Class: EquivalentBranch
The class represents equivalent branches. In cases where a transformer phase shift is modelled and the EquivalentBranch is spanning the same nodes, the impedance quantities for the EquivalentBranch shall consider the needed phase shift.
URI: cim:EquivalentBranch
classDiagram
class EquivalentBranch
EquivalentEquipment <|-- EquivalentBranch
EquivalentBranch : additional_equipment_container
EquivalentBranch --> EquipmentContainer : additional_equipment_container
EquivalentBranch : aggregate
EquivalentBranch : alias_name
EquivalentBranch : asset_datasheet
EquivalentBranch --> AssetInfo : asset_datasheet
EquivalentBranch : assets
EquivalentBranch --> Asset : assets
EquivalentBranch : base_voltage
EquivalentBranch --> BaseVoltage : base_voltage
EquivalentBranch : clearances
EquivalentBranch --> ClearanceDocument : clearances
EquivalentBranch : configuration_event
EquivalentBranch --> ConfigurationEvent : configuration_event
EquivalentBranch : contingency_equipment
EquivalentBranch --> ContingencyEquipment : contingency_equipment
EquivalentBranch : controls
EquivalentBranch --> Control : controls
EquivalentBranch : description
EquivalentBranch : diagram_objects
EquivalentBranch --> DiagramObject : diagram_objects
EquivalentBranch : eqiupment_limit_series_component
EquivalentBranch --> EquipmentLimitSeriesComponent : eqiupment_limit_series_component
EquivalentBranch : equipment_container
EquivalentBranch --> EquipmentContainer : equipment_container
EquivalentBranch : equipment_unavailability_schedule
EquivalentBranch --> EquipmentUnavailabilitySchedule : equipment_unavailability_schedule
EquivalentBranch : equivalent_network
EquivalentBranch --> EquivalentNetwork : equivalent_network
EquivalentBranch : faults
EquivalentBranch --> Fault : faults
EquivalentBranch : generic_action
EquivalentBranch --> GenericAction : generic_action
EquivalentBranch : grounding_action
EquivalentBranch --> GroundAction : grounding_action
EquivalentBranch : in_service
EquivalentBranch : instance_set
EquivalentBranch --> InstanceSet : instance_set
EquivalentBranch : jumping_action
EquivalentBranch --> JumperAction : jumping_action
EquivalentBranch : limit_dependency_model
EquivalentBranch --> LimitDependency : limit_dependency_model
EquivalentBranch : location
EquivalentBranch --> Location : location
EquivalentBranch : m_rid
EquivalentBranch : measurements
EquivalentBranch --> Measurement : measurements
EquivalentBranch : names
EquivalentBranch --> Name : names
EquivalentBranch : negative_r
EquivalentBranch --> Resistance : negative_r
EquivalentBranch : negative_x
EquivalentBranch --> Reactance : negative_x
EquivalentBranch : network_analysis_enabled
EquivalentBranch : normally_in_service
EquivalentBranch : operating_share
EquivalentBranch --> OperatingShare : operating_share
EquivalentBranch : operational_limit_set
EquivalentBranch --> OperationalLimitSet : operational_limit_set
EquivalentBranch : operational_restrictions
EquivalentBranch --> OperationalRestriction : operational_restrictions
EquivalentBranch : operational_tags
EquivalentBranch --> OperationalTag : operational_tags
EquivalentBranch : outage
EquivalentBranch --> Outage : outage
EquivalentBranch : outages
EquivalentBranch --> Outage : outages
EquivalentBranch : pin_equipment
EquivalentBranch --> PinEquipment : pin_equipment
EquivalentBranch : positive_r
EquivalentBranch --> Resistance : positive_r
EquivalentBranch : positive_x
EquivalentBranch --> Reactance : positive_x
EquivalentBranch : properties_cimdata_object
EquivalentBranch --> ChangeSetMember : properties_cimdata_object
EquivalentBranch : protection_equipments
EquivalentBranch --> ProtectionEquipment : protection_equipments
EquivalentBranch : protective_action_adjustment
EquivalentBranch --> ProtectiveActionAdjustment : protective_action_adjustment
EquivalentBranch : protective_action_equipment
EquivalentBranch --> ProtectiveActionEquipment : protective_action_equipment
EquivalentBranch : psrevents
EquivalentBranch --> PSREvent : psrevents
EquivalentBranch : psrtype
EquivalentBranch --> PSRType : psrtype
EquivalentBranch : r
EquivalentBranch --> Resistance : r
EquivalentBranch : reporting_group
EquivalentBranch --> ReportingGroup : reporting_group
EquivalentBranch : sv_status
EquivalentBranch --> SvStatus : sv_status
EquivalentBranch : targeting_cimdata_object
EquivalentBranch --> ChangeSetMember : targeting_cimdata_object
EquivalentBranch : terminals
EquivalentBranch --> Terminal : terminals
EquivalentBranch : usage_points
EquivalentBranch --> UsagePoint : usage_points
EquivalentBranch : verification_action
EquivalentBranch --> VerificationAction : verification_action
EquivalentBranch : weather_station
EquivalentBranch --> WeatherStation : weather_station
EquivalentBranch : x
EquivalentBranch --> Reactance : x
EquivalentBranch : zero_r
EquivalentBranch --> Resistance : zero_r
EquivalentBranch : zero_x
EquivalentBranch --> Reactance : zero_x
Inheritance
- IdentifiedObject
- PowerSystemResource
- Equipment
- ConductingEquipment
- EquivalentEquipment
- EquivalentBranch
- EquivalentEquipment
- ConductingEquipment
- Equipment
- PowerSystemResource
Slots
