Skip to content

Class: ACDCConverter

A unit with valves for three phases, together with unit control equipment, essential protective and switching devices, DC storage capacitors, phase reactors and auxiliaries, if any, used for conversion.

URI: cim:ACDCConverter

 classDiagram
    class ACDCConverter
      ConductingEquipment <|-- ACDCConverter


      ACDCConverter <|-- VsConverter
      ACDCConverter <|-- CsConverter


      ACDCConverter : additional_equipment_container

          ACDCConverter --> EquipmentContainer : additional_equipment_container

      ACDCConverter : aggregate

      ACDCConverter : alias_name

      ACDCConverter : asset_datasheet

          ACDCConverter --> AssetInfo : asset_datasheet

      ACDCConverter : assets

          ACDCConverter --> Asset : assets

      ACDCConverter : base_s

          ACDCConverter --> ApparentPower : base_s

      ACDCConverter : base_voltage

          ACDCConverter --> BaseVoltage : base_voltage

      ACDCConverter : clearances

          ACDCConverter --> ClearanceDocument : clearances

      ACDCConverter : configuration_event

          ACDCConverter --> ConfigurationEvent : configuration_event

      ACDCConverter : contingency_equipment

          ACDCConverter --> ContingencyEquipment : contingency_equipment

      ACDCConverter : controls

          ACDCConverter --> Control : controls

      ACDCConverter : dcterminals

          ACDCConverter --> ACDCConverterDCTerminal : dcterminals

      ACDCConverter : description

      ACDCConverter : diagram_objects

          ACDCConverter --> DiagramObject : diagram_objects

      ACDCConverter : eqiupment_limit_series_component

          ACDCConverter --> EquipmentLimitSeriesComponent : eqiupment_limit_series_component

      ACDCConverter : equipment_container

          ACDCConverter --> EquipmentContainer : equipment_container

      ACDCConverter : equipment_unavailability_schedule

          ACDCConverter --> EquipmentUnavailabilitySchedule : equipment_unavailability_schedule

