Class: ControlArea
_A control area is a grouping of generating units and/or loads and a cutset of tie lines (as terminals) which may be used for a variety of purposes including automatic generation control, power flow solution area interchange control specification, and input to load forecasting. All generation and load within the area defined by the terminals on the border are considered in the area interchange control. Note that any number of overlapping control area specifications can be superimposed on the physical model. The following general principles apply to ControlArea: _
_1. The control area orientation for net interchange is positive for an import, negative for an export. _
_2. The control area net interchange is determined by summing flows in Terminals. The Terminals are identified by creating a set of TieFlow objects associated with a ControlArea object. Each TieFlow object identifies one Terminal. _
_3. In a single network model, a tie between two control areas must be modelled in both control area specifications, such that the two representations of the tie flow sum to zero. _
4. The normal orientation of Terminal flow is positive for flow into the conducting equipment that owns the Terminal. (i.e. flow from a bus into a device is positive.) However, the orientation of each flow in the control area specification must align with the control area convention, i.e. import is positive. If the orientation of the Terminal flow referenced by a TieFlow is positive into the control area, then this is confirmed by setting TieFlow.positiveFlowIn flag TRUE. If not, the orientation must be reversed by setting the TieFlow.positiveFlowIn flag FALSE.
URI: cim:ControlArea
classDiagram
class ControlArea
PowerSystemResource <|-- ControlArea
ControlArea <|-- MktControlArea
ControlArea : alias_name
ControlArea : asset_datasheet
ControlArea --> AssetInfo : asset_datasheet
ControlArea : assets
ControlArea --> Asset : assets
ControlArea : clearances
ControlArea --> ClearanceDocument : clearances
ControlArea : configuration_event
ControlArea --> ConfigurationEvent : configuration_event
ControlArea : control_area_generating_unit
ControlArea --> ControlAreaGeneratingUnit : control_area_generating_unit
ControlArea : controls
ControlArea --> Control : controls
ControlArea : description
ControlArea : diagram_objects
ControlArea --> DiagramObject : diagram_objects
ControlArea : energy_area
ControlArea --> EnergyArea : energy_area
ControlArea : energy_group
ControlArea --> EnergyGroup : energy_group
ControlArea : generic_action
ControlArea --> GenericAction : generic_action
ControlArea : instance_set
ControlArea --> InstanceSet : instance_set
ControlArea : location
ControlArea --> Location : location
ControlArea : m_rid
ControlArea : measurements
ControlArea --> Measurement : measurements
ControlArea : names
ControlArea --> Name : names
ControlArea : net_interchange
ControlArea --> ActivePower : net_interchange
ControlArea : operating_share
ControlArea --> OperatingShare : operating_share
ControlArea : operational_tags
ControlArea --> OperationalTag : operational_tags
ControlArea : p_tolerance
ControlArea --> ActivePower : p_tolerance
ControlArea : properties_cimdata_object
ControlArea --> ChangeSetMember : properties_cimdata_object
ControlArea : psrevents
ControlArea --> PSREvent : psrevents
ControlArea : psrtype
ControlArea --> PSRType : psrtype
ControlArea : reporting_group
ControlArea --> ReportingGroup : reporting_group
ControlArea : targeting_cimdata_object
ControlArea --> ChangeSetMember : targeting_cimdata_object
ControlArea : tie_flow
ControlArea --> TieFlow : tie_flow
ControlArea : type
ControlArea --> ControlAreaTypeKind : type
ControlArea : verification_action
ControlArea --> VerificationAction : verification_action
Inheritance
- IdentifiedObject
- PowerSystemResource
- ControlArea
- PowerSystemResource
Slots
| Name | Cardinality and Range | Description | Inheritance |
|---|---|---|---|
| net_interchange | 0..1 ActivePower |
The specified positive net interchange into the control area, i | direct |
| p_tolerance | 0..1 ActivePower |
Active power net interchange tolerance | direct |
| type | 0..1 ControlAreaTypeKind |
The primary type of control area definition used to determine if this is used... | direct |
| energy_area | 0..1 EnergyArea |
The energy area that is forecast from this control area specification | direct |
| control_area_generating_unit | 0..* ControlAreaGeneratingUnit |
The generating unit specifications for the control area | direct |
| tie_flow | 0..* TieFlow |
The tie flows associated with the control area | direct |
| energy_group | 0..* EnergyGroup |
direct | |
| controls | 0..* Control |
The controller outputs used to actually govern a regulating device, e | PowerSystemResource |
| measurements | 0..* Measurement |
The measurements associated with this power system resource | PowerSystemResource |