| Name | Cardinality and Range | Description | Inheritance |
|---|---|---|---|
| negative_r | 0..1 Resistance |
Negative sequence series resistance from terminal sequence 2 to terminal sequ... | direct |
| negative_x | 0..1 Reactance |
Negative sequence series reactance from terminal sequence 2 to terminal seque... | direct |
| positive_r | 0..1 Resistance |
Positive sequence series resistance from terminal sequence 2 to terminal sequ... | direct |
| positive_x | 0..1 Reactance |
Positive sequence series reactance from terminal sequence 2 to terminal seque... | direct |
| r | 0..1 Resistance |
Resistance from terminal sequence 2 to terminal sequence 1 | direct |
| x | 0..1 Reactance |
Reactance from terminal sequence 2 to terminal sequence 1 | direct |
| zero_r | 0..1 Resistance |
Zero sequence series resistance from terminal sequence 2 to terminal sequenc... | direct |
| zero_x | 0..1 Reactance |
Zero sequence series reactance from terminal sequence 2 to terminal sequence ... | direct |
| equivalent_network | 0..1 EquivalentNetwork |
The equivalent where the reduced model belongs | EquivalentEquipment |
| protective_action_adjustment | 0..* ProtectiveActionAdjustment |
The operating condition to the Conducting Equipment is changed when protectiv... | ConductingEquipment |
| sv_status | 0..* SvStatus |
The status state variable associated with this conducting equipment | ConductingEquipment |
| protection_equipments | 0..* ProtectionEquipment |
Protection equipment used to protect specific conducting equipment | ConductingEquipment |
| base_voltage | 0..1 BaseVoltage |
Base voltage of this conducting equipment | ConductingEquipment |
| terminals | 0..* Terminal |
Conducting equipment have terminals that may be connected to other conducting... | ConductingEquipment |
| jumping_action | 0..1 JumperAction |
Jumper action involving jumping operation on this conducting equipment | ConductingEquipment |
| grounding_action | 0..1 GroundAction |
Action involving grounding operation on this conducting equipment | ConductingEquipment |
| outage | 0..1 Outage |
The outage that is isolated by the outage isolation equipment | ConductingEquipment |
| aggregate | 0..1 Boolean |
The aggregate flag provides an alternative way of representing an aggregated ... | Equipment |
| in_service | 0..1 Boolean |
Specifies the availability of the equipment | Equipment |
| network_analysis_enabled | 0..1 Boolean |
The equipment is enabled to participate in network analysis | Equipment |
| normally_in_service | 0..1 Boolean |
Specifies the availability of the equipment under normal operating conditions | Equipment |
| weather_station | 0..* WeatherStation |
Equipment | |
| operational_limit_set | 0..* OperationalLimitSet |
The operational limit sets associated with this equipment | Equipment |
| contingency_equipment | 0..* ContingencyEquipment |
The contingency equipments in which this equipment participates | Equipment |
| equipment_container | 0..1 EquipmentContainer |
Container of this equipment | Equipment |
| faults | 0..* Fault |
All faults on this equipment | Equipment |
| limit_dependency_model | 0..* LimitDependency |
Limit dependencymodels organized under this equipment as a means for organizi... | Equipment |
| eqiupment_limit_series_component | 0..* EquipmentLimitSeriesComponent |
Equipment limit series calculation component to which this equipment contribu... | Equipment |
| protective_action_equipment | 0..* ProtectiveActionEquipment |
Protective action is controlling equipment | Equipment |
| pin_equipment | 0..* PinEquipment |
Equipment | |
| equipment_unavailability_schedule | 0..* EquipmentUnavailabilitySchedule |
Equipment | |
| additional_equipment_container | 0..* EquipmentContainer |
Additional equipment container beyond the primary equipment container | Equipment |
| usage_points | 0..* UsagePoint |
All usage points connected to the electrical grid through this equipment | Equipment |
| outages | 0..* Outage |
All outages in which this equipment is involved | Equipment |
| operational_restrictions | 0..* OperationalRestriction |
All operational restrictions for this equipment | Equipment |
| controls | 0..* Control |
The controller outputs used to actually govern a regulating device, e | PowerSystemResource |
| measurements | 0..* Measurement |
The measurements associated with this power system resource | PowerSystemResource |
| psrtype | 0..1 PSRType |
Custom classification for this power system resource | PowerSystemResource |
| configuration_event | 0..* ConfigurationEvent |
All configuration events created for this Power System resource | PowerSystemResource |
| reporting_group | 0..* ReportingGroup |
Reporting groups to which this power system resource belongs | PowerSystemResource |
| operating_share | 0..* OperatingShare |
The operating shares of this power system resource | PowerSystemResource |
| asset_datasheet | 0..1 AssetInfo |
Datasheet information for this power system resource | PowerSystemResource |
| verification_action | 0..* VerificationAction |
The verification action that is performed on the power system resource | PowerSystemResource |
| clearances | 0..* ClearanceDocument |