      ACDCConverter : faults

          ACDCConverter --> Fault : faults

      ACDCConverter : generic_action

          ACDCConverter --> GenericAction : generic_action

      ACDCConverter : grounding_action

          ACDCConverter --> GroundAction : grounding_action

      ACDCConverter : idc

          ACDCConverter --> CurrentFlow : idc

      ACDCConverter : idle_loss

          ACDCConverter --> ActivePower : idle_loss

      ACDCConverter : in_service

      ACDCConverter : instance_set

          ACDCConverter --> InstanceSet : instance_set

      ACDCConverter : jumping_action

          ACDCConverter --> JumperAction : jumping_action

      ACDCConverter : limit_dependency_model

          ACDCConverter --> LimitDependency : limit_dependency_model

      ACDCConverter : location

          ACDCConverter --> Location : location

      ACDCConverter : m_rid

      ACDCConverter : max_p

          ACDCConverter --> ActivePower : max_p

      ACDCConverter : max_udc

          ACDCConverter --> Voltage : max_udc

      ACDCConverter : measurements

          ACDCConverter --> Measurement : measurements

      ACDCConverter : min_p

          ACDCConverter --> ActivePower : min_p

      ACDCConverter : min_udc

          ACDCConverter --> Voltage : min_udc

      ACDCConverter : names

          ACDCConverter --> Name : names

      ACDCConverter : network_analysis_enabled

      ACDCConverter : normally_in_service

      ACDCConverter : number_of_valves

      ACDCConverter : operating_share

          ACDCConverter --> OperatingShare : operating_share

      ACDCConverter : operational_limit_set

          ACDCConverter --> OperationalLimitSet : operational_limit_set

      ACDCConverter : operational_restrictions

          ACDCConverter --> OperationalRestriction : operational_restrictions

      ACDCConverter : operational_tags

          ACDCConverter --> OperationalTag : operational_tags

      ACDCConverter : outage

          ACDCConverter --> Outage : outage

      ACDCConverter : outages

          ACDCConverter --> Outage : outages

      ACDCConverter : p

          ACDCConverter --> ActivePower : p

      ACDCConverter : pcc_terminal

          ACDCConverter --> Terminal : pcc_terminal

      ACDCConverter : pin_equipment

          ACDCConverter --> PinEquipment : pin_equipment

      ACDCConverter : pole_loss_p

          ACDCConverter --> ActivePower : pole_loss_p

      ACDCConverter : properties_cimdata_object

          ACDCConverter --> ChangeSetMember : properties_cimdata_object

      ACDCConverter : protection_equipments

          ACDCConverter --> ProtectionEquipment : protection_equipments

      ACDCConverter : protective_action_adjustment

          ACDCConverter --> ProtectiveActionAdjustment : protective_action_adjustment

      ACDCConverter : protective_action_equipment

          ACDCConverter --> ProtectiveActionEquipment : protective_action_equipment

      ACDCConverter : psrevents

          ACDCConverter --> PSREvent : psrevents

      ACDCConverter : psrtype

          ACDCConverter --> PSRType : psrtype

      ACDCConverter : q

          ACDCConverter --> ReactivePower : q

      ACDCConverter : rated_udc

          ACDCConverter --> Voltage : rated_udc

      ACDCConverter : reporting_group

          ACDCConverter --> ReportingGroup : reporting_group

      ACDCConverter : resistive_loss

          ACDCConverter --> Resistance : resistive_loss

      ACDCConverter : sv_status

          ACDCConverter --> SvStatus : sv_status

      ACDCConverter : switching_loss

          ACDCConverter --> ActivePowerPerCurrentFlow : switching_loss

      ACDCConverter : target_ppcc

          ACDCConverter --> ActivePower : target_ppcc

      ACDCConverter : target_udc

          ACDCConverter --> Voltage : target_udc

      ACDCConverter : targeting_cimdata_object

          ACDCConverter --> ChangeSetMember : targeting_cimdata_object

      ACDCConverter : terminals

          ACDCConverter --> Terminal : terminals

      ACDCConverter : uc

          ACDCConverter --> Voltage : uc

      ACDCConverter : udc

          ACDCConverter --> Voltage : udc

      ACDCConverter : usage_points

          ACDCConverter --> UsagePoint : usage_points

      ACDCConverter : valve_u

          ACDCConverter --> Voltage : valve_u

      ACDCConverter : verification_action

          ACDCConverter --> VerificationAction : verification_action

      ACDCConverter : weather_station

          ACDCConverter --> WeatherStation : weather_station

Inheritance

Slots

Name Cardinality and Range Description Inheritance
base_s 0..1
ApparentPower
Base apparent power of the converter pole direct
idc 0..1
CurrentFlow
Converter DC current, also called Id direct
idle_loss 0..1
ActivePower
Active power loss in pole at no power transfer direct
max_p 0..1
ActivePower
Maximum active power limit direct
max_udc 0..1
Voltage
The maximum voltage on the DC side at which the converter should operate direct
min_p 0..1
ActivePower
Minimum active power limit direct
min_udc 0..1
Voltage
The minimum voltage on the DC side at which the converter should operate direct
number_of_valves 0..1
Integer
Number of valves in the converter direct
p 0..1
ActivePower
Active power at the point of common coupling direct
pole_loss_p 0..1
ActivePower
The active power loss at a DC Pole
direct
q 0..1
ReactivePower
Reactive power at the point of common coupling direct
rated_udc 0..1
Voltage
Rated converter DC voltage, also called UdN direct
resistive_loss 0..1
Resistance
It is converter’s configuration data used in power flow direct
switching_loss 0..1
ActivePowerPerCurrentFlow
Switching losses, relative to the base apparent power 'baseS' direct