| psrtype | 0..1 PSRType |
Custom classification for this power system resource | PowerSystemResource |
| configuration_event | 0..* ConfigurationEvent |
All configuration events created for this Power System resource | PowerSystemResource |
| reporting_group | 0..* ReportingGroup |
Reporting groups to which this power system resource belongs | PowerSystemResource |
| operating_share | 0..* OperatingShare |
The operating shares of this power system resource | PowerSystemResource |
| asset_datasheet | 0..1 AssetInfo |
Datasheet information for this power system resource | PowerSystemResource |
| verification_action | 0..* VerificationAction |
The verification action that is performed on the power system resource | PowerSystemResource |
| clearances | 0..* ClearanceDocument |
All clearances applicable to this power system resource | PowerSystemResource |
| generic_action | 0..* GenericAction |
The generic action that is performed on the power system resource | PowerSystemResource |
| psrevents | 0..* PSREvent |
All events associated with this power system resource | PowerSystemResource |
| assets | 0..* Asset |
All assets represented by this power system resource | PowerSystemResource |
| location | 0..1 Location |
Location of this power system resource | PowerSystemResource |
| operational_tags | 0..* OperationalTag |
All operational tags placed on this power system resource | PowerSystemResource |
| alias_name | 0..1 String |
The aliasName is free text human readable name of the object alternative to I... | IdentifiedObject |
| description | 0..1 String |
The description is a free human readable text describing or naming the object | IdentifiedObject |
| m_rid | 0..1 String |
Master resource identifier issued by a model authority | IdentifiedObject |
| diagram_objects | 0..* DiagramObject |
The diagram objects that are associated with the domain object | IdentifiedObject |
| instance_set | 1..1 InstanceSet |
Dataset containing the data objects | IdentifiedObject |
| names | 0..* Name |
All names of this identified object | IdentifiedObject |
| properties_cimdata_object | 0..1 ChangeSetMember |
The single CIM data object in the appropriate dataset context | IdentifiedObject |
| targeting_cimdata_object | 0..* ChangeSetMember |
Data objects registered | IdentifiedObject |
Usages
| used by | used in | type | used |
|---|---|---|---|
| ControlAreaGeneratingUnit | control_area | range | ControlArea |
| TieFlow | control_area | range | ControlArea |
| EnergyGroup | control_area | range | ControlArea |
| EnergyArea | control_area | range | ControlArea |
| SubLoadArea | control_area | range | ControlArea |
| LoadArea | control_area | range | ControlArea |
Identifier and Mapping Information
Schema Source
- from schema: https://cim.ucaiug.io/ns#TC57CIM
Mappings
| Mapping Type | Mapped Value |
|---|---|
| self | cim:ControlArea |
| native | cim:ControlArea |
LinkML Source
Direct
name: ControlArea
description: "A control area is a grouping of generating units and/or loads and a\
\ cutset of tie lines (as terminals) which may be used for a variety of purposes\
\ including automatic generation control, power flow solution area interchange control\
\ specification, and input to load forecasting. All generation and load within the\
\ area defined by the terminals on the border are considered in the area interchange\
\ control. Note that any number of overlapping control area specifications can be\
\ superimposed on the physical model. The following general principles apply to\
\ ControlArea:\r\n1. The control area orientation for net interchange is positive\
\ for an import, negative for an export.\r\n2. The control area net interchange\
\ is determined by summing flows in Terminals. The Terminals are identified by creating\
\ a set of TieFlow objects associated with a ControlArea object. Each TieFlow object\
\ identifies one Terminal.\r\n3. In a single network model, a tie between two control\
\ areas must be modelled in both control area specifications, such that the two\
\ representations of the tie flow sum to zero.\r\n4. The normal orientation of\
\ Terminal flow is positive for flow into the conducting equipment that owns the\
\ Terminal. (i.e. flow from a bus into a device is positive.) However, the orientation\
\ of each flow in the control area specification must align with the control area\
\ convention, i.e. import is positive. If the orientation of the Terminal flow referenced\
\ by a TieFlow is positive into the control area, then this is confirmed by setting\
\ TieFlow.positiveFlowIn flag TRUE. If not, the orientation must be reversed by\
\ setting the TieFlow.positiveFlowIn flag FALSE."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
is_a: PowerSystemResource
attributes:
net_interchange:
name: net_interchange
description: The specified positive net interchange into the control area, i.e.