All clearances applicable to this power system resource | PowerSystemResource |
| generic_action | 0..* GenericAction |
The generic action that is performed on the power system resource | PowerSystemResource |
| psrevents | 0..* PSREvent |
All events associated with this power system resource | PowerSystemResource |
| assets | 0..* Asset |
All assets represented by this power system resource | PowerSystemResource |
| location | 0..1 Location |
Location of this power system resource | PowerSystemResource |
| operational_tags | 0..* OperationalTag |
All operational tags placed on this power system resource | PowerSystemResource |
| alias_name | 0..1 String |
The aliasName is free text human readable name of the object alternative to I... | IdentifiedObject |
| description | 0..1 String |
The description is a free human readable text describing or naming the object | IdentifiedObject |
| m_rid | 0..1 String |
Master resource identifier issued by a model authority | IdentifiedObject |
| diagram_objects | 0..* DiagramObject |
The diagram objects that are associated with the domain object | IdentifiedObject |
| instance_set | 1..1 InstanceSet |
Dataset containing the data objects | IdentifiedObject |
| names | 0..* Name |
All names of this identified object | IdentifiedObject |
| properties_cimdata_object | 0..1 ChangeSetMember |
The single CIM data object in the appropriate dataset context | IdentifiedObject |
| targeting_cimdata_object | 0..* ChangeSetMember |
Data objects registered | IdentifiedObject |
Identifier and Mapping Information
Schema Source
- from schema: https://cim.ucaiug.io/ns#TC57CIM
Mappings
| Mapping Type | Mapped Value |
|---|---|
| self | cim:EquivalentBranch |
| native | cim:EquivalentBranch |
LinkML Source
Direct
name: EquivalentBranch
description: The class represents equivalent branches. In cases where a transformer
phase shift is modelled and the EquivalentBranch is spanning the same nodes, the
impedance quantities for the EquivalentBranch shall consider the needed phase shift.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
is_a: EquivalentEquipment
attributes:
negative_r:
name: negative_r
description: "Negative sequence series resistance from terminal sequence 2 to\
\ terminal sequence 1. Used for short circuit data exchange according to IEC\
\ 60909.\r\nEquivalentBranch is a result of network reduction prior to the data\
\ exchange."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:EquivalentBranch.negativeR21
multivalued: false
domain_of:
- EquivalentBranch
range: Resistance
required: false
negative_x:
name: negative_x
description: "Negative sequence series reactance from terminal sequence 2 to terminal\
\ sequence 1. Used for short circuit data exchange according to IEC 60909.\r\
\nUsage: EquivalentBranch is a result of network reduction prior to the data\
\ exchange."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:EquivalentBranch.negativeX21
multivalued: false
domain_of:
- EquivalentBranch
range: Reactance
required: false
positive_r:
name: positive_r
description: "Positive sequence series resistance from terminal sequence 2 to\
\ terminal sequence 1. Used for short circuit data exchange according to IEC\
\ 60909.\r\nEquivalentBranch is a result of network reduction prior to the data\
\ exchange."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:EquivalentBranch.positiveR21
multivalued: false
domain_of:
- EquivalentBranch
range: Resistance
required: false
positive_x:
name: positive_x
description: "Positive sequence series reactance from terminal sequence 2 to terminal\
\ sequence 1. Used for short circuit data exchange according to IEC 60909.\r\
\nUsage : EquivalentBranch is a result of network reduction prior to the data\
\ exchange."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:EquivalentBranch.positiveX21
multivalued: false
domain_of:
- EquivalentBranch
range: Reactance
required: false
r:
name: r
description: "Resistance from terminal sequence 2 to terminal sequence 1 .Used\
\ for steady state power flow. This attribute is optional and represent unbalanced\
\ network such as off-nominal phase shifter. If only EquivalentBranch.r is given,\
\ then EquivalentBranch.r21 is assumed equal to EquivalentBranch.r.\r\nUsage\
\ rule : EquivalentBranch is a result of network reduction prior to the data\
\ exchange."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:EquivalentBranch.r21
multivalued: false
domain_of:
- MutualCoupling
- TransformerMeshImpedance
- TransformerEndInfo
- PowerTransformerEnd
- ACLineSegment
- SynchronousMachine
- EquivalentInjection
- PowerElectronicsConnection
- SeriesCompensator
- TransformerStarImpedance
- TapChangerTablePoint
- PerLengthSequenceImpedance
- PhaseImpedanceData
- EarthFaultCompensator
- EnergySource
- EquivalentBranch
- DCGround
- GovCT1
- GovCT2
- GovGAST
- GovGAST1
- GovHydroDD
- GovHydroPID
- GovHydroR
- GovSteam0
- GovSteamFV2
- ExcNI
- UnderexcLimX2
range: Resistance
required: false
x:
name: x
description: "Reactance from terminal sequence 2 to terminal sequence 1. Used\
\ for steady state power flow. This attribute is optional and represents an\
\ unbalanced network such as off-nominal phase shifter. If only EquivalentBranch.x\
