Skip to content

Class: ControlArea

_A control area is a grouping of generating units and/or loads and a cutset of tie lines (as terminals) which may be used for a variety of purposes including automatic generation control, power flow solution area interchange control specification, and input to load forecasting. All generation and load within the area defined by the terminals on the border are considered in the area interchange control. Note that any number of overlapping control area specifications can be superimposed on the physical model. The following general principles apply to ControlArea: _

_1. The control area orientation for net interchange is positive for an import, negative for an export. _

_2. The control area net interchange is determined by summing flows in Terminals. The Terminals are identified by creating a set of TieFlow objects associated with a ControlArea object. Each TieFlow object identifies one Terminal. _

_3. In a single network model, a tie between two control areas must be modelled in both control area specifications, such that the two representations of the tie flow sum to zero. _

4. The normal orientation of Terminal flow is positive for flow into the conducting equipment that owns the Terminal. (i.e. flow from a bus into a device is positive.) However, the orientation of each flow in the control area specification must align with the control area convention, i.e. import is positive. If the orientation of the Terminal flow referenced by a TieFlow is positive into the control area, then this is confirmed by setting TieFlow.positiveFlowIn flag TRUE. If not, the orientation must be reversed by setting the TieFlow.positiveFlowIn flag FALSE.

URI: cim:ControlArea

 classDiagram
    class ControlArea
      PowerSystemResource <|-- ControlArea


      ControlArea <|-- MktControlArea


      ControlArea : alias_name

      ControlArea : asset_datasheet

          ControlArea --> AssetInfo : asset_datasheet

      ControlArea : assets

          ControlArea --> Asset : assets

      ControlArea : clearances

          ControlArea --> ClearanceDocument : clearances

      ControlArea : configuration_event

          ControlArea --> ConfigurationEvent : configuration_event

      ControlArea : control_area_generating_unit

          ControlArea --> ControlAreaGeneratingUnit : control_area_generating_unit

      ControlArea : controls

          ControlArea --> Control : controls

      ControlArea : description

      ControlArea : diagram_objects

          ControlArea --> DiagramObject : diagram_objects

      ControlArea : energy_area

          ControlArea --> EnergyArea : energy_area

      ControlArea : energy_group

          ControlArea --> EnergyGroup : energy_group

      ControlArea : generic_action

          ControlArea --> GenericAction : generic_action

      ControlArea : instance_set

          ControlArea --> InstanceSet : instance_set

      ControlArea : location

          ControlArea --> Location : location

      ControlArea : m_rid

      ControlArea : measurements

          ControlArea --> Measurement : measurements

      ControlArea : names

          ControlArea --> Name : names

      ControlArea : net_interchange

          ControlArea --> ActivePower : net_interchange

      ControlArea : operating_share

          ControlArea --> OperatingShare : operating_share

      ControlArea : operational_tags

          ControlArea --> OperationalTag : operational_tags

      ControlArea : p_tolerance

          ControlArea --> ActivePower : p_tolerance

      ControlArea : properties_cimdata_object

          ControlArea --> ChangeSetMember : properties_cimdata_object

      ControlArea : psrevents

          ControlArea --> PSREvent : psrevents

      ControlArea : psrtype

          ControlArea --> PSRType : psrtype