target_ppcc 0..1
ActivePower
Real power injection target in AC grid, at point of common coupling direct
target_udc 0..1
Voltage
Target value for DC voltage magnitude direct
uc 0..1
Voltage
Line-to-line converter voltage, the voltage at the AC side of the valve direct
udc 0..1
Voltage
Converter voltage at the DC side, also called Ud direct
valve_u 0..1
Voltage
Valve threshold voltage, also called Uvalve direct
pcc_terminal 0..1
Terminal
Point of common coupling terminal for this converter DC side direct
dcterminals 0..*
ACDCConverterDCTerminal
A DC converter have DC converter terminals direct
protective_action_adjustment 0..*
ProtectiveActionAdjustment
The operating condition to the Conducting Equipment is changed when protectiv... ConductingEquipment
sv_status 0..*
SvStatus
The status state variable associated with this conducting equipment ConductingEquipment
protection_equipments 0..*
ProtectionEquipment
Protection equipment used to protect specific conducting equipment ConductingEquipment
base_voltage 0..1
BaseVoltage
Base voltage of this conducting equipment ConductingEquipment
terminals 0..*
Terminal
Conducting equipment have terminals that may be connected to other conducting... ConductingEquipment
jumping_action 0..1
JumperAction
Jumper action involving jumping operation on this conducting equipment ConductingEquipment
grounding_action 0..1
GroundAction
Action involving grounding operation on this conducting equipment ConductingEquipment
outage 0..1
Outage
The outage that is isolated by the outage isolation equipment ConductingEquipment
aggregate 0..1
Boolean
The aggregate flag provides an alternative way of representing an aggregated ... Equipment
in_service 0..1
Boolean
Specifies the availability of the equipment Equipment
network_analysis_enabled 0..1
Boolean
The equipment is enabled to participate in network analysis Equipment
normally_in_service 0..1
Boolean
Specifies the availability of the equipment under normal operating conditions Equipment
weather_station 0..*
WeatherStation
Equipment
operational_limit_set 0..*
OperationalLimitSet
The operational limit sets associated with this equipment Equipment
contingency_equipment 0..*
ContingencyEquipment
The contingency equipments in which this equipment participates Equipment
equipment_container 0..1
EquipmentContainer
Container of this equipment Equipment
faults 0..*
Fault
All faults on this equipment Equipment
limit_dependency_model 0..*
LimitDependency
Limit dependencymodels organized under this equipment as a means for organizi... Equipment
eqiupment_limit_series_component 0..*
EquipmentLimitSeriesComponent
Equipment limit series calculation component to which this equipment contribu... Equipment
protective_action_equipment 0..*
ProtectiveActionEquipment
Protective action is controlling equipment Equipment
pin_equipment 0..*
PinEquipment
Equipment
equipment_unavailability_schedule 0..*
EquipmentUnavailabilitySchedule
Equipment
additional_equipment_container 0..*
EquipmentContainer
Additional equipment container beyond the primary equipment container Equipment
usage_points 0..*
UsagePoint
All usage points connected to the electrical grid through this equipment Equipment
outages 0..*
Outage
All outages in which this equipment is involved Equipment
operational_restrictions 0..*
OperationalRestriction
All operational restrictions for this equipment Equipment
controls 0..*
Control
The controller outputs used to actually govern a regulating device, e PowerSystemResource
measurements 0..*
Measurement
The measurements associated with this power system resource PowerSystemResource
psrtype 0..1
PSRType
Custom classification for this power system resource PowerSystemResource
configuration_event 0..*
ConfigurationEvent
All configuration events created for this Power System resource PowerSystemResource
reporting_group 0..*
ReportingGroup
Reporting groups to which this power system resource belongs PowerSystemResource
operating_share 0..*
OperatingShare
The operating shares of this power system resource PowerSystemResource
asset_datasheet 0..1
AssetInfo
Datasheet information for this power system resource PowerSystemResource
verification_action 0..*
VerificationAction
The verification action that is performed on the power system resource PowerSystemResource
clearances 0..*
ClearanceDocument
All clearances applicable to this power system resource PowerSystemResource
generic_action 0..*
GenericAction
The generic action that is performed on the power system resource PowerSystemResource
psrevents 0..*
PSREvent
All events associated with this power system resource PowerSystemResource
assets 0..*
Asset
All assets represented by this power system resource PowerSystemResource
location 0..1
Location
Location of this power system resource PowerSystemResource
operational_tags 0..*
OperationalTag
All operational tags placed on this power system resource PowerSystemResource
alias_name 0..1
String
The aliasName is free text human readable name of the object alternative to I... IdentifiedObject
description 0..1
String
The description is a free human readable text describing or naming the object IdentifiedObject
m_rid 0..1
String
Master resource identifier issued by a model authority IdentifiedObject
diagram_objects 0..*
DiagramObject
The diagram objects that are associated with the domain object IdentifiedObject
instance_set 1..1
InstanceSet
Dataset containing the data objects IdentifiedObject
names 0..*
Name
All names of this identified object IdentifiedObject
properties_cimdata_object 0..1
ChangeSetMember
The single CIM data object in the appropriate dataset context IdentifiedObject
targeting_cimdata_object 0..*
ChangeSetMember
Data objects registered IdentifiedObject