\ is given, then EquivalentBranch.x21 is assumed equal to EquivalentBranch.x.\r\
\nUsage rule: EquivalentBranch is a result of network reduction prior to the\
\ data exchange."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:EquivalentBranch.x21
multivalued: false
domain_of:
- MutualCoupling
- TransformerMeshImpedance
- PowerTransformerEnd
- ACLineSegment
- SynchronousMachine
- EquivalentInjection
- PowerElectronicsConnection
- SeriesCompensator
- TransformerStarImpedance
- TapChangerTablePoint
- PerLengthSequenceImpedance
- PhaseImpedanceData
- GroundingImpedance
- EnergySource
- EquivalentBranch
- GovGAST2
range: Reactance
required: false
zero_r:
name: zero_r
description: "Zero sequence series resistance from terminal sequence 2 to terminal\
\ sequence 1. Used for short circuit data exchange according to IEC 60909.\r\
\nUsage : EquivalentBranch is a result of network reduction prior to the data\
\ exchange."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:EquivalentBranch.zeroR21
multivalued: false
domain_of:
- EquivalentBranch
range: Resistance
required: false
zero_x:
name: zero_x
description: "Zero sequence series reactance from terminal sequence 2 to terminal\
\ sequence 1. Used for short circuit data exchange according to IEC 60909.\r\
\nUsage : EquivalentBranch is a result of network reduction prior to the data\
\ exchange."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:EquivalentBranch.zeroX21
multivalued: false
domain_of:
- EquivalentBranch
range: Reactance
required: false
class_uri: cim:EquivalentBranch
Induced
name: EquivalentBranch
description: The class represents equivalent branches. In cases where a transformer
phase shift is modelled and the EquivalentBranch is spanning the same nodes, the
impedance quantities for the EquivalentBranch shall consider the needed phase shift.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
is_a: EquivalentEquipment
attributes:
negative_r:
name: negative_r
description: "Negative sequence series resistance from terminal sequence 2 to\
\ terminal sequence 1. Used for short circuit data exchange according to IEC\
\ 60909.\r\nEquivalentBranch is a result of network reduction prior to the data\
\ exchange."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:EquivalentBranch.negativeR21
multivalued: false
alias: negative_r
owner: EquivalentBranch
domain_of:
- EquivalentBranch
range: Resistance
required: false
negative_x:
name: negative_x
description: "Negative sequence series reactance from terminal sequence 2 to terminal\
\ sequence 1. Used for short circuit data exchange according to IEC 60909.\r\
\nUsage: EquivalentBranch is a result of network reduction prior to the data\
\ exchange."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:EquivalentBranch.negativeX21
multivalued: false
alias: negative_x
owner: EquivalentBranch
domain_of:
- EquivalentBranch
range: Reactance
required: false
positive_r:
name: positive_r
description: "Positive sequence series resistance from terminal sequence 2 to\
\ terminal sequence 1. Used for short circuit data exchange according to IEC\
\ 60909.\r\nEquivalentBranch is a result of network reduction prior to the data\
\ exchange."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:EquivalentBranch.positiveR21
multivalued: false
alias: positive_r
owner: EquivalentBranch
domain_of:
- EquivalentBranch
range: Resistance
required: false
positive_x:
name: positive_x
description: "Positive sequence series reactance from terminal sequence 2 to terminal\
\ sequence 1. Used for short circuit data exchange according to IEC 60909.\r\
\nUsage : EquivalentBranch is a result of network reduction prior to the data\
\ exchange."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:EquivalentBranch.positiveX21
multivalued: false
alias: positive_x
owner: EquivalentBranch
domain_of:
- EquivalentBranch
range: Reactance
required: false
r:
name: r
description: "Resistance from terminal sequence 2 to terminal sequence 1 .Used\
\ for steady state power flow. This attribute is optional and represent unbalanced\
\ network such as off-nominal phase shifter. If only EquivalentBranch.r is given,\
\ then EquivalentBranch.r21 is assumed equal to EquivalentBranch.r.\r\nUsage\
\ rule : EquivalentBranch is a result of network reduction prior to the data\
\ exchange."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:EquivalentBranch.r21
multivalued: false
alias: r
owner: EquivalentBranch
domain_of:
- MutualCoupling
- TransformerMeshImpedance
- TransformerEndInfo
- PowerTransformerEnd
- ACLineSegment
- SynchronousMachine
- EquivalentInjection
- PowerElectronicsConnection
- SeriesCompensator
- TransformerStarImpedance
- TapChangerTablePoint
- PerLengthSequenceImpedance
- PhaseImpedanceData
- EarthFaultCompensator
- EnergySource
- EquivalentBranch
- DCGround
- GovCT1
- GovCT2
- GovGAST
- GovGAST1
- GovHydroDD
- GovHydroPID
- GovHydroR
- GovSteam0
- GovSteamFV2
- ExcNI
- UnderexcLimX2
range: Resistance
required: false
x:
name: x
description: "Reactance from terminal sequence 2 to terminal sequence 1. Used\
\ for steady state power flow. This attribute is optional and represents an\