      ControlArea : reporting_group

          ControlArea --> ReportingGroup : reporting_group

      ControlArea : targeting_cimdata_object

          ControlArea --> ChangeSetMember : targeting_cimdata_object

      ControlArea : tie_flow

          ControlArea --> TieFlow : tie_flow

      ControlArea : type

          ControlArea --> ControlAreaTypeKind : type

      ControlArea : verification_action

          ControlArea --> VerificationAction : verification_action

Inheritance

Slots

Name Cardinality and Range Description Inheritance
net_interchange 0..1
ActivePower
The specified positive net interchange into the control area, i direct
p_tolerance 0..1
ActivePower
Active power net interchange tolerance direct
type 0..1
ControlAreaTypeKind
The primary type of control area definition used to determine if this is used... direct
energy_area 0..1
EnergyArea
The energy area that is forecast from this control area specification direct
control_area_generating_unit 0..*
ControlAreaGeneratingUnit
The generating unit specifications for the control area direct
tie_flow 0..*
TieFlow
The tie flows associated with the control area direct
energy_group 0..*
EnergyGroup
direct
controls 0..*
Control
The controller outputs used to actually govern a regulating device, e PowerSystemResource
measurements 0..*
Measurement
The measurements associated with this power system resource PowerSystemResource
psrtype 0..1
PSRType
Custom classification for this power system resource PowerSystemResource
configuration_event 0..*
ConfigurationEvent
All configuration events created for this Power System resource PowerSystemResource
reporting_group 0..*
ReportingGroup
Reporting groups to which this power system resource belongs PowerSystemResource
operating_share 0..*
OperatingShare
The operating shares of this power system resource PowerSystemResource
asset_datasheet 0..1
AssetInfo
Datasheet information for this power system resource PowerSystemResource
verification_action 0..*
VerificationAction
The verification action that is performed on the power system resource PowerSystemResource
clearances 0..*
ClearanceDocument
All clearances applicable to this power system resource PowerSystemResource
generic_action 0..*
GenericAction
The generic action that is performed on the power system resource PowerSystemResource
psrevents 0..*
PSREvent
All events associated with this power system resource PowerSystemResource
assets 0..*
Asset
All assets represented by this power system resource PowerSystemResource
location 0..1
Location
Location of this power system resource PowerSystemResource
operational_tags 0..*
OperationalTag
All operational tags placed on this power system resource PowerSystemResource
alias_name 0..1
String
The aliasName is free text human readable name of the object alternative to I... IdentifiedObject
description 0..1
String
The description is a free human readable text describing or naming the object IdentifiedObject
m_rid 0..1
String
Master resource identifier issued by a model authority IdentifiedObject
diagram_objects 0..*
DiagramObject
The diagram objects that are associated with the domain object IdentifiedObject
instance_set 1..1
InstanceSet
Dataset containing the data objects IdentifiedObject
names 0..*
Name
All names of this identified object IdentifiedObject
properties_cimdata_object 0..1
ChangeSetMember
The single CIM data object in the appropriate dataset context IdentifiedObject
targeting_cimdata_object 0..*
ChangeSetMember
Data objects registered IdentifiedObject

Usages

used by used in type used
ControlAreaGeneratingUnit control_area range ControlArea
TieFlow control_area range ControlArea
EnergyGroup control_area range ControlArea
EnergyArea control_area range ControlArea
SubLoadArea control_area range ControlArea
LoadArea control_area range ControlArea