positive sign means flow into the area.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ControlArea.netInterchange
multivalued: false
domain_of:
- ControlArea
range: ActivePower
required: false
p_tolerance:
name: p_tolerance
description: Active power net interchange tolerance. The attribute shall be a
positive value or zero.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ControlArea.pTolerance
multivalued: false
domain_of:
- ControlArea
range: ActivePower
required: false
type:
name: type
description: The primary type of control area definition used to determine if
this is used for automatic generation control, for planning interchange control,
or other purposes. A control area specified with primary type of automatic
generation control could still be forecast and used as an interchange area in
power flow analysis.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ControlArea.type
multivalued: false
domain_of:
- Asset
- AcceptanceTest
- Document
- StreetDetail
- Location
- Priority
- CatalogAssetType
- Capability
- Craft
- OldPerson
- Role
- ActivityRecord
- EndDeviceEventType
- EndDeviceGroup
- DemandResponseProgram
- UsagePointGroup
- EndDeviceControlType
- Hazard
- OldCrew
- Route
- ConstraintDuration
- AceTariffType
- ControlArea
- SynchronousMachine
- ChargeProfile
- ChargeComponent
- MarketRole
- ResourceGroup
- Quantity
- ResourceCertification
- Auction
- ScheduledEvent
- PotentialTransformer
- BusinessRole
range: ControlAreaTypeKind
required: false
energy_area:
name: energy_area
description: The energy area that is forecast from this control area specification.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ControlArea.EnergyArea
multivalued: false
domain_of:
- ControlArea
range: EnergyArea
required: false
control_area_generating_unit:
name: control_area_generating_unit
description: The generating unit specifications for the control area.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ControlArea.ControlAreaGeneratingUnit
multivalued: true
domain_of:
- GeneratingUnit
- AltGeneratingUnitMeas
- ControlArea
range: ControlAreaGeneratingUnit
required: false
tie_flow:
name: tie_flow
description: The tie flows associated with the control area.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ControlArea.TieFlow
multivalued: true
domain_of:
- Terminal
- AltTieMeas
- ControlArea
range: TieFlow
required: false
energy_group:
name: energy_group
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ControlArea.EnergyGroup
multivalued: true
domain_of:
- ControlArea
- BlockDispatchInstruction
- EnergyComponent
- SvPowerFlow
- EnergyTypeReference
range: EnergyGroup
required: false
class_uri: cim:ControlArea
Induced
name: ControlArea
description: "A control area is a grouping of generating units and/or loads and a\
\ cutset of tie lines (as terminals) which may be used for a variety of purposes\
\ including automatic generation control, power flow solution area interchange control\
\ specification, and input to load forecasting. All generation and load within the\
\ area defined by the terminals on the border are considered in the area interchange\
\ control. Note that any number of overlapping control area specifications can be\
\ superimposed on the physical model. The following general principles apply to\
\ ControlArea:\r\n1. The control area orientation for net interchange is positive\
\ for an import, negative for an export.\r\n2. The control area net interchange\
\ is determined by summing flows in Terminals. The Terminals are identified by creating\
\ a set of TieFlow objects associated with a ControlArea object. Each TieFlow object\
\ identifies one Terminal.\r\n3. In a single network model, a tie between two control\
\ areas must be modelled in both control area specifications, such that the two\
\ representations of the tie flow sum to zero.\r\n4. The normal orientation of\
\ Terminal flow is positive for flow into the conducting equipment that owns the\
\ Terminal. (i.e. flow from a bus into a device is positive.) However, the orientation\
\ of each flow in the control area specification must align with the control area\
\ convention, i.e. import is positive. If the orientation of the Terminal flow referenced\
\ by a TieFlow is positive into the control area, then this is confirmed by setting\
\ TieFlow.positiveFlowIn flag TRUE. If not, the orientation must be reversed by\
\ setting the TieFlow.positiveFlowIn flag FALSE."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
is_a: PowerSystemResource
attributes:
net_interchange:
name: net_interchange
description: The specified positive net interchange into the control area, i.e.