\ unbalanced network such as off-nominal phase shifter. If only EquivalentBranch.x\
\ is given, then EquivalentBranch.x21 is assumed equal to EquivalentBranch.x.\r\
\nUsage rule: EquivalentBranch is a result of network reduction prior to the\
\ data exchange."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:EquivalentBranch.x21
multivalued: false
alias: x
owner: EquivalentBranch
domain_of:
- MutualCoupling
- TransformerMeshImpedance
- PowerTransformerEnd
- ACLineSegment
- SynchronousMachine
- EquivalentInjection
- PowerElectronicsConnection
- SeriesCompensator
- TransformerStarImpedance
- TapChangerTablePoint
- PerLengthSequenceImpedance
- PhaseImpedanceData
- GroundingImpedance
- EnergySource
- EquivalentBranch
- GovGAST2
range: Reactance
required: false
zero_r:
name: zero_r
description: "Zero sequence series resistance from terminal sequence 2 to terminal\
\ sequence 1. Used for short circuit data exchange according to IEC 60909.\r\
\nUsage : EquivalentBranch is a result of network reduction prior to the data\
\ exchange."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:EquivalentBranch.zeroR21
multivalued: false
alias: zero_r
owner: EquivalentBranch
domain_of:
- EquivalentBranch
range: Resistance
required: false
zero_x:
name: zero_x
description: "Zero sequence series reactance from terminal sequence 2 to terminal\
\ sequence 1. Used for short circuit data exchange according to IEC 60909.\r\
\nUsage : EquivalentBranch is a result of network reduction prior to the data\
\ exchange."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:EquivalentBranch.zeroX21
multivalued: false
alias: zero_x
owner: EquivalentBranch
domain_of:
- EquivalentBranch
range: Reactance
required: false
equivalent_network:
name: equivalent_network
description: The equivalent where the reduced model belongs.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:EquivalentEquipment.EquivalentNetwork
multivalued: false
alias: equivalent_network
owner: EquivalentBranch
domain_of:
- EquivalentEquipment
range: EquivalentNetwork
required: false
protective_action_adjustment:
name: protective_action_adjustment
description: 'The operating condition to the Conducting Equipment is changed when
protective action adjustment is activated. For ShuntCompensator or other conducting
equipment that operates on discrete values (integer), the values given in float
will be rounded. '
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ConductingEquipment.ProtectiveActionAdjustment
multivalued: true
alias: protective_action_adjustment
owner: EquivalentBranch
domain_of:
- Measurement
- ConductingEquipment
- DCConductingEquipment
range: ProtectiveActionAdjustment
required: false
sv_status:
name: sv_status
description: The status state variable associated with this conducting equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ConductingEquipment.SvStatus
multivalued: true
alias: sv_status
owner: EquivalentBranch
domain_of:
- ConductingEquipment
range: SvStatus
required: false
protection_equipments:
name: protection_equipments
description: 'Protection equipment used to protect specific conducting equipment. '
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ConductingEquipment.ProtectionEquipments
multivalued: true
alias: protection_equipments
owner: EquivalentBranch
domain_of:
- ConductingEquipment
range: ProtectionEquipment
required: false
base_voltage:
name: base_voltage
description: Base voltage of this conducting equipment. Use only when there is
no voltage level container used and only one base voltage applies. For example,
not used for transformers.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ConductingEquipment.BaseVoltage
multivalued: false
alias: base_voltage
owner: EquivalentBranch
domain_of:
- TopologicalNode
- TransformerEnd
- ConductingEquipment
- VoltageLevel
- AssetDeployment
range: BaseVoltage
required: false
terminals:
name: terminals
description: Conducting equipment have terminals that may be connected to other
conducting equipment terminals via connectivity nodes or topological nodes.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ConductingEquipment.Terminals
multivalued: true
alias: terminals
owner: EquivalentBranch
domain_of:
- ConnectivityNode
- ConductingEquipment
range: Terminal
required: false
jumping_action:
name: jumping_action
description: Jumper action involving jumping operation on this conducting equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ConductingEquipment.JumpingAction
multivalued: false
alias: jumping_action
owner: EquivalentBranch
domain_of:
- ConductingEquipment
range: JumperAction
required: false
grounding_action:
name: grounding_action
description: Action involving grounding operation on this conducting equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ConductingEquipment.GroundingAction
multivalued: false
alias: grounding_action
owner: EquivalentBranch
domain_of:
- ConductingEquipment
range: GroundAction
required: false
outage:
name: outage
description: The outage that is isolated by the outage isolation equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ConductingEquipment.Outage
multivalued: false
alias: outage
owner: EquivalentBranch
domain_of:
- Incident