Identifier and Mapping Information

Schema Source

  • from schema: https://cim.ucaiug.io/ns#TC57CIM

Mappings

Mapping Type Mapped Value
self cim:ControlArea
native cim:ControlArea

LinkML Source

Direct

name: ControlArea
description: "A control area is a grouping of generating units and/or loads and a\
  \ cutset of tie lines (as terminals) which may be used for a variety of purposes\
  \ including automatic generation control, power flow solution area interchange control\
  \ specification, and input to load forecasting. All generation and load within the\
  \ area defined by the terminals on the border are considered in the area interchange\
  \ control. Note that any number of overlapping control area specifications can be\
  \ superimposed on the physical model. The following general principles apply to\
  \ ControlArea:\r\n1.  The control area orientation for net interchange is positive\
  \ for an import, negative for an export.\r\n2.  The control area net interchange\
  \ is determined by summing flows in Terminals. The Terminals are identified by creating\
  \ a set of TieFlow objects associated with a ControlArea object. Each TieFlow object\
  \ identifies one Terminal.\r\n3.  In a single network model, a tie between two control\
  \ areas must be modelled in both control area specifications, such that the two\
  \ representations of the tie flow sum to zero.\r\n4.  The normal orientation of\
  \ Terminal flow is positive for flow into the conducting equipment that owns the\
  \ Terminal. (i.e. flow from a bus into a device is positive.) However, the orientation\
  \ of each flow in the control area specification must align with the control area\
  \ convention, i.e. import is positive. If the orientation of the Terminal flow referenced\
  \ by a TieFlow is positive into the control area, then this is confirmed by setting\
  \ TieFlow.positiveFlowIn flag TRUE. If not, the orientation must be reversed by\
  \ setting the TieFlow.positiveFlowIn flag FALSE."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
is_a: PowerSystemResource
attributes:
  net_interchange:
    name: net_interchange
    description: The specified positive net interchange into the control area, i.e.
      positive sign means flow into the area.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ControlArea.netInterchange
    multivalued: false
    domain_of:
    - ControlArea
    range: ActivePower
    required: false
  p_tolerance:
    name: p_tolerance
    description: Active power net interchange tolerance. The attribute shall be a
      positive value or zero.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ControlArea.pTolerance
    multivalued: false
    domain_of:
    - ControlArea
    range: ActivePower
    required: false
  type:
    name: type
    description: The primary type of control area definition used to determine if
      this is used for automatic generation control, for planning interchange control,
      or other purposes.   A control area specified with primary type of automatic
      generation control could still be forecast and used as an interchange area in
      power flow analysis.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ControlArea.type
    multivalued: false
    domain_of:
    - Asset
    - AcceptanceTest
    - Document
    - StreetDetail
    - Location
    - Priority
    - CatalogAssetType
    - Capability
    - Craft
    - OldPerson
    - Role
    - ActivityRecord
    - EndDeviceEventType
    - EndDeviceGroup
    - DemandResponseProgram
    - UsagePointGroup
    - EndDeviceControlType
    - Hazard
    - OldCrew
    - Route
    - ConstraintDuration
    - AceTariffType
    - ControlArea
    - SynchronousMachine
    - ChargeProfile
    - ChargeComponent
    - MarketRole
    - ResourceGroup
    - Quantity
    - ResourceCertification
    - Auction
    - ScheduledEvent
    - PotentialTransformer
    - BusinessRole
    range: ControlAreaTypeKind
    required: false
  energy_area:
    name: energy_area
    description: The energy area that is forecast from this control area specification.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ControlArea.EnergyArea
    multivalued: false
    domain_of:
    - ControlArea
    range: EnergyArea
    required: false
  control_area_generating_unit:
    name: control_area_generating_unit
    description: The generating unit specifications for the control area.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ControlArea.ControlAreaGeneratingUnit
    multivalued: true
    domain_of:
    - GeneratingUnit
    - AltGeneratingUnitMeas
    - ControlArea
    range: ControlAreaGeneratingUnit
    required: false
  tie_flow:
    name: tie_flow
    description: The tie flows associated with the control area.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ControlArea.TieFlow
    multivalued: true
    domain_of:
    - Terminal
    - AltTieMeas
    - ControlArea
    range: TieFlow
    required: false
  energy_group:
    name: energy_group
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ControlArea.EnergyGroup
    multivalued: true
    domain_of:
    - ControlArea
    - BlockDispatchInstruction
    - EnergyComponent
    - SvPowerFlow
    - EnergyTypeReference
    range: EnergyGroup
    required: false
class_uri: cim:ControlArea