Usages

used by used in type used
Terminal converter_dcsides range ACDCConverter
MktTerminal converter_dcsides range ACDCConverter
ACDCConverterDCTerminal dcconducting_equipment range ACDCConverter

Identifier and Mapping Information

Schema Source

  • from schema: https://cim.ucaiug.io/ns#TC57CIM

Mappings

Mapping Type Mapped Value
self cim:ACDCConverter
native cim:ACDCConverter

LinkML Source

Direct

name: ACDCConverter
description: A unit with valves for three phases, together with unit control equipment,
  essential protective and switching devices, DC storage capacitors, phase reactors
  and auxiliaries, if any, used for conversion.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
is_a: ConductingEquipment
attributes:
  base_s:
    name: base_s
    description: Base apparent power of the converter pole. The attribute shall be
      a positive value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.baseS
    multivalued: false
    domain_of:
    - ACDCConverter
    range: ApparentPower
    required: false
  idc:
    name: idc
    description: Converter DC current, also called Id. It is converter’s state variable,
      result from power flow.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.idc
    multivalued: false
    domain_of:
    - ACDCConverter
    range: CurrentFlow
    required: false
  idle_loss:
    name: idle_loss
    description: Active power loss in pole at no power transfer. It is converter’s
      configuration data used in power flow. The attribute shall be a positive value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.idleLoss
    multivalued: false
    domain_of:
    - ACDCConverter
    range: ActivePower
    required: false
  max_p:
    name: max_p
    description: Maximum active power limit. The value is overwritten by values of
      VsCapabilityCurve, if present.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ACDCConverter.maxP
    multivalued: false
    domain_of:
    - EquivalentInjection
    - PowerElectronicsUnit
    - ACDCConverter
    - FrequencyConverter
    - ExternalNetworkInjection
    - GeneratorTypeAsset
    range: ActivePower
    required: false
  max_udc:
    name: max_udc
    description: The maximum voltage on the DC side at which the converter should
      operate. It is converter’s configuration data used in power flow. The attribute
      shall be a positive value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.maxUdc
    multivalued: false
    domain_of:
    - ACDCConverter
    range: Voltage
    required: false
  min_p:
    name: min_p
    description: Minimum active power limit. The value is overwritten by values of
      VsCapabilityCurve, if present.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ACDCConverter.minP
    multivalued: false
    domain_of:
    - EquivalentInjection
    - PowerElectronicsUnit
    - ACDCConverter
    - FrequencyConverter
    - ExternalNetworkInjection
    - GeneratorTypeAsset
    range: ActivePower
    required: false
  min_udc:
    name: min_udc
    description: The minimum voltage on the DC side at which the converter should
      operate. It is converter’s configuration data used in power flow. The attribute
      shall be a positive value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.minUdc
    multivalued: false
    domain_of:
    - ACDCConverter
    range: Voltage
    required: false
  number_of_valves:
    name: number_of_valves
    description: Number of valves in the converter. Used in loss calculations.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.numberOfValves
    multivalued: false
    domain_of:
    - ACDCConverter
    range: integer
    required: false
  p:
    name: p
    description: "Active power at the point of common coupling. Load sign convention\
      \ is used, i.e. positive sign means flow out from a node.\r\nStarting value\
      \ for a steady state solution in the case a simplified power flow model is used."
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ACDCConverter.p
    multivalued: false
    domain_of:
    - EnergyGroup
    - BlockDispatchOrder
    - SvPowerFlow
    - RotatingMachine
    - EquivalentInjection
    - PowerElectronicsConnection
    - PowerElectronicsConnectionPhase
    - ACDCConverter
    - EnergyConsumerPhase
    - EnergyConsumer
    - ExternalNetworkInjection
    - GovHydroPID2
    - UnderexcLimIEEE2
    - UnderexcLim2Simplified
    range: ActivePower
    required: false
  pole_loss_p:
    name: pole_loss_p
    description: "The active power loss at a DC Pole \r\n= idleLoss + switchingLoss*|Idc|\
      \ + resitiveLoss*Idc^2.\r\nFor lossless operation Pdc=Pac.\r\nFor rectifier\
      \ operation with losses Pdc=Pac-lossP.\r\nFor inverter operation with losses\
      \ Pdc=Pac+lossP.\r\nIt is converter’s state variable used in power flow. The\
      \ attribute shall be a positive value."
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.poleLossP
    multivalued: false
    domain_of:
    - ACDCConverter
    range: ActivePower
    required: false
  q:
    name: q
    description: "Reactive power at the point of common coupling. Load sign convention\
      \ is used, i.e. positive sign means flow out from a node.\r\nStarting value\
      \ for a steady state solution in the case a simplified power flow model is used."
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ACDCConverter.q
    multivalued: false
    domain_of:
    - SvPowerFlow
    - RotatingMachine
    - EquivalentInjection
    - PowerElectronicsConnection
    - PowerElectronicsConnectionPhase
    - ACDCConverter
    - EnergyConsumerPhase
    - EnergyConsumer
    - StaticVarCompensator
    - ExternalNetworkInjection
    - UnderexcLimIEEE2
    - UnderexcLim2Simplified
    range: ReactivePower
    required: false
  rated_udc:
    name: rated_udc
    description: Rated converter DC voltage, also called UdN. The attribute shall
      be a positive value. It is converter’s configuration data used in power flow.
      For instance a bipolar HVDC link with value  200 kV has a 400kV difference between
      the dc lines.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ACDCConverter.ratedUdc
    multivalued: false
    domain_of:
    - DCConductingEquipment
    - ACDCConverter
    range: Voltage
    required: false
  resistive_loss:
    name: resistive_loss
    description: It is converter’s configuration data used in power flow. Refer to
      poleLossP. The attribute shall be a positive value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.resistiveLoss
    multivalued: false
    domain_of:
    - ACDCConverter
    range: Resistance
    required: false
  switching_loss:
    name: switching_loss
    description: Switching losses, relative to the base apparent power 'baseS'. Refer
      to poleLossP. The attribute shall be a positive value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.switchingLoss
    multivalued: false
    domain_of:
    - ACDCConverter
    range: ActivePowerPerCurrentFlow
    required: false
  target_ppcc:
    name: target_ppcc
    description: Real power injection target in AC grid, at point of common coupling.  Load
      sign convention is used, i.e. positive sign means flow out from a node.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.targetPpcc
    multivalued: false
    domain_of:
    - ACDCConverter
    range: ActivePower
    required: false
  target_udc:
    name: target_udc
    description: Target value for DC voltage magnitude. The attribute shall be a positive
      value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.targetUdc
    multivalued: false
    domain_of:
    - ACDCConverter
    range: Voltage
    required: false
  uc:
    name: uc
    description: Line-to-line converter voltage, the voltage at the AC side of the
      valve. It is converter’s state variable, result from power flow. The attribute
      shall be a positive value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.uc
    multivalued: false
    domain_of:
    - ACDCConverter
    - GovHydroIEEE2
    - GovSteamIEEE1
    - GovHydro2
    - GovHydro4
    - GovSteam1
    - GovSteamFV3
    range: Voltage
    required: false
  udc:
    name: udc
    description: Converter voltage at the DC side, also called Ud. It is converter’s
      state variable, result from power flow. The attribute shall be a positive value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.udc
    multivalued: false
    domain_of:
    - ACDCConverter
    range: Voltage
    required: false
  valve_u:
    name: valve_u
    description: Valve threshold voltage, also called Uvalve. Forward voltage drop
      when the valve is conducting. Used in loss calculations, i.e. the switchLoss
      depend on numberOfValves * valveU0.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.valveU0
    multivalued: false
    domain_of:
    - ACDCConverter
    range: Voltage
    required: false
  pcc_terminal:
    name: pcc_terminal
    description: Point of common coupling terminal for this converter DC side. It
      is typically the terminal on the power transformer (or switch) closest to the
      AC network.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.PccTerminal
    multivalued: false
    domain_of:
    - ACDCConverter
    range: Terminal
    required: false
  dcterminals:
    name: dcterminals
    description: A DC converter have DC converter terminals. A converter has two DC
      converter terminals.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ACDCConverter.DCTerminals
    multivalued: true
    domain_of:
    - DCNode
    - DCTopologicalNode
    - DCConductingEquipment
    - ACDCConverter
    range: ACDCConverterDCTerminal
    required: false
class_uri: cim:ACDCConverter