- SwitchingPlan
- UsagePoint
- ConductingEquipment
- Crew
- EstimatedRestorationTime
- OutageArea
- Fault
range: Outage
required: false
aggregate:
name: aggregate
description: "The aggregate flag provides an alternative way of representing an\
\ aggregated (equivalent) element. It is applicable in cases when the dedicated\
\ classes for equivalent equipment do not have all of the attributes necessary\
\ to represent the required level of detail. In case the flag is set to “true”\
\ the single instance of equipment represents multiple pieces of equipment that\
\ have been modelled together as an aggregate equivalent obtained by a network\
\ reduction procedure. Examples would be power transformers or synchronous machines\
\ operating in parallel modelled as a single aggregate power transformer or\
\ aggregate synchronous machine. \r\nThe attribute is not used for EquivalentBranch,\
\ EquivalentShunt and EquivalentInjection."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.aggregate
multivalued: false
alias: aggregate
owner: EquivalentBranch
domain_of:
- Equipment
- ReadingType
range: boolean
required: false
in_service:
name: in_service
description: Specifies the availability of the equipment. True means the equipment
is available for topology processing, which determines if the equipment is energized
or not. False means that the equipment is treated by network applications as
if it is not in the model.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.inService
multivalued: false
alias: in_service
owner: EquivalentBranch
domain_of:
- Equipment
- SvStatus
- ProtectiveActionEquipment
range: boolean
required: false
network_analysis_enabled:
name: network_analysis_enabled
description: The equipment is enabled to participate in network analysis. If
unspecified, the value is assumed to be true.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.networkAnalysisEnabled
multivalued: false
alias: network_analysis_enabled
owner: EquivalentBranch
domain_of:
- Equipment
range: boolean
required: false
normally_in_service:
name: normally_in_service
description: Specifies the availability of the equipment under normal operating
conditions. True means the equipment is available for topology processing, which
determines if the equipment is energized or not. False means that the equipment
is treated by network applications as if it is not in the model.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.normallyInService
multivalued: false
alias: normally_in_service
owner: EquivalentBranch
domain_of:
- Equipment
range: boolean
required: false
weather_station:
name: weather_station
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.WeatherStation
multivalued: true
alias: weather_station
owner: EquivalentBranch
domain_of:
- Equipment
range: WeatherStation
required: false
operational_limit_set:
name: operational_limit_set
description: The operational limit sets associated with this equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:Equipment.OperationalLimitSet
multivalued: true
alias: operational_limit_set
owner: EquivalentBranch
domain_of:
- ACDCTerminal
- OperationalLimit
- Equipment
range: OperationalLimitSet
required: false
contingency_equipment:
name: contingency_equipment
description: The contingency equipments in which this equipment participates.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.ContingencyEquipment
multivalued: true
alias: contingency_equipment
owner: EquivalentBranch
domain_of:
- Equipment
range: ContingencyEquipment
required: false
equipment_container:
name: equipment_container
description: Container of this equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.EquipmentContainer
multivalued: false
alias: equipment_container
owner: EquivalentBranch
domain_of:
- Equipment
range: EquipmentContainer
required: false
faults:
name: faults
description: All faults on this equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.Faults
multivalued: true
alias: faults
owner: EquivalentBranch
domain_of:
- Equipment
- Outage
- FaultCauseType
range: Fault
required: false
limit_dependency_model:
name: limit_dependency_model
description: Limit dependencymodels organized under this equipment as a means
for organizing the model in a tree view.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:Equipment.LimitDependencyModel
multivalued: true
alias: limit_dependency_model
owner: EquivalentBranch
domain_of:
- OperationalLimit
- Equipment
range: LimitDependency
required: false
eqiupment_limit_series_component:
name: eqiupment_limit_series_component
description: Equipment limit series calculation component to which this equipment
contributes.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.EqiupmentLimitSeriesComponent
multivalued: true
alias: eqiupment_limit_series_component
owner: EquivalentBranch
domain_of:
- Equipment
range: EquipmentLimitSeriesComponent
required: false
protective_action_equipment:
name: protective_action_equipment
description: Protective action is controlling equipment. This can be direct signals
from the control center, or emulation of action done by protection equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.ProtectiveActionEquipment