Induced

name: ControlArea
description: "A control area is a grouping of generating units and/or loads and a\
  \ cutset of tie lines (as terminals) which may be used for a variety of purposes\
  \ including automatic generation control, power flow solution area interchange control\
  \ specification, and input to load forecasting. All generation and load within the\
  \ area defined by the terminals on the border are considered in the area interchange\
  \ control. Note that any number of overlapping control area specifications can be\
  \ superimposed on the physical model. The following general principles apply to\
  \ ControlArea:\r\n1.  The control area orientation for net interchange is positive\
  \ for an import, negative for an export.\r\n2.  The control area net interchange\
  \ is determined by summing flows in Terminals. The Terminals are identified by creating\
  \ a set of TieFlow objects associated with a ControlArea object. Each TieFlow object\
  \ identifies one Terminal.\r\n3.  In a single network model, a tie between two control\
  \ areas must be modelled in both control area specifications, such that the two\
  \ representations of the tie flow sum to zero.\r\n4.  The normal orientation of\
  \ Terminal flow is positive for flow into the conducting equipment that owns the\
  \ Terminal. (i.e. flow from a bus into a device is positive.) However, the orientation\
  \ of each flow in the control area specification must align with the control area\
  \ convention, i.e. import is positive. If the orientation of the Terminal flow referenced\
  \ by a TieFlow is positive into the control area, then this is confirmed by setting\
  \ TieFlow.positiveFlowIn flag TRUE. If not, the orientation must be reversed by\
  \ setting the TieFlow.positiveFlowIn flag FALSE."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
is_a: PowerSystemResource
attributes:
  net_interchange:
    name: net_interchange
    description: The specified positive net interchange into the control area, i.e.
      positive sign means flow into the area.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ControlArea.netInterchange
    multivalued: false
    alias: net_interchange
    owner: ControlArea
    domain_of:
    - ControlArea
    range: ActivePower
    required: false
  p_tolerance:
    name: p_tolerance
    description: Active power net interchange tolerance. The attribute shall be a
      positive value or zero.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ControlArea.pTolerance
    multivalued: false
    alias: p_tolerance
    owner: ControlArea
    domain_of:
    - ControlArea
    range: ActivePower
    required: false
  type:
    name: type
    description: The primary type of control area definition used to determine if
      this is used for automatic generation control, for planning interchange control,
      or other purposes.   A control area specified with primary type of automatic
      generation control could still be forecast and used as an interchange area in
      power flow analysis.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ControlArea.type
    multivalued: false
    alias: type
    owner: ControlArea
    domain_of:
    - Asset
    - AcceptanceTest
    - Document
    - StreetDetail
    - Location
    - Priority
    - CatalogAssetType
    - Capability
    - Craft
    - OldPerson
    - Role
    - ActivityRecord
    - EndDeviceEventType
    - EndDeviceGroup
    - DemandResponseProgram
    - UsagePointGroup
    - EndDeviceControlType
    - Hazard
    - OldCrew
    - Route
    - ConstraintDuration
    - AceTariffType
    - ControlArea
    - SynchronousMachine
    - ChargeProfile
    - ChargeComponent
    - MarketRole
    - ResourceGroup
    - Quantity
    - ResourceCertification
    - Auction
    - ScheduledEvent
    - PotentialTransformer
    - BusinessRole
    range: ControlAreaTypeKind
    required: false
  energy_area:
    name: energy_area
    description: The energy area that is forecast from this control area specification.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ControlArea.EnergyArea
    multivalued: false
    alias: energy_area
    owner: ControlArea
    domain_of:
    - ControlArea
    range: EnergyArea
    required: false
  control_area_generating_unit:
    name: control_area_generating_unit
    description: The generating unit specifications for the control area.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ControlArea.ControlAreaGeneratingUnit
    multivalued: true
    alias: control_area_generating_unit
    owner: ControlArea
    domain_of:
    - GeneratingUnit
    - AltGeneratingUnitMeas
    - ControlArea
    range: ControlAreaGeneratingUnit
    required: false
  tie_flow:
    name: tie_flow
    description: The tie flows associated with the control area.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ControlArea.TieFlow
    multivalued: true