Induced

name: ACDCConverter
description: A unit with valves for three phases, together with unit control equipment,
  essential protective and switching devices, DC storage capacitors, phase reactors
  and auxiliaries, if any, used for conversion.
from_schema: https://cim.ucaiug.io/ns#TC57CIM
rank: 1000
is_a: ConductingEquipment
attributes:
  base_s:
    name: base_s
    description: Base apparent power of the converter pole. The attribute shall be
      a positive value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.baseS
    multivalued: false
    alias: base_s
    owner: ACDCConverter
    domain_of:
    - ACDCConverter
    range: ApparentPower
    required: false
  idc:
    name: idc
    description: Converter DC current, also called Id. It is converter’s state variable,
      result from power flow.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.idc
    multivalued: false
    alias: idc
    owner: ACDCConverter
    domain_of:
    - ACDCConverter
    range: CurrentFlow
    required: false
  idle_loss:
    name: idle_loss
    description: Active power loss in pole at no power transfer. It is converter’s
      configuration data used in power flow. The attribute shall be a positive value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.idleLoss
    multivalued: false
    alias: idle_loss
    owner: ACDCConverter
    domain_of:
    - ACDCConverter
    range: ActivePower
    required: false
  max_p:
    name: max_p
    description: Maximum active power limit. The value is overwritten by values of
      VsCapabilityCurve, if present.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ACDCConverter.maxP
    multivalued: false
    alias: max_p
    owner: ACDCConverter
    domain_of:
    - EquivalentInjection
    - PowerElectronicsUnit
    - ACDCConverter
    - FrequencyConverter
    - ExternalNetworkInjection
    - GeneratorTypeAsset
    range: ActivePower
    required: false
  max_udc:
    name: max_udc
    description: The maximum voltage on the DC side at which the converter should
      operate. It is converter’s configuration data used in power flow. The attribute
      shall be a positive value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.maxUdc
    multivalued: false
    alias: max_udc
    owner: ACDCConverter
    domain_of:
    - ACDCConverter
    range: Voltage
    required: false
  min_p:
    name: min_p
    description: Minimum active power limit. The value is overwritten by values of
      VsCapabilityCurve, if present.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ACDCConverter.minP
    multivalued: false
    alias: min_p
    owner: ACDCConverter
    domain_of:
    - EquivalentInjection
    - PowerElectronicsUnit
    - ACDCConverter
    - FrequencyConverter
    - ExternalNetworkInjection
    - GeneratorTypeAsset
    range: ActivePower
    required: false
  min_udc:
    name: min_udc
    description: The minimum voltage on the DC side at which the converter should
      operate. It is converter’s configuration data used in power flow. The attribute
      shall be a positive value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.minUdc
    multivalued: false
    alias: min_udc
    owner: ACDCConverter
    domain_of:
    - ACDCConverter
    range: Voltage
    required: false
  number_of_valves:
    name: number_of_valves
    description: Number of valves in the converter. Used in loss calculations.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.numberOfValves
    multivalued: false
    alias: number_of_valves
    owner: ACDCConverter
    domain_of:
    - ACDCConverter
    range: integer
    required: false
  p:
    name: p
    description: "Active power at the point of common coupling. Load sign convention\
      \ is used, i.e. positive sign means flow out from a node.\r\nStarting value\
      \ for a steady state solution in the case a simplified power flow model is used."
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ACDCConverter.p
    multivalued: false
    alias: p
    owner: ACDCConverter
    domain_of:
    - EnergyGroup
    - BlockDispatchOrder
    - SvPowerFlow
    - RotatingMachine
    - EquivalentInjection
    - PowerElectronicsConnection
    - PowerElectronicsConnectionPhase
    - ACDCConverter
    - EnergyConsumerPhase
    - EnergyConsumer
    - ExternalNetworkInjection
    - GovHydroPID2
    - UnderexcLimIEEE2
    - UnderexcLim2Simplified
    range: ActivePower
    required: false
  pole_loss_p:
    name: pole_loss_p
    description: "The active power loss at a DC Pole \r\n= idleLoss + switchingLoss*|Idc|\
      \ + resitiveLoss*Idc^2.\r\nFor lossless operation Pdc=Pac.\r\nFor rectifier\
      \ operation with losses Pdc=Pac-lossP.\r\nFor inverter operation with losses\
      \ Pdc=Pac+lossP.\r\nIt is converter’s state variable used in power flow. The\
      \ attribute shall be a positive value."
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.poleLossP
    multivalued: false
    alias: pole_loss_p
    owner: ACDCConverter
    domain_of:
    - ACDCConverter
    range: ActivePower
    required: false
  q:
    name: q
    description: "Reactive power at the point of common coupling. Load sign convention\
      \ is used, i.e. positive sign means flow out from a node.\r\nStarting value\
      \ for a steady state solution in the case a simplified power flow model is used."
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ACDCConverter.q
    multivalued: false
    alias: q
    owner: ACDCConverter
    domain_of:
    - SvPowerFlow
    - RotatingMachine
    - EquivalentInjection
    - PowerElectronicsConnection
    - PowerElectronicsConnectionPhase
    - ACDCConverter
    - EnergyConsumerPhase
    - EnergyConsumer
    - StaticVarCompensator
    - ExternalNetworkInjection
    - UnderexcLimIEEE2
    - UnderexcLim2Simplified
    range: ReactivePower
    required: false
  rated_udc:
    name: rated_udc
    description: Rated converter DC voltage, also called UdN. The attribute shall
      be a positive value. It is converter’s configuration data used in power flow.
      For instance a bipolar HVDC link with value  200 kV has a 400kV difference between
      the dc lines.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ACDCConverter.ratedUdc
    multivalued: false
    alias: rated_udc
    owner: ACDCConverter
    domain_of:
    - DCConductingEquipment
    - ACDCConverter
    range: Voltage
    required: false
  resistive_loss:
    name: resistive_loss
    description: It is converter’s configuration data used in power flow. Refer to
      poleLossP. The attribute shall be a positive value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.resistiveLoss
    multivalued: false
    alias: resistive_loss
    owner: ACDCConverter
    domain_of:
    - ACDCConverter
    range: Resistance
    required: false
  switching_loss:
    name: switching_loss
    description: Switching losses, relative to the base apparent power 'baseS'. Refer
      to poleLossP. The attribute shall be a positive value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.switchingLoss
    multivalued: false
    alias: switching_loss
    owner: ACDCConverter
    domain_of:
    - ACDCConverter
    range: ActivePowerPerCurrentFlow
    required: false
  target_ppcc:
    name: target_ppcc
    description: Real power injection target in AC grid, at point of common coupling.  Load
      sign convention is used, i.e. positive sign means flow out from a node.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.targetPpcc
    multivalued: false
    alias: target_ppcc
    owner: ACDCConverter
    domain_of:
    - ACDCConverter
    range: ActivePower
    required: false
  target_udc:
    name: target_udc
    description: Target value for DC voltage magnitude. The attribute shall be a positive
      value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.targetUdc
    multivalued: false
    alias: target_udc
    owner: ACDCConverter
    domain_of:
    - ACDCConverter
    range: Voltage
    required: false
  uc:
    name: uc
    description: Line-to-line converter voltage, the voltage at the AC side of the
      valve. It is converter’s state variable, result from power flow. The attribute
      shall be a positive value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.uc
    multivalued: false
    alias: uc
    owner: ACDCConverter
    domain_of:
    - ACDCConverter
    - GovHydroIEEE2
    - GovSteamIEEE1
    - GovHydro2
    - GovHydro4
    - GovSteam1
    - GovSteamFV3
    range: Voltage
    required: false
  udc:
    name: udc
    description: Converter voltage at the DC side, also called Ud. It is converter’s
      state variable, result from power flow. The attribute shall be a positive value.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.udc
    multivalued: false
    alias: udc
    owner: ACDCConverter
    domain_of:
    - ACDCConverter
    range: Voltage
    required: false
  valve_u:
    name: valve_u
    description: Valve threshold voltage, also called Uvalve. Forward voltage drop
      when the valve is conducting. Used in loss calculations, i.e. the switchLoss
      depend on numberOfValves * valveU0.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.valveU0
    multivalued: false
    alias: valve_u
    owner: ACDCConverter
    domain_of:
    - ACDCConverter
    range: Voltage
    required: false
  pcc_terminal:
    name: pcc_terminal
    description: Point of common coupling terminal for this converter DC side. It
      is typically the terminal on the power transformer (or switch) closest to the
      AC network.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ACDCConverter.PccTerminal
    multivalued: false
    alias: pcc_terminal
    owner: ACDCConverter
    domain_of:
    - ACDCConverter
    range: Terminal
    required: false
  dcterminals:
    name: dcterminals
    description: A DC converter have DC converter terminals. A converter has two DC
      converter terminals.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ACDCConverter.DCTerminals
    multivalued: true
    alias: dcterminals
    owner: ACDCConverter
    domain_of:
    - DCNode
    - DCTopologicalNode
    - DCConductingEquipment
    - ACDCConverter
    range: ACDCConverterDCTerminal
    required: false
  protective_action_adjustment:
    name: protective_action_adjustment
    description: 'The operating condition to the Conducting Equipment is changed when
      protective action adjustment is activated. For ShuntCompensator or other conducting
      equipment that operates on discrete values (integer), the values given in float
      will be rounded. '
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ConductingEquipment.ProtectiveActionAdjustment
    multivalued: true
    alias: protective_action_adjustment
    owner: ACDCConverter
    domain_of:
    - Measurement
    - ConductingEquipment
    - DCConductingEquipment
    range: ProtectiveActionAdjustment
    required: false
  sv_status:
    name: sv_status
    description: The status state variable associated with this conducting equipment.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ConductingEquipment.SvStatus
    multivalued: true
    alias: sv_status
    owner: ACDCConverter
    domain_of:
    - ConductingEquipment
    range: SvStatus
    required: false
  protection_equipments:
    name: protection_equipments
    description: 'Protection equipment  used to protect specific conducting equipment. '
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ConductingEquipment.ProtectionEquipments
    multivalued: true
    alias: protection_equipments
    owner: ACDCConverter
    domain_of:
    - ConductingEquipment
    range: ProtectionEquipment
    required: false
  base_voltage:
    name: base_voltage
    description: Base voltage of this conducting equipment.  Use only when there is
      no voltage level container used and only one base voltage applies.  For example,
      not used for transformers.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ConductingEquipment.BaseVoltage
    multivalued: false
    alias: base_voltage
    owner: ACDCConverter
    domain_of:
    - TopologicalNode
    - TransformerEnd
    - ConductingEquipment
    - VoltageLevel
    - AssetDeployment
    range: BaseVoltage
    required: false
  terminals:
    name: terminals
    description: Conducting equipment have terminals that may be connected to other
      conducting equipment terminals via connectivity nodes or topological nodes.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ConductingEquipment.Terminals
    multivalued: true
    alias: terminals
    owner: ACDCConverter
    domain_of:
    - ConnectivityNode
    - ConductingEquipment
    range: Terminal
    required: false
  jumping_action:
    name: jumping_action
    description: Jumper action involving jumping operation on this conducting equipment.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ConductingEquipment.JumpingAction
    multivalued: false
    alias: jumping_action
    owner: ACDCConverter
    domain_of:
    - ConductingEquipment
    range: JumperAction
    required: false
  grounding_action:
    name: grounding_action
    description: Action involving grounding operation on this conducting equipment.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:ConductingEquipment.GroundingAction
    multivalued: false
    alias: grounding_action
    owner: ACDCConverter
    domain_of:
    - ConductingEquipment
    range: GroundAction
    required: false
  outage:
    name: outage
    description: The outage that is isolated by the outage isolation equipment.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:ConductingEquipment.Outage
    multivalued: false
    alias: outage
    owner: ACDCConverter
    domain_of:
    - Incident
    - SwitchingPlan
    - UsagePoint
    - ConductingEquipment
    - Crew
    - EstimatedRestorationTime
    - OutageArea
    - Fault
    range: Outage
    required: false
  aggregate:
    name: aggregate
    description: "The aggregate flag provides an alternative way of representing an\
      \ aggregated (equivalent) element. It is applicable in cases when the dedicated\
      \ classes for equivalent equipment do not have all of the attributes necessary\
      \ to represent the required level of detail.  In case the flag is set to “true”\
      \ the single instance of equipment represents multiple pieces of equipment that\
      \ have been modelled together as an aggregate equivalent obtained by a network\
      \ reduction procedure. Examples would be power transformers or synchronous machines\
      \ operating in parallel modelled as a single aggregate power transformer or\
      \ aggregate synchronous machine.  \r\nThe attribute is not used for EquivalentBranch,\
      \ EquivalentShunt and EquivalentInjection."
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:Equipment.aggregate
    multivalued: false
    alias: aggregate
    owner: ACDCConverter
    domain_of:
    - Equipment
    - ReadingType
    range: boolean
    required: false
  in_service:
    name: in_service
    description: Specifies the availability of the equipment. True means the equipment
      is available for topology processing, which determines if the equipment is energized
      or not. False means that the equipment is treated by network applications as
      if it is not in the model.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:Equipment.inService
    multivalued: false
    alias: in_service
    owner: ACDCConverter
    domain_of:
    - Equipment
    - SvStatus
    - ProtectiveActionEquipment
    range: boolean
    required: false
  network_analysis_enabled:
    name: network_analysis_enabled
    description: The equipment is enabled to participate in network analysis.  If
      unspecified, the value is assumed to be true.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:Equipment.networkAnalysisEnabled