multivalued: true
alias: protective_action_equipment
owner: EquivalentBranch
domain_of:
- Equipment
range: ProtectiveActionEquipment
required: false
pin_equipment:
name: pin_equipment
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.PinEquipment
multivalued: true
alias: pin_equipment
owner: EquivalentBranch
domain_of:
- Equipment
range: PinEquipment
required: false
equipment_unavailability_schedule:
name: equipment_unavailability_schedule
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.EquipmentUnavailabilitySchedule
multivalued: true
alias: equipment_unavailability_schedule
owner: EquivalentBranch
domain_of:
- Equipment
- UnavailabilitySwitchAction
- UnavailablitySchedule
range: EquipmentUnavailabilitySchedule
required: false
additional_equipment_container:
name: additional_equipment_container
description: Additional equipment container beyond the primary equipment container. The
equipment is contained in another equipment container, but also grouped with
this equipment container.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.AdditionalEquipmentContainer
multivalued: true
alias: additional_equipment_container
owner: EquivalentBranch
domain_of:
- Equipment
range: EquipmentContainer
required: false
usage_points:
name: usage_points
description: All usage points connected to the electrical grid through this equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.UsagePoints
multivalued: true
alias: usage_points
owner: EquivalentBranch
domain_of:
- Equipment
- CustomerAgreement
- ServiceCategory
- PricingStructure
- EndDeviceControl
- UsagePointGroup
- ServiceLocation
- MetrologyRequirement
- ServiceSupplier
- UsagePointLocation
range: UsagePoint
required: false
outages:
name: outages
description: All outages in which this equipment is involved.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.Outages
multivalued: true
alias: outages
owner: EquivalentBranch
domain_of:
- Equipment
range: Outage
required: false
operational_restrictions:
name: operational_restrictions
description: All operational restrictions for this equipment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:Equipment.OperationalRestrictions
multivalued: true
alias: operational_restrictions
owner: EquivalentBranch
domain_of:
- Equipment
- ProductAssetModel
range: OperationalRestriction
required: false
controls:
name: controls
description: The controller outputs used to actually govern a regulating device,
e.g. the magnetization of a synchronous machine or capacitor bank breaker actuator.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.Controls
multivalued: true
alias: controls
owner: EquivalentBranch
domain_of:
- PowerSystemResource
- HostControlArea
range: Control
required: false
measurements:
name: measurements
description: The measurements associated with this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.Measurements
multivalued: true
alias: measurements
owner: EquivalentBranch
domain_of:
- PowerSystemResource
- ACDCTerminal
- Asset
- Location
- Procedure
- AnalogLimitSet
- AccumulatorLimitSet
range: Measurement
required: false
psrtype:
name: psrtype
description: Custom classification for this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.PSRType
multivalued: false
alias: psrtype
owner: EquivalentBranch
domain_of:
- PowerSystemResource
range: PSRType
required: false
configuration_event:
name: configuration_event
description: All configuration events created for this Power System resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.ConfigurationEvent
multivalued: true
alias: configuration_event
owner: EquivalentBranch
domain_of:
- PowerSystemResource
- FaultCauseType
range: ConfigurationEvent
required: false
reporting_group:
name: reporting_group
description: Reporting groups to which this power system resource belongs.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.ReportingGroup
multivalued: true
alias: reporting_group
owner: EquivalentBranch
domain_of:
- PowerSystemResource
- BusNameMarker
- TopologicalNode
- ReportingSuperGroup
range: ReportingGroup
required: false
operating_share:
name: operating_share
description: The operating shares of this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.OperatingShare
multivalued: true
alias: operating_share
owner: EquivalentBranch
domain_of:
- PowerSystemResource
- OperatingParticipant
range: OperatingShare
required: false
asset_datasheet:
name: asset_datasheet
description: Datasheet information for this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.AssetDatasheet
multivalued: false
alias: asset_datasheet
owner: EquivalentBranch
domain_of:
- PowerSystemResource
range: AssetInfo
required: false
verification_action:
name: verification_action
description: The verification action that is performed on the power system resource
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.VerificationAction
multivalued: true
alias: verification_action
owner: EquivalentBranch
domain_of:
- PowerSystemResource
range: VerificationAction
required: false
clearances:
name: clearances
description: All clearances applicable to this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.Clearances
multivalued: true
alias: clearances