    alias: tie_flow
    owner: ControlArea
    domain_of:
    - Terminal
    - AltTieMeas
    - ControlArea
    range: TieFlow
    required: false
  energy_group:
    name: energy_group
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ControlArea.EnergyGroup
    multivalued: true
    alias: energy_group
    owner: ControlArea
    domain_of:
    - ControlArea
    - BlockDispatchInstruction
    - EnergyComponent
    - SvPowerFlow
    - EnergyTypeReference
    range: EnergyGroup
    required: false
  controls:
    name: controls
    description: The controller outputs used to actually govern a regulating device,
      e.g. the magnetization of a synchronous machine or capacitor bank breaker actuator.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.Controls
    multivalued: true
    alias: controls
    owner: ControlArea
    domain_of:
    - PowerSystemResource
    - HostControlArea
    range: Control
    required: false
  measurements:
    name: measurements
    description: The measurements associated with this power system resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.Measurements
    multivalued: true
    alias: measurements
    owner: ControlArea
    domain_of:
    - PowerSystemResource
    - ACDCTerminal
    - Asset
    - Location
    - Procedure
    - AnalogLimitSet
    - AccumulatorLimitSet
    range: Measurement
    required: false
  psrtype:
    name: psrtype
    description: Custom classification for this power system resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.PSRType
    multivalued: false
    alias: psrtype
    owner: ControlArea
    domain_of:
    - PowerSystemResource
    range: PSRType
    required: false
  configuration_event:
    name: configuration_event
    description: All configuration events created for this Power System resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.ConfigurationEvent
    multivalued: true
    alias: configuration_event
    owner: ControlArea
    domain_of:
    - PowerSystemResource
    - FaultCauseType
    range: ConfigurationEvent
    required: false
  reporting_group:
    name: reporting_group
    description: Reporting groups to which this power system resource belongs.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.ReportingGroup
    multivalued: true
    alias: reporting_group
    owner: ControlArea
    domain_of:
    - PowerSystemResource
    - BusNameMarker
    - TopologicalNode
    - ReportingSuperGroup
    range: ReportingGroup
    required: false
  operating_share:
    name: operating_share
    description: The operating shares of this power system resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.OperatingShare
    multivalued: true
    alias: operating_share
    owner: ControlArea
    domain_of:
    - PowerSystemResource
    - OperatingParticipant
    range: OperatingShare
    required: false
  asset_datasheet:
    name: asset_datasheet
    description: Datasheet information for this power system resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.AssetDatasheet
    multivalued: false
    alias: asset_datasheet
    owner: ControlArea
    domain_of:
    - PowerSystemResource
    range: AssetInfo
    required: false
  verification_action:
    name: verification_action
    description: The verification action that is performed on the power system resource
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.VerificationAction
    multivalued: true
    alias: verification_action
    owner: ControlArea
    domain_of:
    - PowerSystemResource
    range: VerificationAction
    required: false
  clearances:
    name: clearances
    description: All clearances applicable to this power system resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.Clearances
    multivalued: true
    alias: clearances
    owner: ControlArea
    domain_of:
    - PowerSystemResource
    range: ClearanceDocument
    required: false
  generic_action:
    name: generic_action
    description: The generic action that is performed on the power system resource
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.GenericAction
    multivalued: true
    alias: generic_action
    owner: ControlArea
    domain_of:
    - PowerSystemResource
    range: GenericAction
    required: false
  psrevents:
    name: psrevents
    description: All events associated with this power system resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.PSREvents
    multivalued: true
    alias: psrevents
    owner: ControlArea
    domain_of:
    - PowerSystemResource
    range: PSREvent
    required: false
  assets:
    name: assets
    description: All assets represented by this power system resource. For example,
      multiple conductor assets are electrically modelled as a single AC line segment.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.Assets
    multivalued: true
    alias: assets
    owner: ControlArea
    domain_of:
    - PowerSystemResource
    - AssetInfo
    - Location
    - WorkTask
    - ErpRecDelvLineItem
    - AssetContainer
    - ActivityRecord
    - Procedure
    - ReliabilityInfo
    - AssetPropertyCurve
    - AssetOrganisationRole
    - ScheduledEvent
    range: Asset
    required: false
  location:
    name: location
    description: Location of this power system resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.Location
    multivalued: false
    alias: location
    owner: ControlArea
    domain_of:
    - PowerSystemResource
    - Asset
    - Incident
    - SwitchingOrder
    - TroubleOrder
    - Crew
    - Fault
    - PointOfSale
    - TroubleTicket
    - OutageOrder
    - EnvironmentalMonitoringStation
    - EnvironmentalLocationType
    - PositionPoint
    - FailureEvent
    range: Location
    required: false
  operational_tags:
    name: operational_tags
    description: All operational tags placed on this power system resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.OperationalTags
    multivalued: true
    alias: operational_tags
    owner: ControlArea
    domain_of:
    - PowerSystemResource
    - Asset
    range: OperationalTag
    required: false
  alias_name:
    name: alias_name
    description: "The aliasName is free text human readable name of the object alternative\
      \ to IdentifiedObject.name. It may be non unique and may not correlate to a\
      \ naming hierarchy.\r\nThe attribute aliasName is retained because of backwards\
      \ compatibility between CIM relases. It is however recommended to replace aliasName\
      \ with the Name class as aliasName is planned for retirement at a future time.\r\
      \n\r\n"
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:IdentifiedObject.aliasName
    multivalued: false
    alias: alias_name
    owner: ControlArea
    domain_of:
    - IdentifiedObject
    range: string
    required: false
  description:
    name: description
    description: The description is a free human readable text describing or naming
      the object. It may be non unique and may not correlate to a naming hierarchy.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:IdentifiedObject.description
    multivalued: false
    alias: description
    owner: ControlArea
    domain_of:
    - IdentifiedObject
    - NameType
    - NameTypeAuthority
    - DataSet
    - SwitchingStepGroup
    - AreaReserveSpec
    range: string
    required: false
  m_rid:
    name: m_rid
    description: "Master resource identifier issued by a model authority. The mRID\
      \ is unique within an exchange context. Global uniqueness is easily achieved\
      \ by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is\
      \ strongly recommended.\r\nFor CIMXML data files in RDF syntax conforming to\
      \ IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify\
      \ CIM object elements."
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:IdentifiedObject.mRID
    multivalued: false
    alias: m_rid
    owner: ControlArea
    domain_of:
    - IdentifiedObject
    - DataSet
    range: string
    required: false
  diagram_objects:
    name: diagram_objects
    description: The diagram objects that are associated with the domain object.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:IdentifiedObject.DiagramObjects
    multivalued: true
    alias: diagram_objects
    owner: ControlArea
    domain_of:
    - IdentifiedObject
    range: DiagramObject
    required: false
  instance_set:
    name: instance_set
    description: Dataset containing the data objects.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:IdentifiedObject.InstanceSet
    multivalued: false
    alias: instance_set
    owner: ControlArea
    domain_of:
    - IdentifiedObject
    range: InstanceSet
    required: true
  names:
    name: names
    description: All names of this identified object.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:IdentifiedObject.Names
    multivalued: true
    alias: names
    owner: ControlArea
    domain_of:
    - IdentifiedObject
    - NameType
    range: Name
    required: false
  properties_cimdata_object:
    name: properties_cimdata_object
    description: The single CIM data object in the appropriate dataset context.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:IdentifiedObject.PropertiesCIMDataObject
    multivalued: false
    alias: properties_cimdata_object
    owner: ControlArea
    domain_of:
    - IdentifiedObject
    range: ChangeSetMember
    required: false
  targeting_cimdata_object:
    name: targeting_cimdata_object
    description: Data objects registered.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:IdentifiedObject.TargetingCIMDataObject
    multivalued: true
    alias: targeting_cimdata_object
    owner: ControlArea
    domain_of:
    - IdentifiedObject
    range: ChangeSetMember
    required: false
class_uri: cim:ControlArea