    multivalued: false
    alias: network_analysis_enabled
    owner: ACDCConverter
    domain_of:
    - Equipment
    range: boolean
    required: false
  normally_in_service:
    name: normally_in_service
    description: Specifies the availability of the equipment under normal operating
      conditions. True means the equipment is available for topology processing, which
      determines if the equipment is energized or not. False means that the equipment
      is treated by network applications as if it is not in the model.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:Equipment.normallyInService
    multivalued: false
    alias: normally_in_service
    owner: ACDCConverter
    domain_of:
    - Equipment
    range: boolean
    required: false
  weather_station:
    name: weather_station
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:Equipment.WeatherStation
    multivalued: true
    alias: weather_station
    owner: ACDCConverter
    domain_of:
    - Equipment
    range: WeatherStation
    required: false
  operational_limit_set:
    name: operational_limit_set
    description: The operational limit sets associated with this equipment.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:Equipment.OperationalLimitSet
    multivalued: true
    alias: operational_limit_set
    owner: ACDCConverter
    domain_of:
    - ACDCTerminal
    - OperationalLimit
    - Equipment
    range: OperationalLimitSet
    required: false
  contingency_equipment:
    name: contingency_equipment
    description: The contingency equipments in which this equipment participates.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:Equipment.ContingencyEquipment
    multivalued: true
    alias: contingency_equipment
    owner: ACDCConverter
    domain_of:
    - Equipment
    range: ContingencyEquipment
    required: false
  equipment_container:
    name: equipment_container
    description: Container of this equipment.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:Equipment.EquipmentContainer
    multivalued: false
    alias: equipment_container
    owner: ACDCConverter
    domain_of:
    - Equipment
    range: EquipmentContainer
    required: false
  faults:
    name: faults
    description: All faults on this equipment.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:Equipment.Faults
    multivalued: true
    alias: faults
    owner: ACDCConverter
    domain_of:
    - Equipment
    - Outage
    - FaultCauseType
    range: Fault
    required: false
  limit_dependency_model:
    name: limit_dependency_model
    description: Limit dependencymodels organized under this equipment as a means
      for organizing the model in a tree view.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    slot_uri: cim:Equipment.LimitDependencyModel
    multivalued: true
    alias: limit_dependency_model
    owner: ACDCConverter
    domain_of:
    - OperationalLimit
    - Equipment
    range: LimitDependency
    required: false
  eqiupment_limit_series_component:
    name: eqiupment_limit_series_component
    description: Equipment limit series calculation component to which this equipment
      contributes.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:Equipment.EqiupmentLimitSeriesComponent
    multivalued: true
    alias: eqiupment_limit_series_component
    owner: ACDCConverter
    domain_of:
    - Equipment
    range: EquipmentLimitSeriesComponent
    required: false
  protective_action_equipment:
    name: protective_action_equipment
    description: Protective action is controlling equipment. This can be direct signals
      from the control center, or emulation of action done by protection equipment.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:Equipment.ProtectiveActionEquipment
    multivalued: true
    alias: protective_action_equipment
    owner: ACDCConverter
    domain_of:
    - Equipment
    range: ProtectiveActionEquipment
    required: false
  pin_equipment:
    name: pin_equipment
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:Equipment.PinEquipment
    multivalued: true
    alias: pin_equipment
    owner: ACDCConverter
    domain_of:
    - Equipment
    range: PinEquipment
    required: false
  equipment_unavailability_schedule:
    name: equipment_unavailability_schedule
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:Equipment.EquipmentUnavailabilitySchedule
    multivalued: true
    alias: equipment_unavailability_schedule
    owner: ACDCConverter
    domain_of:
    - Equipment
    - UnavailabilitySwitchAction
    - UnavailablitySchedule
    range: EquipmentUnavailabilitySchedule
    required: false
  additional_equipment_container:
    name: additional_equipment_container
    description: Additional equipment container beyond the primary equipment container.  The
      equipment is contained in another equipment container, but also grouped with
      this equipment container.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:Equipment.AdditionalEquipmentContainer
    multivalued: true
    alias: additional_equipment_container
    owner: ACDCConverter
    domain_of:
    - Equipment
    range: EquipmentContainer
    required: false
  usage_points:
    name: usage_points
    description: All usage points connected to the electrical grid through this equipment.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:Equipment.UsagePoints
    multivalued: true
    alias: usage_points
    owner: ACDCConverter
    domain_of:
    - Equipment
    - CustomerAgreement
    - ServiceCategory
    - PricingStructure
    - EndDeviceControl
    - UsagePointGroup
    - ServiceLocation
    - MetrologyRequirement
    - ServiceSupplier
    - UsagePointLocation
    range: UsagePoint
    required: false
  outages:
    name: outages
    description: All outages in which this equipment is involved.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:Equipment.Outages
    multivalued: true
    alias: outages
    owner: ACDCConverter
    domain_of:
    - Equipment
    range: Outage
    required: false
  operational_restrictions:
    name: operational_restrictions
    description: All operational restrictions for this equipment.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:Equipment.OperationalRestrictions
    multivalued: true
    alias: operational_restrictions
    owner: ACDCConverter
    domain_of:
    - Equipment
    - ProductAssetModel
    range: OperationalRestriction
    required: false
  controls:
    name: controls
    description: The controller outputs used to actually govern a regulating device,
      e.g. the magnetization of a synchronous machine or capacitor bank breaker actuator.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.Controls
    multivalued: true
    alias: controls
    owner: ACDCConverter
    domain_of:
    - PowerSystemResource
    - HostControlArea
    range: Control
    required: false
  measurements:
    name: measurements
    description: The measurements associated with this power system resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.Measurements
    multivalued: true
    alias: measurements
    owner: ACDCConverter
    domain_of:
    - PowerSystemResource
    - ACDCTerminal
    - Asset
    - Location
    - Procedure
    - AnalogLimitSet
    - AccumulatorLimitSet
    range: Measurement
    required: false
  psrtype:
    name: psrtype
    description: Custom classification for this power system resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.PSRType
    multivalued: false
    alias: psrtype
    owner: ACDCConverter
    domain_of:
    - PowerSystemResource
    range: PSRType
    required: false
  configuration_event:
    name: configuration_event
    description: All configuration events created for this Power System resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.ConfigurationEvent
    multivalued: true
    alias: configuration_event
    owner: ACDCConverter