positive sign means flow into the area.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ControlArea.netInterchange
multivalued: false
alias: net_interchange
owner: ControlArea
domain_of:
- ControlArea
range: ActivePower
required: false
p_tolerance:
name: p_tolerance
description: Active power net interchange tolerance. The attribute shall be a
positive value or zero.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ControlArea.pTolerance
multivalued: false
alias: p_tolerance
owner: ControlArea
domain_of:
- ControlArea
range: ActivePower
required: false
type:
name: type
description: The primary type of control area definition used to determine if
this is used for automatic generation control, for planning interchange control,
or other purposes. A control area specified with primary type of automatic
generation control could still be forecast and used as an interchange area in
power flow analysis.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ControlArea.type
multivalued: false
alias: type
owner: ControlArea
domain_of:
- Asset
- AcceptanceTest
- Document
- StreetDetail
- Location
- Priority
- CatalogAssetType
- Capability
- Craft
- OldPerson
- Role
- ActivityRecord
- EndDeviceEventType
- EndDeviceGroup
- DemandResponseProgram
- UsagePointGroup
- EndDeviceControlType
- Hazard
- OldCrew
- Route
- ConstraintDuration
- AceTariffType
- ControlArea
- SynchronousMachine
- ChargeProfile
- ChargeComponent
- MarketRole
- ResourceGroup
- Quantity
- ResourceCertification
- Auction
- ScheduledEvent
- PotentialTransformer
- BusinessRole
range: ControlAreaTypeKind
required: false
energy_area:
name: energy_area
description: The energy area that is forecast from this control area specification.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ControlArea.EnergyArea
multivalued: false
alias: energy_area
owner: ControlArea
domain_of:
- ControlArea
range: EnergyArea
required: false
control_area_generating_unit:
name: control_area_generating_unit
description: The generating unit specifications for the control area.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ControlArea.ControlAreaGeneratingUnit
multivalued: true
alias: control_area_generating_unit
owner: ControlArea
domain_of:
- GeneratingUnit
- AltGeneratingUnitMeas
- ControlArea
range: ControlAreaGeneratingUnit
required: false
tie_flow:
name: tie_flow
description: The tie flows associated with the control area.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
slot_uri: cim:ControlArea.TieFlow
multivalued: true
alias: tie_flow
owner: ControlArea
domain_of:
- Terminal
- AltTieMeas
- ControlArea
range: TieFlow
required: false
energy_group:
name: energy_group
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:ControlArea.EnergyGroup
multivalued: true
alias: energy_group
owner: ControlArea
domain_of:
- ControlArea
- BlockDispatchInstruction
- EnergyComponent
- SvPowerFlow
- EnergyTypeReference
range: EnergyGroup
required: false
controls:
name: controls
description: The controller outputs used to actually govern a regulating device,
e.g. the magnetization of a synchronous machine or capacitor bank breaker actuator.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.Controls
multivalued: true
alias: controls
owner: ControlArea
domain_of:
- PowerSystemResource
- HostControlArea
range: Control
required: false
measurements:
name: measurements
description: The measurements associated with this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.Measurements
multivalued: true
alias: measurements
owner: ControlArea
domain_of:
- PowerSystemResource
- ACDCTerminal
- Asset
- Location
- Procedure
- AnalogLimitSet
- AccumulatorLimitSet
range: Measurement
required: false
psrtype:
name: psrtype
description: Custom classification for this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.PSRType
multivalued: false
alias: psrtype
owner: ControlArea
domain_of:
- PowerSystemResource
range: PSRType
required: false
configuration_event:
name: configuration_event
description: All configuration events created for this Power System resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.ConfigurationEvent
multivalued: true
alias: configuration_event
owner: ControlArea
domain_of:
- PowerSystemResource
- FaultCauseType
range: ConfigurationEvent
required: false
reporting_group:
name: reporting_group
description: Reporting groups to which this power system resource belongs.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.ReportingGroup
multivalued: true
alias: reporting_group
owner: ControlArea
domain_of:
- PowerSystemResource
- BusNameMarker
- TopologicalNode
- ReportingSuperGroup
range: ReportingGroup
required: false
operating_share:
name: operating_share
description: The operating shares of this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.OperatingShare
multivalued: true
alias: operating_share
owner: ControlArea
domain_of:
- PowerSystemResource
- OperatingParticipant
range: OperatingShare
required: false
asset_datasheet:
name: asset_datasheet
description: Datasheet information for this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.AssetDatasheet
multivalued: false
alias: asset_datasheet
owner: ControlArea
domain_of:
- PowerSystemResource
range: AssetInfo
required: false
verification_action:
name: verification_action
description: The verification action that is performed on the power system resource
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.VerificationAction
multivalued: true
alias: verification_action