owner: EquivalentBranch
domain_of:
- PowerSystemResource
range: ClearanceDocument
required: false
generic_action:
name: generic_action
description: The generic action that is performed on the power system resource
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.GenericAction
multivalued: true
alias: generic_action
owner: EquivalentBranch
domain_of:
- PowerSystemResource
range: GenericAction
required: false
psrevents:
name: psrevents
description: All events associated with this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.PSREvents
multivalued: true
alias: psrevents
owner: EquivalentBranch
domain_of:
- PowerSystemResource
range: PSREvent
required: false
assets:
name: assets
description: All assets represented by this power system resource. For example,
multiple conductor assets are electrically modelled as a single AC line segment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.Assets
multivalued: true
alias: assets
owner: EquivalentBranch
domain_of:
- PowerSystemResource
- AssetInfo
- Location
- WorkTask
- ErpRecDelvLineItem
- AssetContainer
- ActivityRecord
- Procedure
- ReliabilityInfo
- AssetPropertyCurve
- AssetOrganisationRole
- ScheduledEvent
range: Asset
required: false
location:
name: location
description: Location of this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.Location
multivalued: false
alias: location
owner: EquivalentBranch
domain_of:
- PowerSystemResource
- Asset
- Incident
- SwitchingOrder
- TroubleOrder
- Crew
- Fault
- PointOfSale
- TroubleTicket
- OutageOrder
- EnvironmentalMonitoringStation
- EnvironmentalLocationType
- PositionPoint
- FailureEvent
range: Location
required: false
operational_tags:
name: operational_tags
description: All operational tags placed on this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.OperationalTags
multivalued: true
alias: operational_tags
owner: EquivalentBranch
domain_of:
- PowerSystemResource
- Asset
range: OperationalTag
required: false
alias_name:
name: alias_name
description: "The aliasName is free text human readable name of the object alternative\
\ to IdentifiedObject.name. It may be non unique and may not correlate to a\
\ naming hierarchy.\r\nThe attribute aliasName is retained because of backwards\
\ compatibility between CIM relases. It is however recommended to replace aliasName\
\ with the Name class as aliasName is planned for retirement at a future time.\r\
\n\r\n"
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.aliasName
multivalued: false
alias: alias_name
owner: EquivalentBranch
domain_of:
- IdentifiedObject
range: string
required: false
description:
name: description
description: The description is a free human readable text describing or naming
the object. It may be non unique and may not correlate to a naming hierarchy.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.description
multivalued: false
alias: description
owner: EquivalentBranch
domain_of:
- IdentifiedObject
- NameType
- NameTypeAuthority
- DataSet
- SwitchingStepGroup
- AreaReserveSpec
range: string
required: false
m_rid:
name: m_rid
description: "Master resource identifier issued by a model authority. The mRID\
\ is unique within an exchange context. Global uniqueness is easily achieved\
\ by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is\
\ strongly recommended.\r\nFor CIMXML data files in RDF syntax conforming to\
\ IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify\
\ CIM object elements."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.mRID
multivalued: false
alias: m_rid
owner: EquivalentBranch
domain_of:
- IdentifiedObject
- DataSet
range: string
required: false
diagram_objects:
name: diagram_objects
description: The diagram objects that are associated with the domain object.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.DiagramObjects
multivalued: true
alias: diagram_objects
owner: EquivalentBranch
domain_of:
- IdentifiedObject
range: DiagramObject
required: false
instance_set:
name: instance_set
description: Dataset containing the data objects.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.InstanceSet
multivalued: false
alias: instance_set
owner: EquivalentBranch
domain_of:
- IdentifiedObject
range: InstanceSet
required: true
names:
name: names
description: All names of this identified object.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.Names
multivalued: true
alias: names
owner: EquivalentBranch
domain_of:
- IdentifiedObject
- NameType
range: Name
required: false
properties_cimdata_object:
name: properties_cimdata_object
description: The single CIM data object in the appropriate dataset context.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.PropertiesCIMDataObject
multivalued: false
alias: properties_cimdata_object
owner: EquivalentBranch
domain_of:
- IdentifiedObject
range: ChangeSetMember
required: false
targeting_cimdata_object:
name: targeting_cimdata_object
description: Data objects registered.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.TargetingCIMDataObject
multivalued: true
alias: targeting_cimdata_object
owner: EquivalentBranch
domain_of:
- IdentifiedObject
range: ChangeSetMember
required: false
class_uri: cim:EquivalentBranch