    domain_of:
    - PowerSystemResource
    - FaultCauseType
    range: ConfigurationEvent
    required: false
  reporting_group:
    name: reporting_group
    description: Reporting groups to which this power system resource belongs.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.ReportingGroup
    multivalued: true
    alias: reporting_group
    owner: ACDCConverter
    domain_of:
    - PowerSystemResource
    - BusNameMarker
    - TopologicalNode
    - ReportingSuperGroup
    range: ReportingGroup
    required: false
  operating_share:
    name: operating_share
    description: The operating shares of this power system resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.OperatingShare
    multivalued: true
    alias: operating_share
    owner: ACDCConverter
    domain_of:
    - PowerSystemResource
    - OperatingParticipant
    range: OperatingShare
    required: false
  asset_datasheet:
    name: asset_datasheet
    description: Datasheet information for this power system resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.AssetDatasheet
    multivalued: false
    alias: asset_datasheet
    owner: ACDCConverter
    domain_of:
    - PowerSystemResource
    range: AssetInfo
    required: false
  verification_action:
    name: verification_action
    description: The verification action that is performed on the power system resource
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.VerificationAction
    multivalued: true
    alias: verification_action
    owner: ACDCConverter
    domain_of:
    - PowerSystemResource
    range: VerificationAction
    required: false
  clearances:
    name: clearances
    description: All clearances applicable to this power system resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.Clearances
    multivalued: true
    alias: clearances
    owner: ACDCConverter
    domain_of:
    - PowerSystemResource
    range: ClearanceDocument
    required: false
  generic_action:
    name: generic_action
    description: The generic action that is performed on the power system resource
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.GenericAction
    multivalued: true
    alias: generic_action
    owner: ACDCConverter
    domain_of:
    - PowerSystemResource
    range: GenericAction
    required: false
  psrevents:
    name: psrevents
    description: All events associated with this power system resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.PSREvents
    multivalued: true
    alias: psrevents
    owner: ACDCConverter
    domain_of:
    - PowerSystemResource
    range: PSREvent
    required: false
  assets:
    name: assets
    description: All assets represented by this power system resource. For example,
      multiple conductor assets are electrically modelled as a single AC line segment.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.Assets
    multivalued: true
    alias: assets
    owner: ACDCConverter
    domain_of:
    - PowerSystemResource
    - AssetInfo
    - Location
    - WorkTask
    - ErpRecDelvLineItem
    - AssetContainer
    - ActivityRecord
    - Procedure
    - ReliabilityInfo
    - AssetPropertyCurve
    - AssetOrganisationRole
    - ScheduledEvent
    range: Asset
    required: false
  location:
    name: location
    description: Location of this power system resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.Location
    multivalued: false
    alias: location
    owner: ACDCConverter
    domain_of:
    - PowerSystemResource
    - Asset
    - Incident
    - SwitchingOrder
    - TroubleOrder
    - Crew
    - Fault
    - PointOfSale
    - TroubleTicket
    - OutageOrder
    - EnvironmentalMonitoringStation
    - EnvironmentalLocationType
    - PositionPoint
    - FailureEvent
    range: Location
    required: false
  operational_tags:
    name: operational_tags
    description: All operational tags placed on this power system resource.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:PowerSystemResource.OperationalTags
    multivalued: true
    alias: operational_tags
    owner: ACDCConverter
    domain_of:
    - PowerSystemResource
    - Asset
    range: OperationalTag
    required: false
  alias_name:
    name: alias_name
    description: "The aliasName is free text human readable name of the object alternative\
      \ to IdentifiedObject.name. It may be non unique and may not correlate to a\
      \ naming hierarchy.\r\nThe attribute aliasName is retained because of backwards\
      \ compatibility between CIM relases. It is however recommended to replace aliasName\
      \ with the Name class as aliasName is planned for retirement at a future time.\r\
      \n\r\n"
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:IdentifiedObject.aliasName
    multivalued: false
    alias: alias_name
    owner: ACDCConverter
    domain_of:
    - IdentifiedObject
    range: string
    required: false
  description:
    name: description
    description: The description is a free human readable text describing or naming
      the object. It may be non unique and may not correlate to a naming hierarchy.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:IdentifiedObject.description
    multivalued: false
    alias: description
    owner: ACDCConverter
    domain_of:
    - IdentifiedObject
    - NameType
    - NameTypeAuthority
    - DataSet
    - SwitchingStepGroup
    - AreaReserveSpec
    range: string
    required: false
  m_rid:
    name: m_rid
    description: "Master resource identifier issued by a model authority. The mRID\
      \ is unique within an exchange context. Global uniqueness is easily achieved\
      \ by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is\
      \ strongly recommended.\r\nFor CIMXML data files in RDF syntax conforming to\
      \ IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify\
      \ CIM object elements."
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:IdentifiedObject.mRID
    multivalued: false
    alias: m_rid
    owner: ACDCConverter
    domain_of:
    - IdentifiedObject
    - DataSet
    range: string
    required: false
  diagram_objects:
    name: diagram_objects
    description: The diagram objects that are associated with the domain object.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:IdentifiedObject.DiagramObjects
    multivalued: true
    alias: diagram_objects
    owner: ACDCConverter
    domain_of:
    - IdentifiedObject
    range: DiagramObject
    required: false
  instance_set:
    name: instance_set
    description: Dataset containing the data objects.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:IdentifiedObject.InstanceSet
    multivalued: false
    alias: instance_set
    owner: ACDCConverter
    domain_of:
    - IdentifiedObject
    range: InstanceSet
    required: true
  names:
    name: names
    description: All names of this identified object.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:IdentifiedObject.Names
    multivalued: true
    alias: names
    owner: ACDCConverter
    domain_of:
    - IdentifiedObject
    - NameType
    range: Name
    required: false
  properties_cimdata_object:
    name: properties_cimdata_object
    description: The single CIM data object in the appropriate dataset context.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:IdentifiedObject.PropertiesCIMDataObject
    multivalued: false
    alias: properties_cimdata_object
    owner: ACDCConverter
    domain_of:
    - IdentifiedObject
    range: ChangeSetMember
    required: false
  targeting_cimdata_object:
    name: targeting_cimdata_object
    description: Data objects registered.
    from_schema: https://cim.ucaiug.io/ns#TC57CIM
    rank: 1000
    slot_uri: cim:IdentifiedObject.TargetingCIMDataObject
    multivalued: true
    alias: targeting_cimdata_object
    owner: ACDCConverter
    domain_of:
    - IdentifiedObject
    range: ChangeSetMember
    required: false
class_uri: cim:ACDCConverter