owner: ControlArea
domain_of:
- PowerSystemResource
range: VerificationAction
required: false
clearances:
name: clearances
description: All clearances applicable to this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.Clearances
multivalued: true
alias: clearances
owner: ControlArea
domain_of:
- PowerSystemResource
range: ClearanceDocument
required: false
generic_action:
name: generic_action
description: The generic action that is performed on the power system resource
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.GenericAction
multivalued: true
alias: generic_action
owner: ControlArea
domain_of:
- PowerSystemResource
range: GenericAction
required: false
psrevents:
name: psrevents
description: All events associated with this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.PSREvents
multivalued: true
alias: psrevents
owner: ControlArea
domain_of:
- PowerSystemResource
range: PSREvent
required: false
assets:
name: assets
description: All assets represented by this power system resource. For example,
multiple conductor assets are electrically modelled as a single AC line segment.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.Assets
multivalued: true
alias: assets
owner: ControlArea
domain_of:
- PowerSystemResource
- AssetInfo
- Location
- WorkTask
- ErpRecDelvLineItem
- AssetContainer
- ActivityRecord
- Procedure
- ReliabilityInfo
- AssetPropertyCurve
- AssetOrganisationRole
- ScheduledEvent
range: Asset
required: false
location:
name: location
description: Location of this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.Location
multivalued: false
alias: location
owner: ControlArea
domain_of:
- PowerSystemResource
- Asset
- Incident
- SwitchingOrder
- TroubleOrder
- Crew
- Fault
- PointOfSale
- TroubleTicket
- OutageOrder
- EnvironmentalMonitoringStation
- EnvironmentalLocationType
- PositionPoint
- FailureEvent
range: Location
required: false
operational_tags:
name: operational_tags
description: All operational tags placed on this power system resource.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:PowerSystemResource.OperationalTags
multivalued: true
alias: operational_tags
owner: ControlArea
domain_of:
- PowerSystemResource
- Asset
range: OperationalTag
required: false
alias_name:
name: alias_name
description: "The aliasName is free text human readable name of the object alternative\
\ to IdentifiedObject.name. It may be non unique and may not correlate to a\
\ naming hierarchy.\r\nThe attribute aliasName is retained because of backwards\
\ compatibility between CIM relases. It is however recommended to replace aliasName\
\ with the Name class as aliasName is planned for retirement at a future time.\r\
\n\r\n"
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.aliasName
multivalued: false
alias: alias_name
owner: ControlArea
domain_of:
- IdentifiedObject
range: string
required: false
description:
name: description
description: The description is a free human readable text describing or naming
the object. It may be non unique and may not correlate to a naming hierarchy.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.description
multivalued: false
alias: description
owner: ControlArea
domain_of:
- IdentifiedObject
- NameType
- NameTypeAuthority
- DataSet
- SwitchingStepGroup
- AreaReserveSpec
range: string
required: false
m_rid:
name: m_rid
description: "Master resource identifier issued by a model authority. The mRID\
\ is unique within an exchange context. Global uniqueness is easily achieved\
\ by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is\
\ strongly recommended.\r\nFor CIMXML data files in RDF syntax conforming to\
\ IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify\
\ CIM object elements."
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.mRID
multivalued: false
alias: m_rid
owner: ControlArea
domain_of:
- IdentifiedObject
- DataSet
range: string
required: false
diagram_objects:
name: diagram_objects
description: The diagram objects that are associated with the domain object.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.DiagramObjects
multivalued: true
alias: diagram_objects
owner: ControlArea
domain_of:
- IdentifiedObject
range: DiagramObject
required: false
instance_set:
name: instance_set
description: Dataset containing the data objects.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.InstanceSet
multivalued: false
alias: instance_set
owner: ControlArea
domain_of:
- IdentifiedObject
range: InstanceSet
required: true
names:
name: names
description: All names of this identified object.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.Names
multivalued: true
alias: names
owner: ControlArea
domain_of:
- IdentifiedObject
- NameType
range: Name
required: false
properties_cimdata_object:
name: properties_cimdata_object
description: The single CIM data object in the appropriate dataset context.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.PropertiesCIMDataObject
multivalued: false
alias: properties_cimdata_object
owner: ControlArea
domain_of:
- IdentifiedObject
range: ChangeSetMember
required: false
targeting_cimdata_object:
name: targeting_cimdata_object
description: Data objects registered.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
slot_uri: cim:IdentifiedObject.TargetingCIMDataObject
multivalued: true
alias: targeting_cimdata_object
owner: ControlArea
domain_of:
- IdentifiedObject
range: ChangeSetMember
required: false
class_uri: cim:ControlArea