnel and surge chamber inertia time constant (<i>Twng</i>)
(>= 0). Typical value = 3.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.twng
multivalued: false
alias: twng
owner: GovHydroPelton
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: Seconds
required: false
tx:
name: tx
description: Electronic integrator time constant (<i>Tx</i>) (>= 0). Typical
value = 0,5.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.tx
multivalued: false
alias: tx
owner: GovHydroPelton
domain_of:
- GovHydroFrancis
- GovHydroPelton
- PssSB4
range: Seconds
required: false
va:
name: va
description: Maximum gate opening velocity (<i>Va</i>). Unit = PU / s. Typical
value = 0,06.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.va
multivalued: false
alias: va
owner: GovHydroPelton
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: float
required: false
valvmax:
name: valvmax
description: Maximum gate opening (<i>ValvMax</i>) (> GovHydroPelton.valvmin). Typical
value = 1,1.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.valvmax
multivalued: false
alias: valvmax
owner: GovHydroPelton
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: PU
required: false
valvmin:
name: valvmin
description: Minimum gate opening (<i>ValvMin</i>) (< GovHydroPelton.valvmax). Typical
value = 0.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.valvmin
multivalued: false
alias: valvmin
owner: GovHydroPelton
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: PU
required: false
vav:
name: vav
description: Maximum servomotor valve opening velocity (<i>Vav</i>). Typical
value = 0,1.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:GovHydroPelton.vav
multivalued: false
alias: vav
owner: GovHydroPelton
domain_of:
- GovHydroPelton
range: PU
required: false
vc:
name: vc
description: Maximum gate closing velocity (<i>Vc</i>). Unit = PU / s. Typical
value = -0,06.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.vc
multivalued: false
alias: vc
owner: GovHydroPelton
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: float
required: false
vcv:
name: vcv
description: Maximum servomotor valve closing velocity (<i>Vcv</i>). Typical
value = -0,1.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:GovHydroPelton.vcv
multivalued: false
alias: vcv
owner: GovHydroPelton
domain_of:
- GovHydroPelton
range: PU
required: false
water_tunnel_surge_chamber_simulation:
name: water_tunnel_surge_chamber_simulation
description: "Water tunnel and surge chamber simulation (<i>Tflag</i>).\r\ntrue\
\ = enable of water tunnel and surge chamber simulation\r\nfalse = inhibit of\
\ water tunnel and surge chamber simulation.\r\nTypical value = false."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.waterTunnelSurgeChamberSimulation
multivalued: false
alias: water_tunnel_surge_chamber_simulation
owner: GovHydroPelton
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: boolean
required: false
zsfc:
name: zsfc
description: Head of upper water level with respect to the level of penstock (<i>Zsfc</i>). Unit
= km. Typical value = 0,025.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:GovHydroPelton.zsfc
multivalued: false
alias: zsfc
owner: GovHydroPelton
domain_of:
- GovHydroFrancis
- GovHydroPelton
range: Length
required: false
asynchronous_machine_dynamics:
name: asynchronous_machine_dynamics
description: Asynchronous machine model with which this turbine-governor model
is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics
or to AsynchronousMachineDynamics.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:TurbineGovernorDynamics.AsynchronousMachineDynamics
multivalued: false
alias: asynchronous_machine_dynamics
owner: GovHydroPelton
domain_of:
- WindTurbineType1or2Dynamics
- TurbineGovernorDynamics
- MechanicalLoadDynamics
- AsynchronousMachine
range: AsynchronousMachineDynamics
required: false
turbine_load_controller_dynamics:
name: turbine_load_controller_dynamics
description: Turbine load controller providing input to this turbine-governor.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:TurbineGovernorDynamics.TurbineLoadControllerDynamics
multivalued: false
alias: turbine_load_controller_dynamics
owner: GovHydroPelton
domain_of:
- TurbineGovernorDynamics
range: TurbineLoadControllerDynamics
required: false
synchronous_machine_dynamics:
name: synchronous_machine_dynamics
description: Synchronous machine model with which this turbine-governor model
is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics
or to AsynchronousMachineDynamics.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:TurbineGovernorDynamics.SynchronousMachineDynamics
multivalued: false
alias: synchronous_machine_dynamics
owner: GovHydroPelton
domain_of:
- SynchronousMachine
- GenICompensationForGenJ
- ExcitationSystemDynamics
- TurbineGovernorDynamics
- MechanicalLoadDynamics
range: SynchronousMachineDynamics
required: false
enabled:
name: enabled
description: "Function block used indicator.\r\ntrue = use of function block is\
\ enabled\r\nfalse = use of function block is disabled."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:DynamicsFunctionBlock.enabled
multivalued: false
alias: enabled
owner: GovHydroPelton
domain_of:
- ProtectiveAction
- EndDeviceFunction
- RegulatingControl
- DynamicsFunctionBlock
range: boolean
required: false
alias_name:
name: alias_name
description: "The aliasName is free text human readable name of the object alternative\
\ to IdentifiedObject.name. It may be non unique and may not correlate to a\
\ naming hierarchy.\r\nThe attribute aliasName is retained because of backwards\
\ compatibility between CIM relases. It is however recommended to replace aliasName\
\ with the Name class as aliasName is planned for retirement at a future time.\r\
\n\r\n"
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.aliasName
multivalued: false
alias: alias_name
owner: GovHydroPelton
domain_of:
- IdentifiedObject
range: string
required: false
description:
name: description
description: The description is a free human readable text describing or naming
the object. It may be non unique and may not correlate to a naming hierarchy.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.description
multivalued: false
alias: description
owner: GovHydroPelton
domain_of:
- IdentifiedObject
- NameType
- NameTypeAuthority
- DataSet
- SwitchingStepGroup
- AreaReserveSpec
range: string
required: false
m_rid:
name: m_rid
description: "Master resource identifier issued by a model authority. The mRID\
\ is unique within an exchange context. Global uniqueness is easily achieved\
\ by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is\
\ strongly recommended.\r\nFor CIMXML data files in RDF syntax conforming to\
\ IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify\
\ CIM object elements."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.mRID
multivalued: false
alias: m_rid
owner: GovHydroPelton
domain_of:
- IdentifiedObject
- DataSet
range: string
required: false
diagram_objects:
name: diagram_objects
description: The diagram objects that are associated with the domain object.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.DiagramObjects
multivalued: true
alias: diagram_objects
owner: GovHydroPelton
domain_of:
- IdentifiedObject
range: DiagramObject
required: false
instance_set:
name: instance_set
description: Dataset containing the data objects.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.InstanceSet
multivalued: false
alias: instance_set
owner: GovHydroPelton
domain_of:
- IdentifiedObject
range: InstanceSet
required: true
names:
name: names
description: All names of this identified object.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.Names
multivalued: true
alias: names
owner: GovHydroPelton
domain_of:
- IdentifiedObject
- NameType
range: Name
required: false
properties_cimdata_object:
name: properties_cimdata_object
description: The single CIM data object in the appropriate dataset context.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.PropertiesCIMDataObject
multivalued: false
alias: properties_cimdata_object
owner: GovHydroPelton
domain_of:
- IdentifiedObject
range: ChangeSetMember
required: false
targeting_cimdata_object:
name: targeting_cimdata_object
description: Data objects registered.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.TargetingCIMDataObject
multivalued: true
alias: targeting_cimdata_object
owner: GovHydroPelton
domain_of:
- IdentifiedObject
range: ChangeSetMember
required: false
class_uri: cim:GovHydroPelton